background image

18

If the system determines that it cannot deliver the airflow into a
zone that needs conditioning, and that zone has an airflow limit

selected, the system will take the following 4 steps:

Step 1 — Reduce airflow if possible

a. 275 CFM per ton minimum in cooling. 175 CFM/ton

for low stage cooling if 2--stage unit is installed.

b. Comfort Heat airflow is minimum for heat pump heat-

ing (3.5 X Outdoor Temp + 137) CFM/ton.

c. No adjustment for furnace heating

Step 2 — Dump air to unoccupied zones

a. Unoccupied zones can be conditioned up to the most

conditioned setpoint.

Step 3 — Dump air to zones with less conditioned

setpoints

a. Zones with lower setpoints in heating and higher set-

points in cooling may be conditioned to within 3

_

F

(1.7

_

C) of the most conditioned setpoint.

b. Increase or decrease unoccupied zones 0.75

_

F (.4

_

C).

Step 4 — Single stage cooling

a. System will reduce airflow to 275 CFM/ton in single

stage cooling systems.

Step 5 — Stage down equipment

a. Equipment stage down or shut off if necessary.

b. Fault history will record an event of “AIRFLOW LIM-

ITED STAGEDOWN OCCURRED” on stagedown and
“EXCESS STATIC PRESSURE” if shut down.

c. If shut down occurs, other zones need to call before

equipment will resume operation.

Dehumidify Operation

Once a target cooling humidity setpoint is selected in the Advanced
Setup COOLING HUMIDITY screen, two other setup options

affect Dehumidify operation: COOLING AIRFLOW and
DEHUMIDIFY.
COOLING AIRFLOW: Setting this to

COMFORT

or

QUIET

will enable the system to use low airflow to help dehumidify the
space. If duct sweating becomes an issue, setting DEHUM

AIRFLOW to

HIGH

may resolve the problem.

DEHUMIDIFY: Located in the Cooling Humidity screen of the

Advanced Setup, this option has 2 settings:

ON

and

OFF

.

If DEHUMIDIFY is set to

ON

(factory default), then the cooling

unit will be allowed to overcool the space up to 3

_

F (.6

_

C) if the

humidity level is above the cooling humidity target setpoint.
The amount of over--cooling allowed varies with the

dehumidification demand, the cooling demand, and the actual
space temperature. More over--cooling is allowed with greater

dehumidification demand.
When the space temperature is at or above 75

_

F (24

_

C) and the

dehumidify demand is high, over--cooling up to 3

_

F (1.7

_

C) is

allowed. As the space temperature approaches 70

_

F (21

_

C), less

over--cooling is allowed. At 70

_

F (21

_

C) space temperature, no

more over--cooling is allowed no matter how great the dehumidify

demand. This is done to protect the equipment.

Hybrid Heat Setup / Operation

Furnace Lockout Operation

(

in HYBRID HEAT SETUP

menu) is the outside temperature above which the furnace will not

run except for defrost (otherwise known as the aux heat lockout).

Heat Pump Lockout Operation

— (in HYBRID HEAT SETUP)

is the outside temperature below which the heat pump will not run

(otherwise known as the balance point).
These values can be set identical to each other. If they are not

identical, the system will stage up and down normally from heat
pump to furnace when the outside temperature is between these

settings. The User Interface will not allow the heat pump lockout

setting to be above the furnace lockout setting.
The factory default settings for both of these is NONE (no

lockouts). Even though a furnace lockout temperature may be set,
the system will still use the furnace in defrost operation, and may

stage back down to heat pump when defrost is completed after a 2

minute delay.

Hybrid Heat Defrost

— (in HYBRID HEAT SETUP) When the

outdoor unit needs a defrost cycle, the furnace will run during
defrost regardless of lockout temperature, unless told not to in the

Hybrid Heat Setup screen. After defrost, the system may stage

down to heat pump after a 2 minute delay.
If the room temperature falls below 40

_

F (4

_

C) and a furnace

lockout is in enabled, the furnace lockout will be overridden to
bring on the furnace.

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: