background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

CODES AND STANDARDS

Follow all national and local  codes and  standards in  addition to these

instructions.  The  installation  must  comply  with  regulations  of  the

serving gas supplier, local building, heating, plumbing, and other codes.

In absence of local codes, the installation must comply with the national

codes listed below and all authorities having jurisdiction. 

In the United States, follow all codes and standards for the following:

Safety

• USA:  Current  edition  of  National  Fuel  Gas  Code  (NFGC)  NFPA

54/ANSI  Z223.1  and  the  Installation  Standards,  Warm Air  Heating

and Air Conditioning Systems ANSI/NFPA 90B

General Installation

• Current edition of the NFGC and the NFPA 90B. For copies, contact

the  National  Fire  Protection  Association  Inc.,  Batterymarch  Park,

Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact

the  American  Gas  Association,  400  N.  Capitol  Street,  N.W.,

Washington, DC 20001 (www.AGA.org). 

Combustion and Ventilation Air

• Current edition of NFGC NFPA54/ANSI Z223.1 Section 9.3, Air for

Combustion and Ventilation.

Duct Systems

• Air Conditioning Contractors Association (ACCA) Manual D, Sheet

Metal  and  Air  Conditioning  Contractors  National  Association

(SMACNA), or American Society of Heating, Refrigeration, and Air

Conditioning  Engineers  (ASHRAE)  2005  Fundamentals  Handbook

Chapter  35  or  2004  HVAC  Systems  and  Equipment  Handbook

Chapters 9 and 16.

Acoustical Lining and Fibrous Glass Duct

• Current edition of SMACNA and NFPA 90B as tested by UL Standard

181 for Class I Rigid Air Ducts

Gas Piping and Gas Pipe Pressure Testing

• Current edition of NFGC NFPA54/ANSI Z223.1; chapters 5, 6, 7, and

8 and National Plumbing Codes.

Electrical Connections

• Current edition of National Electrical Code (NEC) NFPA 70.

Venting

• Current edition of NFGC NFPA 54 / ANSI Z223.1; Chapters 12 and

13.

ELECTROSTATIC DISCHARGE (ESD) 

PRECAUTIONS PROCEDURE

1. Disconnect all power to the furnace. Multiple  disconnects maybe

required.  DO  NOT  TOUCH  THE  CONTROL  OR  ANY  WIRE

CONNECTED TO THE CONTROL PRIOR TO DISCHARGING

YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.

2. Firmly  touch  the  clean,  unpainted,  metal  surface  of  the  furnace

chassis  which  is  close  to  the  control.  Firmly  touch  the  clean,

unpainted, metal surface of the furnace chassis which is close to the

control.  Tools  held  in  a  person’s  hand  during  grounding  will  be

satisfactorily discharged.

3. After touching the chassis, you may proceed to service the control

or  connecting  wires  as  long  as  you  do  nothing  to  recharge  your

body with static electricity (for example; DO NOT move or shuffle

your feet, do not touch ungrounded objects, etc.).

4. If  you  touch  ungrounded  objects  (and  recharge  your  body  with

static electricity), firmly touch a clean, unpainted metal surface of

the furnace again before touching control or wires.

5. Use  this  procedure  for  installed  and  uninstalled  (ungrounded)

furnaces.

6. Before removing a new control from its container, discharge your

body’s  electrostatic  charge  to  ground  to  protect  the  control  from

damage. If the control is to be installed in a furnace, follow items 1

through 4 before bringing the control or yourself in contact with the

furnace.  Put  all  used  and  new  controls  into  containers  before

touching ungrounded objects.

7. An ESD service kit (available from commercial sources) may also

be used to prevent ESD damage.

LOCATION

GENERAL

This  multipoise  furnace  is  shipped  in  packaged  configuration.  Some

assembly and modifications are required when used in any of the four

applications shown in 

Fig. 3

.

This furnace must:

• be installed so the electrical components are protected from water.

• not be installed directly on any combustible material other than wood

flooring for upflow applications. Downflow installations require use

of a factory-approved floor base or coil assembly when installed on

combustible  materials  or  wood  flooring  (refer  to  SAFETY

CONSIDERATIONS).

• be  located  close  to  the  chimney  or  vent  and  attached  to  an  air

distribution system. Refer to Air Ducts section.

• be provided ample space for servicing and cleaning. Always comply

with  minimum  fire  protection  clearances  shown  on  the  furnace

clearance to combustible label. 

The  following  types  of  furnace  installations  may  require  OUTDOOR

AIR for combustion due to chemical exposures:

• Commercial buildings

• Buildings with indoor pools

• Laundry rooms

• Hobby or craft rooms, and

CAUTION

!

FURNACE RELIABILITY HAZARD

Improper  installation  or  service  of  furnace  may  cause  premature

furnace component failure. 
Electrostatic  discharge  can  affect  electronic  components.  Follow  the

Electrostatic  Discharge  Precautions  Procedure  listed  below  during

furnace  installation  and  servicing  to  protect  the  furnace  electronic

control.  Precautions  will  prevent  electrostatic  discharges  from

personnel and hand tools which are held during the procedure. These

precautions  will  help  to  avoid  exposing  the  control  to  electrostatic

discharge by putting the furnace, the control, and the person at the same

electrostatic potential.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death,

and unit component damage. 

Corrosive or contaminated air may cause failure of parts containing flue

gas, which could leak into the living space. Air for combustion must not

be  contaminated  by  halogen  compounds,  which  include  fluoride,

chloride,  bromide,  and  iodide.  These  elements  can  corrode  heat

exchangers  and  shorten  furnace  life. Air  contaminants  are  found  in

aerosol  sprays,  detergents,  bleaches,  cleaning  solvents,  salts,  air

fresheners, and other household products. Do not  install furnace in a

corrosive or contaminated atmosphere. Make sure all combustion and

circulating air requirements are met, in addition to all local codes and

ordinances.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: