background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

29

Adjust Temperature Rise

6. Set  temperature  rise.  The  furnace  must  operate  within  the

temperature rise ranges specified on the furnace rating plate. Do not

exceed  temperature  rise  range  specified  on  unit  rating  plate.

Determine the temperature rise as follows: 

NOTE: 

Blower access door must be installed when taking temperature

rise  reading.  Leaving  blower  access  door  off  will  result  in  incorrect

temperature measurements.

a. Place thermometers in return and supply ducts as close to furnace 

as possible. Be sure thermometers do not see radiant heat from 

heat exchangers. Radiant heat affects temperature rise readings. 

This practice is particularly important with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air 

temperature from supply-air temperature to determine air 

temperature rise.

NOTE: 

If the temperature rise is outside this range, first check: 

(1.)Gas input for heating operation. 

(2.)Return and supply ducts for excessive restrictions causing 

static pressures greater than the maximum heating static listed on 

the rating plate.

c. Adjust air temperature rise by adjusting blower speed. Increase 

blower speed to reduce temperature rise. Decrease blower speed 

to increase temperature rise

d. Turn thermostat down below room temperature and remove 

blower access door.

e. Refer to the 

FURNACE CONTROL PROGRAMMING AND 

NAVIGATION

 section of this manual for instructions on 

adjusting the blower speed.

f. Repeat steps a through e until temperature rise is within range on 

rating plate.

g. When correct input rate and temperature rise is achieved, turn 

gas valve ON/OFF switch to OFF.

h. Remove manometer or similar device from gas valve.

i. Tighten set screw on outlet tower pressure tap with 3/32 in. hex 

wrench.

Check Safety Controls

1. Check Main Limit Switch(es)

This  control  shuts  off  combustion  control  system  and  energizes

air-circulating  blower  motor,  if  furnace  overheats.  By  using  this

method  to  check  limit  control,  it  can  be  established  that  limit  is

functioning  properly and  will  operate  if  there is  a restricted duct

system or motor failure. If limit control does not function during

this test, cause must be determined and corrected.

a. Run furnace for at least 5 minutes.

b. Gradually block off return air with a piece of cardboard or sheet 

metal until the limit trips.

c. Unblock return air to permit normal circulation for 5 minutes.

d. Reset unit power to clear limit fault lockout. 

2. Check draft safeguard switch. 

The purpose  of  this  control  is  to  cause  the  safe  shutdown  of  the

furnace during certain blocked vent conditions. 

a. Verify vent pipe is cool to the touch.

b. Disconnect power to furnace and remove vent connector from 

furnace vent elbow. 

c. Restore power to furnace and set room thermostat above room 

temperature. 

d. After normal start-up, allow furnace to operate for 2 minutes, 

then block vent elbow in furnace 80 percent of vent area with a 

piece of flat sheet metal. 

e. Furnace should cycle off within 2 minutes. If gas does not shut 

off within 2 minutes, determine reason draft safeguard switch did 

not function properly and correct condition. 

f. Remove blockage from furnace vent elbow. 

g. Switch will auto-reset when it cools. 

h. Re-install vent connector. 

i. Reset unit power to clear limit fault lockout. 

Checklist

• Put away tools and instruments. Clean up debris.

• Check Input/Output gas pressure

• Check heat rise per application static pressure

• Cooling CFM per application static pressure

• Verify that blower-OFF delay time is selected as desired.

• Verify that blower and burner access doors are properly installed.

• Cycle test furnace with room thermostat.

• Check operation of accessories per manufacturer’s instructions.

• Review User’s Guide with owner. 

• Attach literature packet to furnace.

CAUTION

!

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in:

-

Overheating  the  heat  exchangers  or  condensing  flue  gases  in

heat exchanger areas not designed for condensate.

-

Shortened furnace life

-

Component damage.

Temperature rise must be within limits specified on furnace rating plate.

Recommended operation is at midpoint of rise range or slightly above.

WARNING

!

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death,

and/or property damage.

Gas valve outlet pressure tap must be tightened to prevent gas leak.

CAUTION

!

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reduced furnace life.
Recheck  temperature  rise.  It  must  be  within  limits  specified  on  the

rating plate. Recommended operation is at the mid-point of rise range

or slightly above.

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: