background image

Installation, Start-up, Operating and Service and Maintenance 

Instructions

NOTE: 

Read the entire instruction manual before starting the 

installation.

Approved for installations up to 5,400 feet (1646 meters)

TABLE OF CONTENTS

Table 1 – Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INTRODUCTION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE

-

DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

LOCATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 6

Table 2 – Minimum Free Area Required for Each Combustion Air 

Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Table 3 – Minimum Space volumes for 100% combustion, Ventila

-

tion, and Dilution from Indoors . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Table 4 – Opening Dimensions - In. (mm)  . . . . . . . . . . . . . . . . . 10

FILTER ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Table 5 – Maximum Capacity of Pipe* . . . . . . . . . . . . . . . . . . . . 13

ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Table 6 – Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Table 7 – Combined Appliance Maximum Input Rating in Thousands 

of BTUh per Hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Table 8 – Minimum Allowable Input Rating of Space-Heating Appli

-

ance in Thousands of BTUh per Hour . . . . . . . . . . . . . . . . . . . . . 17

AIR DELIVERY - CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Table 9 – Air Delivery - CFM (with filter) . . . . . . . . . . . . . . . . . 20

Table 10 – Airflow Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

FURNACE CONTROL PROGRAMMING AND NAVIGATION  21

Table 11 – System Status Display Codes. . . . . . . . . . . . . . . . . . . 21

Table 12 – Main Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . 22

SERVICE LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

START-UP, ADJUSTMENT, AND SAFETY CHECK . . . . . . . . . 24

Table 13 – Test Sequence  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Table 14 – Altitude Derate Multiplier for U.S.A. . . . . . . . . . . . . 26

Table 15 – Gas Rate (Cu Ft./Hr.) . . . . . . . . . . . . . . . . . . . . . . . . . 26

Table 16 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude 

- 40,000  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Table 17 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude 

- 60,000  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Table 18 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude 

- 80,000  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Table 19 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude 

- 100,000  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 30

CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Table 20 – Filter Size Information (In. / mm) . . . . . . . . . . . . . . . 31

SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 40

MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
To learn more about this appliance and installation via a mobile device,

go to 

https://www.payne.com/NFC

 or use the QR code below. To access

airflow  tables  or  troubleshooting  guide  on  your  mobile  device  go  to

mlctraining.com/training/techdocs/38/

 or use the QR code below.

A220949

A200103

Most  states  in  the  USA  and  jurisdictions  in  Canada  have  laws  that

require  the  use  of  Carbon  Monoxide  (CO)  alarms  with  fuel  burning

products. Examples of fuel burning products are furnaces, boilers, space

heaters,  generators,  water  heaters,  stoves/ranges,  clothes  dryers,

fireplaces,  incinerators,  automobiles,  and  other  internal  combustion

engines. Even if there are no laws in your jurisdiction requiring a CO

Alarm, it’s highly recommended that whenever any fuel burning product

is used in or around the home or business that the dwelling be equipped

with  a  CO  Alarm(s).  The  Consumer  Product  Safety  Commission

recommends  the  use  of  CO  Alarm(s).  The  CO  Alarm(s)  must  be

installed,  operated,  and  maintained  according  to  the  CO  Alarm

manufacturer’s  instructions.  For  more  information  about  Carbon

Monoxide, local laws, or to purchase a CO Alarm online, please visit the

following website. https://www.kidde.com.

Portions of the text and tables are reprinted from current edition of NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, 

Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the 

NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.

PG80MSU

80% AFUE, Single Stage, ECM Motor, Ultra Low NOx,

4-Way Multipoise, Non-Condensing, Gas Furnace

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  and/or

death.

Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous

gas that can be fatal when inhaled. Follow all installation, maintenance,

and  service  instructions.  See  additional  information  below  regarding

the installation of a CO Alarm.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: