PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
A89014
Fig. 10 – Leveling Legs
2. For each leg, install nut on bolt and then install bolt and nut in hole.
(Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer
if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut
to secure arrangement.
5. Reinstall bottom closure panel if removed.
Downflow Installation
NOTE:
For downflow applications, this furnace is approved for use on
combustible flooring when any one of the following 3 accessories are
used:
• Manufacturer’s approved downflow combustible floor subbase
• Manufacturer’s approved cased evaporator coil
• Manufacturer’s approved evaporator coil casing
1. Determine application being installed from
.
2. Construct hole in floor per
.
3. Construct plenum to dimensions specified in
4. If downflow subbase is used, install as shown in
. If
manufacturer’s cased evaporator coil or coil casing is used, install
.
NOTE:
It is required that the perforated supply-air duct flanges be
completely folded over or removed from furnace when installing the
furnace on a factory-supplied cased coil or coil box. To remove the
supply-air duct flange, use wide duct pliers or hand seamers to bend
flange back and forth until it breaks off. Be careful of sharp edges, see
.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws
A96283
Fig. 11 – Floor and Plenum Opening Dimensions
A96285
Fig. 12 – Furnace, Plenum, and Subbase Installed
on a Combustible Floor
A08556
Fig. 13 – Furnace, Plenum, and Coil Assembly or
Coil Box Installed on a Combustible Floor
WARNING
!
FIRE AND PROPERTY HAZARD
Failure to follow this warning could result in equipment damage,
personal injury, or property damage.
When furnace is installed in a downflow application, make sure water
lines and other sources of water cannot drip or fail in such a way that
water can collect on the blower motor, wiring, and furnace control
board.