background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

13

1. Gas supply connections MUST be performed by a licensed plumber

or gas fitter.

2. When flexible connectors are used, the maximum length shall not

exceed 36 inches (915 mm).

3. When lever handle type manual equipment shutoff valves are used,

they shall be T-handle valves.

4. The use of copper tubing for gas piping is NOT approved by the

state of Massachusetts. 

Refer to 

Table 5

 for recommended gas pipe sizing. Risers must be used

to  connect  to  furnace  and  to  meter.  Support  all  gas  piping  with

appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft.

(2 M). Joint compound (pipe dope) should be applied sparingly and only

to male threads of  joints. Pipe dope must be resistant to  the action of

propane gas.

 

* Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14-in. w.c.) or less and a 

pressure drop of 0.5-in. w.c. (based on a 0.60 specific gravity gas). Ref: Chapter 6 current 

edition of ANSI Z223/NFPA 54.

An  accessible  manual  equipment  shutoff  valve  MUST  be  installed

external to furnace casing and within 6 ft. (2 M) of furnace. A 1/8-in. (3

mm) NPT plugged tapping, accessible for test gauge connection, MUST

be installed immediately upstream of gas supply connection to furnace

and downstream of manual equipment shutoff valve. 

NOTE: 

The furnace gas control valve inlet pressure tap connection is

suitable to use as test gauge connection providing test pressure DOES

NOT exceed maximum 0.5 psig (14-in. w.c.) stated on gas control valve,

see 

Fig. 21

. 

A180231

Fig. 21 – Gas Control Valve

Install a sediment trap in riser leading to furnace as shown in 

Fig. 22

.

Connect a  capped nipple into lower end of  tee. Capped  nipple should

extend below level of furnace gas controls. Place a ground joint union

between furnace gas control valve and exterior manual equipment gas

shutoff valve. A 1/8-in. (3 mm) NPT plugged tapping, accessible for test

gauge  connection,  MUST  be  installed  immediately  upstream  of  gas

supply  connection  to  furnace  and  downstream  of  manual  equipment

shutoff valve.

A02035

Fig. 22 – Typical Gas Pipe Arrangement

Piping should be pressure and leak tested in accordance with NFGC in

the United States, local, and national plumbing and gas codes before the

furnace  has  been  connected.  After  all  connections  have  been  made,

purge lines and check for leakage at furnace prior to operating furnace. 
If  pressure  exceeds  0.5  psig  (14-in.  w.c.),  gas  supply  pipe  must  be

disconnected  from  furnace  and  capped  before  and  during  supply  pipe

pressure test. If test pressure is equal to or less than 0.5 psig (14-in. w.c.),

turn off electric shutoff switch located on furnace gas control valve and

accessible  manual  equipment  shutoff  valve  before  and  during  supply

pipe pressure test. After all connections have been made, purge lines and

check for leakage at furnace prior to operating furnace. 
The  gas  supply  pressure  shall  be  within  the  maximum  and  minimum

inlet  supply  pressures  marked  on  the  rating  plate  with  the  furnace

burners ON and OFF. 

ELECTRICAL CONNECTIONS

See 

Fig. 23

 for field wiring diagram showing typical field 115-V wiring.

Check all factory and field electrical connections for tightness.

Table 5 – Maximum Capacity of Pipe*

NOMINAL 

IRON 

PIPE 

INTERNAL 

DIAMETER 

LENGTH OF PIPE - FT. (M) 

SIZE IN. 

(mm) 

In. (mm) 

10 

20 

30 

40 

50 

1/2 (13)

0.622 (16)

175 (53)

120 (37) 

97 (30)

82 (25)

73 (22)

3/4 (19)

0.824 (21) 360 (110)

250 (76) 

200 (61)  170 (52)  151 (46)

1 (25)

1.049 (27) 680 (207)  465 (142)  375 (114)  320 (98)  285 (87) 

1-1/4 (32)  1.380 (35) 1400 (427)  950 (290) 770 (235)  660 (201)  580 (177) 
1-1/2 (38) 1.610 (41) 2100 (640)  1460 (445)  1180 (360)  990 (301)  900 (274) 

WARNING

!

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings could result in dangerous operation,

serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious injury,

death or property damage.

-

Before servicing, disconnect all electrical power to furnace.

-

When servicing controls, label all wires prior to disconnecting.

Reconnect wires correctly.

-

Verify proper operation after servicing.

-

Always  reinstall  access  doors  after  completing  service  and

maintenance.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Blower  access  panel  door  switch  opens  115-V  power  to  control.  No

component  operation  can  occur.  Do  not  bypass  or  close  switch  with

panel removed.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: