background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

34

A190291

Fig. 39 – Cleaning Heat Exchanger Cell

SEQUENCE OF OPERATION 

NOTE: 

Furnace  control  must  be  grounded  for  proper  operation  of

furnace  control  and  flame  sensing  electrode.  Control  is  grounded

through  green/yellow  wire  routed  to  gas  valve  and  burner  box  screw.

Using  the  schematic  diagram  in 

Fig. 36

,  follow  the  sequence  of

operation  through  the  different  modes.  Read  and  follow  the  wiring

diagram very carefully.

NOTE: 

If  a  power  interruption  occurs  during  a  call  for  heat  W,  the

control  will  start  a  90-second  blower-only  ON  period  2  seconds  after

power is restored, if the thermostat is still calling for gas heating. The

LED light will flash code 12 and display will show (

12.1

) during the

90-second period, after which the LED will be ON continuous, as long

as  no  faults  are  detected. After  the  90-second  blower-ON  period,  the

furnace will respond to the thermostat normally. 
The blower door must be installed for power to be conducted through the

blower  door  interlock  switch  ILK  to  the  furnace  control  CPU,

transformer  TRAN,  inducer  motor  IDM,  blower  motor  BLWM,

hot-surface igniter HSI, and gas valve GV. 

1.

Call for Heat: 

The wall thermostat “calls for heat”, closing the R

-

W circuit. The

furnace control performs a self-check, verifies the transducer reads

no  pressure  present,  and  starts  the  inducer  motor  IDM  ramp  to

prepurge

a.

Inducer Prepurge Period: 

The furnace control CPU ramps up 

the inducer motor IDM to prepurge pressure then the furnace 

control CPU begins a 15-second prepurge period. If the 

transducer fails to reach target pressure the inducer motor IDM 

will remain running until target pressure is maintained. 

b.

Igniter Warm-Up: 

At the end of the prepurge period, the 

Hot-Surface Igniter HSI is energized for a 17-second igniter 

warm-up period. Inducer maintains pressure during igniter 

warm-up. If inducer prepurge and igniter warm up sequence is 

not completed in 5 minutes, the unit will shut down and LED 

light will flash code 31. Retry occurs after 2 minutes.

c.

Trial for Ignition:

 When the igniter warm-up period is 

completed the main gas valve relay contact GVR closes to 

energize the gas valve solenoid GV. The gas valve solenoid GV 

permits gas flow to the burners where it is ignited by the HSI. 

Five seconds after the GVR closes, a 2-second flame proving 

period begins. The HSI igniter will remain energized until the 

flame is sensed or until the 2-second flame proving period 

begins.

d.

Flame Proving:

 When the burner flame is proved at the flame 

sensor electrode FSE, the inducer motor IDM will increase speed 

(after a short delay of 14 seconds on some modes) to a higher 

RUN pressure. The control will maintain this pressure once 

reached, and the furnace control CPU will begin the blower-ON 

delay period while continuing to hold the gas valve GV open. If 

the burner flame is not proved within the 2-second flame proving 

period, the control CPU will open the gas valve relay GVR, 

de-energizing the gas valve solenoid GV. The control CPU will 

repeat the ignition sequence for up to three more 

Trials-for-Ignition before going to an Ignition-Lockout. Lockout 

will be reset automatically after 3 hours, or by momentarily 

interrupting 115 VAC power to the furnace, or by interrupting 24 

VAC power at SEC1 or SEC2 to the furnace control CPU (not at 

W, G, R, etc.). If flame is proved when flame should not be 

present, the furnace control CPU will lock out of Heating mode 

and operate the inducer motor IDM until flame is no longer 

proved. 

e.

Blower-ON Delay:

 If the burner flame is proven, the blower 

motor is turned on at HEAT speed 25 seconds after the gas valve 

GV is energized.

Simultaneously, the humidifier terminal HUM and electronic air 

cleaner terminal EAC-1 are energized and remain energized 

throughout the heating cycle. 

f.

Blower-OFF Delay:

 When the thermostat is satisfied, the R to 

W circuit is opened, de-energizing the gas valve GV, stopping 

gas flow to the burners, and de-energizing the humidifier 

terminal HUM. The inducer motor IDM will remain energized 

for a 15-second post-purge period. The blower motor BLWM and 

air cleaner terminal EAC-1 will remain ON at heat airflow for 

90, 120, 150, or 180 seconds (depending on the blower-OFF 

delay selection). The furnace control CPU is factory-set for a 

120-second blower-OFF delay.

2. The thermostat “calls for cooling”.

a.

Single-Speed Cooling

The thermostat closes the R-to-G-and-Y circuits. The R-to-Y 

circuit starts the outdoor unit, and the R-to-G-and-Y/Y2 circuits 

start the furnace blower motor BLWM on COOL speed. The 

electronic air cleaner terminal EAC-1 is energized with 115 VAC 

when the blower motor BLWM is operating. 

When the thermostat is satisfied, the R-to-G-and-Y/Y2 circuits 

are opened. The outdoor unit will stop, and the furnace blower 

motor BLWM will continue operating on the COOL speed for an 

additional 5, 30, or 90 seconds (depending on the cooling 

blower-OFF delay selection). The furnace CPU is factory set for 

a 90 second cooling blower-OFF delay. (See 

Fig. 36

).

b. Two-Stage Thermostat and Two-Speed Cooling

The thermostat closes the R-to-G-and-Y1 circuits for 

low-cooling or closes the R-to-G-and-Y1-and-Y/Y2 circuits for 

high-cooling. The R-to-Y1 circuit starts the outdoor unit on 

low-cooling speed, and the R-to-G-and-Y1 circuit starts the 

furnace blower motor BLWM at low-cooling airflow. The 

R-to-Y1-and-YY/2 circuits start the outdoor unit on high-cooling 

speed, and the R-to-G-and-Y/Y2 circuits start the furnace blower 

motor BLWM at high-cooling airflow. Terminal EAC-1 is 

energized with as long as the blower motor BLWM is ON.

When the thermostat is satisfied, the R-to-G-and-Y1 or R-to- 

G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, 

and the furnace blower BLWM and electronic air cleaner 

terminal EAC-1 will remain energized for an additional 

90-seconds.

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death

and/or property damage. 

Never purge a gas line into a combustion chamber. Never test for gas

leaks with an open flame. Use a commercially available soap solution

made specifically for the detection of leaks to check all connections.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: