background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

26

Table 14 – Altitude Derate Multiplier for U.S.A

.

Furnace gas input rate on rating plate is for installations at altitudes up to

2,000  ft.  (610  M).  Furnace  input  rate  must  be  within  +/-2  percent  of

furnace rating plate input.

2. Determine the correct outlet gas pressure adjustment.

a. Obtain average yearly gas heat value (at installed altitude) from 

local gas supplier.

b. Obtain average yearly gas specific gravity from local gas 

supplier.

c. Find closest natural gas heat value and specific gravity in 

Table 16

 through 

Table 19

.

d. Follow heat value and specific gravity lines to point of 

intersection to find outlet pressure setting for proper operation.

3. Check Inlet Gas Pressure

The inlet gas pressure must be checked with the furnace operating. This

is necessary to make sure the inlet gas pressure does not fall below the

minimum pressure of 4.5 in. w.c.

a. Make sure the gas supply is turned off to the furnace and at the 

electric switch on the gas valve

b. Loosen set screw on inlet tower pressure tap no more than one 

full turn with a 3/32−in. hex wrench or remove the 1/8−in. NPT 

plug from the inlet pressure tap on the gas valve.

c. Connect a manometer to the inlet pressure tap on gas valve.

d. Turn on furnace power supply.

e. Turn gas supply manual shutoff valve to ON position.

f. Turn furnace gas valve switch to ON position.

g. Jumper R and W thermostat connections at the furnace control 

board.

h. When main burners ignite, confirm inlet gas pressure is between 

4.5 in. w.c. (1125 Pa) and 13.6 in. w.c. (3388 Pa).

i. Remove jumper across thermostat connections to terminate call 

for heat. Wait until the blower off delay is completed.

j. Turn furnace gas valve electric switch to OFF position.

k. Turn gas supply manual shutoff valve to OFF position.

l. Turn off furnace power supply.

m.Remove manometer from the inlet pressure tap of the gas valve.

n. Tighten set screw on inlet tower pressure tap with 3/32−in. hex 

wrench, or if 1/8−in. NPT plug was removed, apply pipe dope 

sparingly to end of plug and reinstall in the gas valve

4. Adjust  gas  valve  outlet  pressure  determined  in  Step  2  to  obtain

correct input rate.

a. Turn gas valve ON/OFF switch to OFF.

b. Loosen set screw on outlet tower pressure tap no more than one 

full turn with a 3/32 in. hex wrench, see 

Fig. 21

.

c. Connect a water column manometer or similar device to pressure 

tap on the gas valve.

d. Turn gas valve ON/OFF switch to ON.

e. Manually close blower door switch.

f. Set thermostat to call for heat.

g. Remove regulator seal cap and turn regulator adjusting screw 

counterclockwise (out) to decrease input rate of clockwise (in) to 

increase input rate.

h. Install regulator seal cap.

i. Leave manometer or similar device connected and proceed to 

next step. 

NOTE: 

If orifice hole appears damaged or it is suspected to have been

redrilled, check  orifice  hole  with  a  numbered drill  bit  of  correct  size.

Never  redrill  an  orifice. A  burr-free  and  properly  sized  orifice  hole  is

essential for proper flame characteristics. 

Table 15 – Gas Rate (Cu Ft./Hr.)

5. Verify natural gas input rate by clocking meter. 

NOTE: 

Gas valve regulator adjustment cap must be in place for proper

input to be clocked.

a. Turn off all other gas appliances and pilots served by the meter.

b. Run furnace for 3 minutes in heating operation.

c. Measure time (in seconds) for gas meter to complete 1 revolution 

and note reading. The 2 or 5 cubic feet dial provides a more 

accurate measurement of gas flow.

d. Refer to 

Table 15

 for cubic ft. of gas per hr.

ALTITUDE 

(FT. /  M) 

PERCENT 

OF

DERATE 

DERATE

MULTIPLIER 

FACTOR

*

 

*. Derate multiplier factors are based on midpoint altitude for altitude range

0–2000 (0-610)

1.00 

2001–3000 (610-914)

4-6

0.95 

3001–4000 (914-1219)

6-8

0.93 

4001–5000 (1219-1524)

8-10

0.91 

5001–5400 (1525-1646)

10-11

0.90 

WARNING

!

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death,

and/or property damage.

Inlet  pressure  tap  set  screw  must  be  tightened  and  1/8-in.  NPT  pipe

plug must be installed to prevent gas leaks.

SECONDS 

FOR 1 REV 

SIZE OF TEST DIAL  SECONDS 

FOR 1 REV 

SIZE OF TEST 

DIAL 

1 Cu 

Ft. 

2 Cu 

Ft. 

5 Cu 

Ft. 

1 Cu 

Ft. 

2 Cu 

Ft. 

5 Cu 

Ft. 

10 

360 

720  1800 

50 

72 

144  360 

11 

327 

655  1636 

51 

71 

141  355 

12 

300 

600  1500 

52 

69 

138  346 

13 

277 

555  1385 

53 

68 

136  340 

14 

257 

514  1286 

54 

67 

133  333 

15 

240 

480  1200 

55 

65 

131  327 

16 

225 

450  1125 

56 

64 

129  321 

17 

212 

424  1059 

57 

63 

126  316 

18 

200 

400  1000 

58 

62 

124  310 

19 

189 

379 

947 

59 

61 

122  305 

20 

180 

360 

900 

60 

60 

120  300 

21 

171 

343 

857 

62 

58 

116  290 

22 

164 

327 

818 

64 

56 

112  281 

23 

157 

313 

783 

66 

54 

109  273 

24 

150 

300 

750 

68 

53 

106  265 

25 

144 

288 

720 

70 

51 

103  257 

26 

138 

277 

692 

72 

50 

100  250 

27 

133 

267 

667 

74 

48 

97 

243 

28 

129 

257 

643 

76 

47 

95 

237 

29 

124 

248 

621 

78 

46 

92 

231 

30 

120 

240 

600 

80 

45 

90 

225 

31 

116 

232 

581 

82 

44 

88 

220 

32 

113 

225 

563 

84 

43 

86 

214 

33 

109 

218 

545 

86 

42 

84 

209 

34 

106 

212 

529 

88 

41 

82 

205 

35 

103 

206 

514 

90 

40 

80 

200 

36 

100 

200 

500 

92 

39 

78 

196 

37 

97 

195 

486 

94 

38 

76 

192 

38 

95 

189 

474 

96 

38 

75 

188 

39 

92 

185 

462 

98 

37 

74 

184 

40 

90 

180 

450 

100 

36 

72 

180 

41 

88 

176 

439 

102 

35 

71 

178 

42 

86 

172 

429 

104 

35 

69 

173 

43 

84 

167 

419 

106 

34 

68 

170 

44 

82 

164 

409 

108 

33 

67 

167 

45 

80 

160 

400 

110 

33 

65 

164 

46 

78 

157 

391 

112 

32 

64 

161 

47 

76 

153 

383 

116 

31 

62 

155 

48 

75 

150 

375 

120 

30 

60 

150 

49 

73 

147 

367 

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: