background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

32

d. Remove bolts holding motor to blower housing and slide motor 

out of wheel (40+/-10 in.-lb. when reassembling).

e. Remove blower wheel from housing.

f. Clean wheel and housing.

9. Reassemble motor and blower by reversing steps 8f finishing with

8a. Be sure to reattach ground wire to the blower housing.

10. Verify  that  blower  wheel  is  centered  in  blower  housing  and  set

screw contacts the flat portion of the motor shaft. Loosen set screw

on blower wheel and reposition if necessary.

11. Spin the blower wheel by hand to verify that the wheel does not rub

on the housing.

12. Reinstall blower assembly in furnace.
13. Reinstall two screws securing blower assembly to blower deck.

NOTE: 

Refer to 

Table 9

 for motor speed lead relocation if leads were

not identified before disconnection.

14. Refer to  furnace

 

wiring  diagram, and  connect  thermostat leads if

previously

 

disconnected.

15. To check blower for proper rotation:

a. Turn on electrical supply.

b. Manually close blower access door switch.

c. Verify blower is rotating in the correct direction.

16. If  furnace  is  operating  properly,  RELEASE  BLOWER ACCESS

DOOR  SWITCH.  Remove  any  jumpers  or  reconnect

 

any

disconnected thermostat leads. Replace blower access

 

door.

17. Reinstall outer door.
18. Cycle  furnace  through  one  complete

 

heating  and  cooling  cycle.

Verify  the  furnace  temperature  rise

 

as  shown  in  “Adjustments”

Section.  Adjust  temperature  rise  as

 

shown  in  “Adjustments”

Section.  If  outdoor  temperature  is

 

below  70°F,  (21°C)  turn  off

circuit breaker to outdoor unit before

 

running furnace in the cooling

cycle.  Turn  outdoor  circuit

 

breaker  on  after  completing  cooling

cycle.

 

Flame Sensor Cleaning and Servicing Igniter

Cleaning Flame Sensor

The  following  items  must  be  performed  by  a  qualified  service

technician. If the flame sensor develops an accumulation of light dirt or

dust, it may be cleaned by using the following procedure:

Refer to 

Fig. 38

.

1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect Flame Sensor wire from Flame Sensor.
6. Remove the flame sensor from the burner assembly.
7. (Optiona

l) Remove the Hot Surface Igniter (HSI) and bracket with

igniter gasket

 from the burner assembly.

8. Check  igniter  resistance.  Nominal resistance  is 40 to  70  ohms  at

room temperature and is stable over the life of the igniter.

9. Clean the flame sensor with fine steel wool (0000 grade). Do not

use sand paper or emery cloth.

To reinstall igniter and flame sensor:

1. Install the Hot Surface Igniter (HSI) and bracket with igniter gasket

into burner assembly.

2. Install flame sensor into burner assembly.
3. When installing the HSI and flame sensor, 

¼

” screws that are the

same  size  of  those  removed  must  be  used.  Do  not  use  longer

screws.

NOTE: 

If  insulation  assembly  is  damaged,  do  not  attempt  to  repair,

must be replaced with insulation kit.

NOTE: 

Proper  use  of  Personal  Protective  Equipment  (PPE)  must  be

followed,  including  safety  glasses,  gloves,  and  dust  mask  when

removing and reinstalling the heat exchanger insulation assembly.

4. Connect the wire for the flame sensor.
5. Connect the wire for the Hot Surface Igniter.

6. Turn gas on at electric switch on gas valve and at external shut-off

or meter

7. Turn power on at external disconnect, fuse or circuit breaker.
8. Run the furnace through two complete heating cycles to check for

proper operation

9. Install control door when complete.

Cleaning Heat Exchanger

The following steps should be performed by a qualified service agency: 

NOTE: 

If  the  heat  exchangers  get  a  heavy  accumulation  of  soot  and

carbon,  they  should  be  replaced  rather  than  trying  to  clean  them

thoroughly.  A  heavy  build-up  of  soot  and  carbon  indicates  that  a

problem exists which needs to be corrected, such as improper adjustment

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in shortened heat exchanger

life. 
Heating  fan  speed(s)  MUST  be  adjusted  to  provide  proper  air

temperature  rise  as  specified  on  the  rating  plate.  Recommended

operation is at the midpoint of the rise range or slightly above. Refer to

“SET TEMPERATURE RISE” under START-UP, ADJUSTMENT, and

SAFETY CHECK.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death. 

Blower access door switch opens 115-V power to furnace control. No

component  operation  can  occur  unless  switch  is  closed.  Exercise

caution to avoid electrical shock from exposed electrical components

when manually closing this switch for service purposes.

WARNING

!

ELECTRICAL SHOCK AND FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death,

and/or property damage. 

Turn off the gas and electrical supplies to the furnace and install lockout

tag before performing any maintenance or service. Follow the operating

instructions on the label attached to the furnace. 

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death,

and/or property damage. 

Never purge a gas line into a combustion chamber. Never test for gas

leaks with an open flame. Use a commercially available soap solution

made specifically for the detection of leaks to check all connections. A

fire or explosion may result causing property damage, personal injury

or loss of life.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: