When accessing the SERVICE tables, a password must be entered. The password can be changed from the
Configuration Menu. USER CONFIGURATION allows change of the User access password. SERVICE
PARAMETERS allows change of the Advanced User/Service password, and FACTORY PARAMETERS allows
change of the Factory password. Passwords must be 4 digits (from 1111 to 9999).
IMPORTANT: Be sure to remember the password. Retain a copy for future reference. Without the password, access
to the SERVICE menu will not be possible unless accessed by a Carrier representative.
LOGIN/LOGOUT
— Press the lock icon on the home screen to enter the password.
Fig 47: Lock icon
The User Login Screen is displayed. Enter the password on this screen. The language and system of
measurement can also be changed on this screen. For details, see the PIC 5+ Controls Operation and
Troubleshooting guide.
INPUT TIME AND DATE
— Set day and time and if applicable Holidays through MAIN MENU -
CONFIGURATION MENU and then select appropriate icon. See the Controls Operation and Troubleshooting
guide for details. Because a schedule is integral to the chiller control sequence, the chiller will not start until the
time and date have been set.
NOTE: The date format is MM-DD-YY for English units and DD-MM-YY for SI units.
MODIFY CONTROLLER IDENTIFICATION IF NECESSARY
— The CCN address can be changed from the
Configuration Menu. Change this address under CONTROL IDENTIFICATION for each chiller if there is more than
one chiller at the jobsite. Write the new address on the PIC5+ Touch Screen module for future reference.
CONFIGURE TABLES
— Access the related tables through MAIN MENU CONFIGURATION MENU to modify or
view job site parameters shown in 19DV Configuration tables. Table 19 should be verified or configured during
startup/commissioning. Consult chiller nameplates as indicated.
TABLE
FACTORY - Factory Parameters
Access Menu
Configuration Menu / Factory parameters
Setting
Range
Units Default value
Settings value
Chiller Type
19XR6/7=0,
19XR2~E/D/V=1,
19DV=2
0 to 2
-
0
2
Unit Type
Cool Only=0,Heat Mach=1
0 to 1
-
0
per selection
Comp (Single = 0, Dual = 1)
0 to 1
-
1
1
Chilled Medium Type Water/brine
Water/Brine
-
Water
per selection
Cond Shell Side MAWP
185PSI=0, 300PSI=1
0 to 1
-
0
0
19DV Comp Design Pressure
300 kPa = 0, 500 kPa= 1
0 to 1
-
0
0
Country Code
0 to 999
-
86
33
Free Cooling Option
No/yes
-
NO
per selection
VFD Option No=0,FS VFD=1,Carrier=2
RockwellLF2=3, Eaton=4, Rockwell Std=5,
ABB=6, Danfoss=7
0 to 7
-
0
1, 3, or 7 per
selection
IOB3 option (19XR2~E/D/V)
No/yes
-
Yes
Yes
Summary of Contents for PIC 5+
Page 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Page 52: ...52 Fig 24 19DV control box ...
Page 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Page 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Page 57: ...57 ...
Page 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Page 114: ...114 Detailed menu description ...
Page 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...