background image

5

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

OAT

HUM

COM
24V

Humidifier

Connection

A

B

C

D

 

OAT

Sensor

(Optional)

A B C D

A B C D

Damper

Control

module

A B C D

Indoor

Unit

Communicating

AC or HP

A04018

Fig. 11 -- Communicating Indoor Unit w/2--Stage Puron

Refrigerant Communicating Outdoor Unit

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

OAT

HUM

COM
24V

Humidifier

Connection

OAT

Sensor

A B C D

A B C D

Damper

Control

module

A B C D

Indoor

Unit

C

Y

1-Stage AC

Y/Y2

A04019

Fig. 12 -- Connection Diagram for Furnace or FE Fan Coil

with Non--Communicating 1--Stage AC

A

B

C

D

Zone Control

User Interface &

Smart Sensor(s)

Green

Yellow

White

Red

A

B

C

D

A

B

C

D

Damper

Control

module

A

B

C

D

Variable-Speed

Fan Coil

1-Spd. HP

HUM

C

Y

W2

 Y

O

C

R

O

R

W

OAT

OAT

Sensor

Humidifier

Connection

G

A07149

Fig. 13 -- Connection Diagram for FE Fan Coil with

Non-- Communicating 1--stage HP

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)

NOTE

: It is not mandatory that the above color code be used, but

each ABCD connection in the system MUST be wired consistently.
A separate ABCD Connector comes inside packaging and should
be used when connecting to furnace (or fan coil). Ensure connector
is inserted properly into circuit board. (See Fig. 14.)

A B C D

A03193

Fig. 14 -- Wire ABCD Connector

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Improper wiring of the ABCD connector will cause the

Infinity Zone System to operate improperly. Check to make

sure all wiring is correct before proceeding with installation or

turning on power.

CAUTION

!

9. Push any excess wire into the wall. Seal hole in wall to pre-

vent any air leaks. Leaks can affect operation.

10. Attach Infinity Zone Control to the mounting plastic by lin-

ing up the plastic guides on the back of the control with the
opening on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

dampers, humidifier, ventilator, UV lights, etc.).

12. Turn on power to equipment.

See wiring diagrams Fig. 11, 12, and 13 for connecting the Infinity

Zone Control and Smart Sensors to the Damper Control Module.
More information regarding Damper Control set--up and wiring

can be found in Damper Control Module Installation Instructions.
See wiring diagram, Fig. 11, which includes an indoor

communicating furnace or FE fan coil, with a 2--stage Puron

refrigerant communicating outdoor unit. No additional OAT
(outdoor air temperature) sensor is required because the Infinity

Zone Control will use the temperature sensor inside the outdoor
unit.
See wiring diagram, Fig. 12, for connecting an indoor

communicating furnace or FE fan coil with a 1--stage air
conditioning unit (non--communicating outdoor). An Outdoor Air

Temperature (OAT) sensor may be installed (but is not required) at
the indoor furnace or fan coil OAT terminals. When OAT sensor is

applied, the Infinity System will provide enhanced system features
and benefits.
In a hybrid heat installation with a non--communicating heat pump,

an OAT sensor must be installed or the heat pump will not run.
See wiring diagram Fig. 13 for connecting an FE fan coil with a

1--stage heat pump (non--communicating outdoor unit). When
OAT is applied, the Infinity System will provide enhanced system

features and benefits.

NOTE

: For other applications not listed, refer to the Network

Interface Module (NIM) Installation Instructions.

Humidifier Connection

A 24VAC bypass or fan powered humidifier may be installed.

NOTE

:

Do Not Use

a traditional humidistat to control humidifier

operation. If a humidifier is installed, let the Infinity Zone Control
operate humidifier.

Bypass Humidifiers

A bypass humidifier should be wired directly to the furnace or fan

coil HUM and 24VAC COM terminals. The Infinity Zone Control
will automatically energize the HUM output during a call for

humidification.

Fan Powered Humidifiers

Most fan powered humidifiers produce internal 24VAC in order to
energize upon a switch or contact closure. For this application, a

24VAC N.O. Isolation Relay (DPST)

MUST

be used to prevent

mixing the internal humidifier power with the indoor equipment

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: