background image

8

NOTE

: The static pressure check occurs only at initial installation,

or when INSTALL is run in the INSTALL/SERVICE menu.

Duct Assessment

The following screen will appear after STATIC PRESSURE screen

is exited. Press right--side button to start Duct Assessment. Duct

Assessment will measure the relative size of the ductwork, up

to

and through the dampers. These measurements are used to control

the correct amount of airflow in the zoned system. Status messages
will appear on the screen to indicate what the system is doing. The

process will take approximately one minute per zone. The duct

assessment will override a call for heat or cool.
A duct assessment will automatically occur each day at a user

selectable time. The factory default time is 1:00 p.m. but, may be
changed by entering the Zoning Setup menu. See Zoning Setup

section of this manual. The duct assessment will override a call for
heat or cool. The system will first open all zones and drive the

blower to 175 CFM/ton of cooling (or the minimum indoor unit’s

airflow, whichever is greater). It will then take a static pressure
measurement. The system will then close all zones and open one

zone at a time, taking a static pressure measurement for each zone.
The system will then close all zones and take a pressure

measurement, getting a value for the duct leakage up to and

through the dampers. With these static pressure measurements, the
system will calculate the relative size of each zone as well as the

percent leakage through the dampers At the end of the process, the
display will show the relative size of each zone duct. See Fig. 23.
If the User Interface detects an error (damper not moving or

damper wired backwards), it will perform the duct assessment
again. If it still detects a damper problem, it will default the

measurements into equal sizes, with 10% leakage, and display the
zone number for the suspected zone damper.

DUCT ASSESSMENT

MEASURE DUCT

CAPACITY FOR EACH

ZONE.

4 MINUTES ARE REQUIRED

TO COMPLETE

PRESS START TO BEGIN

   QUIT                   START

DUCT ASSESSMENT

ASSESSMENT ACTIVE

PLEASE WAIT

OPENING ALL ZONES

AIRFLOW STABILIZING

PROGRESS

   STOP

DUCT ASSESSMENT

ZONE CAPACITY
ZONE1

25

ZONE 2

20

ZONE 3

25

ZONE 4

20

DAMPER LEAKAGE 10

   QUIT                   START

A04085

Fig. 23 -- Duct Assessment

QUICK START

For first time installers, Quick Start will allow a quick start up of
the Infinity Zone System before learning all the details of system

operation. However, for the best possible comfort and operation
refer to the Infinity Zone Control Owner’s Manual.

Set Day, Time & Desired Humidity

1. Open the door of the Infinity Zone Control and press the

BASIC

button.

2. Adjust the highlighted

HOUR

setting using the

LEFT

Up/

Down button.

3. Press

SCROLL

button (down) to highlight

MINUTE

.

4. Adjust the

MINUTE

setting using the

LEFT

Up/Down

button.

5. Press

SCROLL

button (down) to highlight

DAY

.

6. Adjust the current

DAY

setting using the

LEFT

Up/Down

button.

7. Press

SCROLL

button (down) to highlight

HUMIDITY

.

8. Press the red

HEAT

button to select heating humidity.

9. Adjust desired heating humidity level using either (+/--) but-

ton.

10. Press the blue

COOL

button to select cooling humidity.

11. Adjust the desired cooling humidity level using ei-

ther(+/--)button.

12. To exit press

BASIC

button or close door.

13. If changes are made, you will be asked to “

SAVE

CHANGES? YES/NO

.”

Override Heating Schedule

1. Press the red

HEAT

button. Heating mode is confirmed

when the red LED next to the red

HEAT

button is lit.

2. Use the

RIGHT

Up/Down button to select your desired

heating temperature.

3. The default time for temporarily overriding the temperature

schedule is 2:00 HRS as indicated by the text on the lower

left.

NOTE

: Override time will not appear if programming has been

turned off.

4. You can change the temporary override time in 15--minute

increments by pressing the

LEFT

Up/Down button until

the desired override time is selected, or press the

HOLD

button anytime to override the schedule indefinitely.

Quick Program Schedule For All Days

This section will give you a quick program schedule for

ALL

DAYS

of the week. For more information on how to create

customized schedules for every day, the entire week, or weekend,
refer to the Owner’s Manual.

1. Open the door of the control.
2. Press the

SCHEDULE

button, which allows you to create

one schedule for the entire home.

3. Press either the

LEFT

or

RIGHT

side button repeatedly (if

necessary) until

“ALLDAYS”

is displayed. The

WAKE

time period will be highlighted.

4. Using the

LEFT

Up/Down button, set the start time for this

time period.

5. Press the red

HEAT

button. Heating temperature will begin

flashing.

6. Set the heating temperature using the

RIGHT

Up/Down

button.

7. Press the blue

COOL

button. Cooling temperature will be-

gin flashing.

8. Set the cooling temperature using the

RIGHT

Up/Down

button.

9. Set the remaining periods by using the

SCROLL

button to

select “

DAY

”, “

EVENING

”, and “

SLEEP

”.

10. To copy a zone, use

SCROLL

button to select

“COPY”

.

Select

YES

and copy this zone schedule to other zones us-

ing

NO

or

YES

.

11. Exit the scheduling mode by either closing the door or

pressing the

SCHEDULE

button.

12. If changes are made, you will be asked to “

SAVE

CHANGES YES/NO.

INSTALL / SERVICE MENUS

The

“INSTALL / SERVICE”

menus contain a set of vital

information. This information enables the Installer or Service
person to view a summary of what has been installed, etc. This

information is not covered in the Owner’s Manual.
To enter

INSTALL / SERVICE

menus, press and hold the

ADVANCED

button for at least ten seconds. The following menu

will appear (See Fig. 24):

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: