background image

PG80MSU: Installation, Start-up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

21

NOTE: 

1.A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in a factory - authorized accessory filter rack. See

accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.

2.Adjust the blower airflow settings as necessary for the proper air temperature rise for each installation.

3.Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is required.

4.For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return

5..The -- entry indicates unstable operating conditions.

FURNACE CONTROL PROGRAMMING AND 

NAVIGATION

On-Board Control Method

This furnace model is equipped with an on-board 3-digit LCD display

with pushbutton navigation for the adjustment of operating parameters,

diagnostics, and service. The control board must be powered to use the

display  and  pushbuttons.  Upon  startup,  the  control  will  alternate

displaying  the  Model  Program  Number  (

PRG

)  and  Software  Version

(

uEr

).  The  control  board  has  been  programmed  at  the  factory  with  a

Model  Program  Number  specific  to  the  furnace  product  number.  The

correct Model Program Number is shown on the furnace rating plate.

The system’s status is displayed after startup or after no control buttons

have  been  pressed  for  60  seconds.  Status  Code  LED  will  also  be

illuminated  or  blinking  when  displaying  the  system  status.  The  codes

which  indicate  the current  operating mode  of  the  system as  shown  in

Table 11

.

Unit Size

Airflow Setting

Default Setting

External Static Pressure (IN.W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

60100C

1

Const. Fan

865

745

640

525

425

315

170

-

-

-

2

935

825

725

620

515

420

315

175

-

-

3

1035

935

830

745

640

550

460

365

235

140

4

1095

1000

900

815

725

630

545

455

360

240

5

1205

1125

1035

945

870

780

695

620

540

455

6

1290

1210

1125

1040

965

890

805

725

645

570

7

1385

1310

1235

1155

1080

1010

940

860

785

710

8

1495

1430

1360

1285

1215

1145

1080

1015

945

870

9

1585

1520

1455

1385

1315

1250

1185

1125

1065

995

10

1685

1625

1565

1505

1435

1370

1305

1250

1190

1135

11

1785

1725

1665

1605

1550

1485

1425

1365

1310

1255

12

Heating

1820

1765

1710

1655

1590

1530

1470

1410

1355

1305

13

1880

1830

1775

1720

1665

1610

1550

1490

1435

1385

14

1985

1930

1880

1830

1780

1730

1675

1620

1565

1515

15

2090

2040

1990

1940

1895

1845

1795

1745

1690

1645

16

2185

2140

2095

2045

2000

1960

1915

1865

1820

1770

17

Cooling

2285

2240

2195

2150

2110

2065

2025

1980

1940

1895

18

2465

2420

2375

2335

2290

2235

2180

2125

2060

2000

Table 10 – Airflow Settings

Default Airflow Settings

*

*. Setting #1 is the default setting for Constant Fan.

Designated Airflow Settings

Unit Size

Heating

Cooling

Heating 

Constant Fan

36040B

4

16

(2-12)

(1-7)

48060B

5

16

(3-11)

(1-8)

60080C

9

16

(5-14)

(1-8)

60100C

12

17

(7-15)

(1-7)

Table 9 – Air Delivery - CFM (with filter) (Continued)

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, or death.
Blower  access  door  switch  removes  115-V  power  to  control.  No

component operation can occur unless switch is closed. Caution must

be taken when manually closing this switch for service purposes.
Do  not  tape  or  permanently  allow  the  door  switch  to  be  bypassed.

Temporarily depress the door switch with one hand while accessing the

service  buttons  with  your  other  hand.  Do  not  touch  uninsulated

electrical components.

Table 11 – System Status Display Codes

Display

Operating Mode

Notes

iDl

Idle/Standby Mode

No active demands

Ht

Heating Mode

Gas Heating active

CL1

Low Cooling Mode

Low Cooling or Heat Pump active

CL2

High Cooling Mode

High Cooling or Heat Pump active

Hpd

Heat Pump Defrost Mode

Gas Heating cycle active during Heat Pump Defrost cycle

Cfn

Continuous Fan Mode

Continuous Fan active

bLr

Secondary Unit Operating 

Blower

Only used when control is the secondary furnace of a twinned furnace system and primary 

furnace is active

##.#

Active Status Code

See 

Fig. 35

 or Furnace Service Label for codes

Summary of Contents for PG80MSU

Page 1: ...NFORMATION GUIDE 40 MODEL NOMENCLATURE 40 To learn more about this appliance and installation via a mobile device go to https www payne com NFC or use the QR code below To access airflow tables or tro...

Page 2: ...se carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified service agency local gas supplier or your distri...

Page 3: ...ply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the...

Page 4: ...db Failure to follow these return air temperature limits may affect reliability of heat exchangers motors and controls see Fig 4 For accessory installation details refer to the applicable instruction...

Page 5: ...city firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrounded furnaces 6 Before removing a new c...

Page 6: ...ut rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 BTUh require the OUTDOOR COMBUSTION AIR METHOD Spaces having at least 50 cubic feet per 1 000 BT...

Page 7: ...ss volume than 50 cubic feet per 1 000 BTUh of the maximum input ratings for all gas appliances installed in the space and 2 The air infiltration rate is not known to be less than 0 40 air changes per...

Page 8: ...ings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section Unusually tight construction is defined as construction...

Page 9: ...own in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box...

