![Carrier PIC 5+ Installation, Operation And Maintenance Instructions Download Page 84](http://html.mh-extra.com/html/carrier/pic-5/pic-5_installation-operation-and-maintenance-instructions_2562218084.webp)
84
ECV On DT for Low Load
1,1 °C
1,1 °C (adjust as required)
ECV Low Load DB
0,6 °C
0,6 °C (adjust as required)
Head Pres Valve Option
Dsable
job site specific
Head Pres Delta P 0%
172,4 kPa
172,4 kPa (adjust as required)
Head Pres Delta P 100%
344,7 kPa
344,7 kPa (adjust as required)
Head Pressure Min Output
0%
0% (adjust as required)
Tower Fan High Setpoint
24 °C
24 °C (adjust as required)
Refrig Leakage Option
Dsable
job site specific
Refrig Leak Alarm mA
20 mA
20 mA (adjust as required)
Oil EXV Option
Dsable
Dsable
Oil Temp High Threshold
50 °C
N/A
Oil Temp Low Threshold
45 °C
N/A
Gas Torque Factor
1
1
Guide Vane/SRD Factor
0.95
0.95
Power Recovery Timeout
15 min
15 min
Condenser Flush Alert
Dsable
Dsable
Customer Alert Option
Dsable
job site specific
Ice Build Option
Dsable
job site specific
Ice Build Recycle
Dsable
job site specific
Ice Build Termin Source
Temp=0,Contact=1,Both=2
0
job site specific
Water Pressure Option
No=0, Flow Meter=1, Water Pres. D=2
0
1
Water Flow Measurement
No=0, Flow Meter=1,Water PD=2
0
0
Water Flow Determination
Sat Temp=0,Flow Switch=1
0
job site specific
Water Flow at 4mA
0 l/sec
adjust as required
Water Flow at 20mA
0 l/sec
adjust as required
Evap Flow Rate Baseline
0 l/sec
adjust as required
Evap Pres Drop Baseline
0 kPa
adjust as required
Cond Flow Rate Baseline
0 l/sec
adjust as required
Cond Pres Drop Baseline
0 kPa
adjust as required
Water Pres Drop @20mA
68,95 kPa
adjust as required
Max Oil Pressure Diff
344,7 kPa
N/A
Oil Pump VFD Max Step
7%
N/A
Vapor Source SV Delay
5 min
N/A
Vapor Source SV Option
Dsable
N/A
Liquid Bypass Selection
Dsable
per selection
Purge on Idle option
Dsable
adjust as required for force
Evap Liquid Temp Opt
Enable
N/A
Evap App Calc Selection
Sat Temp=0, Ref Temp=1
1
1
TABLE
SERVICE - Service Parameters
Access Menu
Configuration Menu / Service parameters
Setting
Default value (SI units)
Settings value (SI)
Atmospheric Pressure
99,978 kPa
*
GV1 Travel Limit
80.70%
*
GV1 Closure at Startup
4.00%
*
Controlled Fluid DB
0,6°C
*
Derivatived EWT Gain
2
*
Proportional Dec Band
6
*
Proportional Inc Band
6.5
*
Maximum GV Movement
2.00%
*
Demand Limit at 20 mA
40%
*
Demand Limit Prop Band
10%
*
Amps or KW Ramp per Min
5%
*
Temp Ramp per Min
1,7°C
*
Recycle Shutdown Delta T
0,6°C
*
Recycle Restart Delta T
2,8°C
*
Damper Valve Act Delay
2 min
*
Damper Valve Close DB
34,5 kPa
*
Damper Valve Open DB
89,6 kPa
*
Damper Action Delta T
3,9°C
*
Oil Press Verify Time
40 sec
*
Soft Stop Amps Threshold
70%
*
Water flow verify Time
5 min
*
Power calibration factor
1
*
Purge Active Temp SP
18.3
*
Summary of Contents for PIC 5+
Page 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Page 52: ...52 Fig 24 19DV control box ...
Page 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Page 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Page 57: ...57 ...
Page 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Page 114: ...114 Detailed menu description ...
Page 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...