background image

13

FURNACE LOCKOUT -- Temperature above which the furnace
will not operate, except for defrost.

S

Default = NONE

S

Available settings = NONE thru >55

_

F (13

_

C)

HEAT PUMP LOCKOUT -- Temperature below which the heat

pump will not operate.

S

Default = NONE

S

Available settings = NONE thru <55

_

F (13

_

C)

DEFROST W/FURNACE -- Choose whether furnace operates

during defrost cycle

S

Default = YES

S

Available settings = YES / NO

HP TO FURNACE STAGING TIME -- Adjust the minimum

amount of time high stage heat pump will run before furnace will

be allowed to run.

S

Default = 15 MIN

S

Available settings = 15--60 minutes

Setup -- Zoning

Disable Zoning:

S

NO (default)

S

YES

If YES is selected, zoning is disabled and all dampers open. The
system will run un--zoned using the Zone 1 sensor.

Zone Offsets:

S

Zone Temperature Offsets (default = 0) Range --5

_

F to +5

_

F

(--3

_

C to +3

_

C)

This option allows actual temperature offset for each zone,

allowing calibration (or deliberate miscalibration) of each sensor.
Humidifier interval is time only, not actual humidifier run time.

Airflow Limits:

Since bypass damper is prohibited in this system, this setting is

used to select the maximum allowable noise/airflow relationship

into each zone based on air noise and comfort requirements. For
setup guidelines, see Airflow Limits Checkout in the next section.

S

Low -- 100% of maximum assessed airflow

S

Med Low -- 138% of maximum assessed airflow

S

Medium -- 176% of maximum assessed airflow

S

Med High -- 214% of maximum assessed airflow

S

High -- 250% of maximum assessed airflow

S

No Limit -- equipment does not stage down

CFM associated for each limit is shown on the screen. Compare

this value with the equipment’s low stage CFM value to ensure that
equipment will run for each zone. Assessed airflow is determined

as described in DUCT ASSESSMENT.

Duct Assessment Time

1 p.m. (default), adjustable in 1 hour increments from 1 p.m. to 12
a.m. (24 hours). Select which hour of the day the duct assessment

will be performed.

Setup -- Hydronic Heat

 

HYDRONIC HEAT SETUP

AIRFLOW:

800 CFM

BLOWER ON DELAY:

30 SEC

HOT WATER
LOCKOUT:

> 30 F

HEAT PUMP
LOCKOUT:

< 45 F

DEFROST W/WATER:

YES

BLOWER OFF DELAY: 30 SEC

< BACK

A07031

Fig. 31 -- Hydronic Heat Setup

HOT WATER LOCKOUT -- Outside temperature above which the
hot water will not operate except for defrost (if selected).

S

Available settings -- NO, 5 to 55

_

F (--15 to 13

_

C) in 1

_

increments

HEAT PUMP LOCKOUT -- Outside temperature below which the

heat pump will not operate, 1

_

resolution.

S

Appears only with a heat pump outdoor unit.

S

Available settings -- NO, 5 to 55

_

F (--15 to 13

_

C) in 1

_

increments

DEFROST W/WATER:

S

Available settings: YES / NO (Default = YES)

S

Appears only if heat pump is available. If no, hot water will not
run during a defrost.

AIRFLOW -- Selects desired airflow during Hydronic Heating

S

Available range from OFF, 500 CFM(minimum) to 400
CFM/ton cooling maximum in 50 CFM increments.

S

Default is the cooling airflow. (350 CFM/ton)

S

OFF selection does not turn off airflow if heat pump is
defrosting.

BLOWER ON DELAY -- Time after hot water is requested that the
blower will turn on.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 30

S

Does not appear if a heat pump is present since heat pump and
hot water run simultaneously.

BLOWER OFF DELAY-- Time after hot water request terminates

before the blower will turn off.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 0

Setup -- Accessories

Filter Type:

S

Air Filter (i.e. TrueSense

t

)

S

Electronic Air Cleaner

S

Air Purifier (i.e. TrueSense

t

)

CLEAN INTERVAL: Never, 1 to 18 months. (Default = 90)
Enables a timer for the filter notification.
Interval at which the Clean Filter notification will turn on.
PRESSURE MONITOR: ENABLE/DISABLE -- enables the static
pressure calculation for media--type filters.

Humidifier Installed:

S

NO

S

YES

If YES, indicates to the system whether a humidifier is installed

and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default = 12

months)
Interval at which the Change Humidify Pad notification will be

displayed.
HUMIDIFY WITH FAN (Heating Mode Only):

S

NO (default)

S

YES

If YES, the humidifier will turn on if there is a humidify demand

present. The fan will turn on to Low speed if the fan setting is
Auto.

Ventilator:
NOTE

: Only appears if ventilator is installed.

CLEAN INTERVAL:

S

60 to 180 days of actual operation (default = 90)

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: