Adjustments
1. Determine the correct gas input rate. Refer to the unit rating plate.
The input rating for altitudes above 2,000 ft. (610 M) must be
reduced by 2 percent for each 1,000 ft. (305 M) above sea level. For
installations below 2,000 ft. (610 M), refer to the unit rating plate.
For installation above 2,000 ft. (610 M), multiply the input on the
rating plate by the derate multiplier in
rate.
A180238
Fig. 37 – Orifice Hole
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in injury, death and/or
property damage.
DO NOT bottom out gas valve regulator adjusting screw. This can
result in unregulated gas valve outlet pressure and result in excess
overfire and heat exchanger failures.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,
etc.) can cause excessive burner noise and misdirection of inlet gas, see