Page 10: ...Protection Provide a minimum 17 3 4 in x 22 in 451 mm x 559 mm piece of sheet metal for flame roll out protection in front of burner area for furnaces closer than 12 inches 305 mm above the combustibl...

Page 11: ...n a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements Ductwork Aco...

Page 12: ...GC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separate line running directly from meter to furnace NOTE In the state...

Page 13: ...and downstream of manual equipment shutoff valve A02035 Fig 22 Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC in the United States local and national pl...

Page 14: ...in Step 1 5 Route J Box wires within furnace away from sharp edges rotating parts and hot surfaces WARNING ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal inju...

Page 15: ...ket BX Cable Installation in Furnace J Box 1 Remove cover from J Box 2 Route BX cable into 7 8 inch diameter hole in J Box 3 Secure BX cable to J Box bracket with connectors approved for the type of c...

Page 16: ...sted or draft hood equipped appliances in accordance with the NFGC the local building codes and furnace and vent manufacturers instructions The following information and warning must be considered in...

Page 17: ...in operation Seal any unused openings in venting system Inspect the venting system for proper size and horizontal pitch as required in the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 5...

Page 18: ...condensation and corrosion in the venting system Do not use vent dampers on appliances common vented with this furnace Additional Venting Requirements A 4 101 mm round vent elbow is supplied with the...

Page 19: ...t connector is required refer to Note 1 above 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflo...

Page 20: ...0 935 875 815 750 690 620 570 520 470 6 1050 995 935 880 820 755 700 645 595 550 7 1130 1075 1020 970 915 855 800 745 690 645 8 1200 1150 1100 1050 1000 945 890 840 785 735 9 1285 1240 1190 1145 1095...

Page 21: ...315 175 3 1035 935 830 745 640 550 460 365 235 140 4 1095 1000 900 815 725 630 545 455 360 240 5 1205 1125 1035 945 870 780 695 620 540 455 6 1290 1210 1125 1040 965 890 805 725 645 570 7 1385 1310 1...

Page 22: ...ct Super Plug available from distributor replacement component for the control board to copy the correct model program onto the new board Further details and instructions for these programming methods...

Page 23: ...Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A221015 Fig 34 3 Digit Display Flow Char...

Page 24: ...to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switches Correct inadequate combustion air supply problem before resetting the switches CA...

Page 25: ...e unit rating plate For installation above 2 000 ft 610 M multiply the input on the rating plate by the derate multiplier in Table 14 for the correct input rate A180238 Fig 37 Orifice Hole WARNING FIR...

Page 26: ...door switch f Set thermostat to call for heat g Remove regulator seal cap and turn regulator adjusting screw counterclockwise out to decrease input rate of clockwise in to increase input rate h Instal...

Page 27: ...2 6 2 7 2 8 2 9 850 2 4 2 5 2 6 2 7 to 875 2 3 2 4 2 5 2 5 900 2 2 2 3 2 3 2 4 5000 925 2 1 2 1 2 2 2 3 1524 950 2 0 2 0 2 1 2 2 975 1 9 1 9 2 0 2 0 1000 1 8 1 8 1 9 1 9 U S A Only 725 3 2 3 3 3 4 3...

Page 28: ...U S A Only 725 2 9 3 0 3 1 3 1 750 2 7 2 8 2 9 3 0 5001 775 2 5 2 6 2 7 2 8 1524 800 2 4 2 4 2 5 2 6 825 2 2 2 3 2 4 2 5 to 850 2 1 2 2 2 2 2 3 875 2 0 2 0 2 1 2 2 5400 900 1 9 1 9 2 0 2 1 1646 925 1...

Page 29: ...failure If limit control does not function during this test cause must be determined and corrected a Run furnace for at least 5 minutes b Gradually block off return air with a piece of cardboard or sh...

Page 30: ...es proceed with the following NOTE NO thermostat signal may be present at control and all blower OFF delays must be completed a Leave 115 V power to furnace turned on b Remove outer access door c Remo...

Page 31: ...d dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports...

Page 32: ...eel wool 0000 grade Do not use sand paper or emery cloth To reinstall igniter and flame sensor 1 Install the Hot Surface Igniter HSI and bracket with igniter gasket into burner assembly 2 Install flam...

Page 33: ...end of spring cable end opposite brush 2 Insert brush end of cable into the outlet opening of cell and slowly rotate with drill DO NOT force cable Gradually insert cable into upper pass of cell see Fi...

Page 34: ...iod the control CPU will open the gas valve relay GVR de energizing the gas valve solenoid GV The control CPU will repeat the ignition sequence for up to three more Trials for Ignition before going to...

Page 35: ...er motor BLWM operation 4 Heat pump When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles Whenever W...

Page 36: ...lation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 TROUBLESHO...

Page 37: ...U Installation Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 37 A2...

Page 38: ...Start up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 38 A221105 Fig 40 T...

Page 39: ...re only furnace is running Firing rate heat content btu cu ft X size of the dial cu ft rev X of rev per 60 sec rev sec X 3600 sec hr Example 1050 btu cu ft X 0 5 cu f t rev X 2 revs 60sec X 3600 sec h...

Page 40: ...ll Cell panel Inducer Group Housing assembly Transducer Inducer motor Inducer wheel TO OBTAIN INFORMATION ON PARTS Consult your installing dealer or a licensed Heating and Air Conditioning company of...

Reviews: