background image

14

Interval at which the Clean Ventilator Pre--filter notification will
turn on.

UV Lights Installed

S

NO

S

YES

If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:

S

6 to 48 months operation time (default = 12 months)

Interval at which the Change UV Lights notification will be
displayed.

Setup -- System Maintenance

Remind Owner of Routine Maintenance Every:

This setup is used to adjust the timer interval in which the normal

System Maintenance notification is turned on for the homeowner.
Range =

S

OFF

S

6 to 24 months, (default = 12 months) Pressing the right side
button will reset the timer. Pop--up confirmation will be shown.

 

SYSTEM  MAINTENANCE

< BACK

REMIND OWNER OF
MAINTENANCE EVERY:

12  MONTHS

% USED:

50%

RESET >

A07033

Fig. 32 -- System Maintenance

Setup -- Utility Saver

Cooling/Heat Pump Heating (Hybrid Heat &Hydronic Heat
only):

S

Turn off, Low Stage

Utility Saver is used to force the equipment to a lower stage (low

or off) when activated by the utility company, typically during

peak load times.
This setup is available only if the equipment has a utility saver

input (refer to outdoor equipment Installation Instructions). This
setup controls the response of the equipment when the utility saver

input is active.
The choices include:

S

Turn Off , (equipment turns off)

S

Low Stage (available if the AC/heat pump is a 2--stage model,
runs low speed only)

CHECKOUT MENUS

The Checkout menu will show the equipment installed in the

system. A sample checkout menu is shown in Fig. 33.

CHECKOUT

FURNACE

HEAT PUMP HEATING

HEAT PUMP COOLING

HUMIDIFIER

VENTILATOR

   BACK               SELECT

A03204

Fig. 33 -- Checkout Menu

Checkout -- Furnace or Gas PAC

Make sure the furnace is properly installed before continuing.

S

LOW HEAT RUNTIME: 5 min.

S

HIGH HEAT RUNTIME: 5 min.

This menu item allows the furnace to be exercised. First, a low heat

runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start--up sequence. This

sequence will be displayed on the Infinity Zone Control screen.
After the gas valve and blower motor turn on, the screen will

automatically change to “

FURNACE CHECK

” and show the

current operating status of the furnace.

Checkout -- Electric Heat

S

ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range = 0 -- 120 min.

If you have a fan coil with electric heaters, this menu item will

allow the heaters to be exercised.
With self--identifying electric heaters, three stages of electric heat

are available to be exercised in any combination. Non--identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised

then press START (right--side button). The display will change to
show the fan coil’s operating status.

Checkout -- Heat Pump Heating

S

HIGH HEAT RUNTIME: 5 min.

S

LOW HEAT RUNTIME: 5 min.

S

DEFROST: NO

The heat pump heating mode can be exercised with this menu

option. With a 2--stage heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost

cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating or cooling demand to the
system.

Checkout -- Heat Pump Cooling or AC Cooling

S

HIGH COOL RUNTIME: 5 min.

S

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2--stage heat pump or AC

unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat

pump or AC operating status.
Default time = Fixed 5 min. minimum, range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump (or AC) cooling mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Humidifier

S

OFF

S

ON

The humidifier can be exercised On and Off with this menu option.

Charging (Appears with Variable Capacity Heat

Pump)

S

Enables charging mode of the variable capacity heat pump.

Evacuation (Appears with Variable Capacity Heat

Pump)

S

Allows the heat pump to be evacuated of refrigerant.

EXV Position (Appears with Variable Capacity

Heat Pump)

S

Positions the Electronic Expansion Valve (open or closed)

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: