background image

11

R

G

FE Fan Coil or 
Variable Speed Furnace

A07115

Fig. 29 -- G Input Wiring for System Shutdown

with Infinity

t

Control (Contact type selectable;

Normally Closed (default) or Normally Open)

High Stage Timer

Minimum amount of time low stage must operate before high stage

is activated. Ten to 60 minutes. 10 = default
A demand of 5

_

or more will override the staging timer.

Furnace Airflow (Capacity) Limiting

The following settings allow the installer to restrict the furnace

within certain minimum and maximum airflows. These airflows
are converted to capacities.

The Min and Max limits are

determined by the equipment size. These settings are not the same
as the zoning airflow limits.
Min CFM (only appears with modulating furnaces)
Minimum CFM to run a modulating furnace. This will increase
the minimum operating capacity of the furnace. Default value is

the furnace air flow for the lowest heat capacity.
Maximum CFM (only appears with modulating furnaces)
Maximum CFM to run a modulating furnace. This will reduce the

operating capacity of the furnace. Default value is the furnace air
flow for the highest heat capacity.

Off Delay

S

90 seconds

S

120 seconds (default)

S

150 seconds

S

180 seconds

Amount of time the blower will continue to run after heating has

shut off.

Dehum Drain

Turns off the continuous fan at the end of cooling for five minutes,
in order to drain the indoor coil of water. The fan will only be

turned off if a dehumidify demand existed at the start of or during
the cooling cycle. Default is enabled.

Altitude

S

US 0 -- 2000 (default)

S

US 2001 -- 3000

S

CA 2001 -- 4500 (for Canada only)

S

US 3001 -- 4000

S

US 4001 -- 5000

S

US 5001 -- 6000

S

US 6001 -- 7000

S

US 7001 -- 8000

S

US 8001 -- 9000

S

US 9001 -- 10000

This setting will adjust the furnace’s airflow to compensate for
altitude. Altitude adjustment is not available with older furnaces.

Please see furnace instructions for further details.

Setup -- Fan Coil

Heat Pump Heating:

S

COMFORT (default) Heat Pump airflow is varied depending on
outdoor temperature to maximize comfort.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton.

Heat Pump Cooling Airflow:

S

COMFORT (default) Cooling airflow is varied depending on
humidity and temperature demand settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When

COMFORT

is not selected, the unit will not run

reduced airflows for dehumidification. Heat Pump airflow is
varied depending on outdoor temperature to maximize comfort.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton. Dehumidify features are not active
when set to maximum.

S

QUIET-- minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.

Dehum Airflow:

S

NORMAL (factory default) -- When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.

S

HIGH -- Minimum airflow during the dehumidify mode is
increased to reduce duct and register sweating. Also increases
minimum airflow during normal cooling operation to reduce
duct sweating.

Heater Size:

S

(choices dependent upon fan coil model)

This will show the heater size entered during the start--up process.

This value can be changed to another value (limited by the model

number of the fan coil). If the electric heater is self--identifying, this
value is not shown.

Elect Heat Lockout

S

NONE (default)

S

+5 to 55

_

F (--15 to 18

_

C)

Outside temperature above which the electric heat will not operate

except for defrost.

G Terminal

This setup option selects desired operation when the R--G circuit is
made on the fan coil control board.

S

DISABLED (Default)

S

FAN -- turns on fan to selected fan speed when G terminal is
energized. See Fig. 28.

This setting is used in conjunction with fresh air supply products

(e.g. fresh air/make--up air dampers).

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: