background image

2

Design Considerations

The Infinity Zone system is unique because a bypass damper must
not be used. This is possible due to the intelligence of the system

and variable speed motor technology. For trouble--free

applications, the following parameters should always be met:

1. Zones should be sized so that each zone can deliver at least

the minimum airflow for the system in both heating and
cooling modes.

2. Oversize duct work by 25% to avoid excess noise at mini-

mum zone airflow.

3. Be aware that heating airflow may be higher than cooling

airflow depending on equipment combination.

INSTALLATION, START--UP OVERVIEW

This instruction covers installation of the Infinity Zone Control

only

. Physical installation instructions for the indoor and outdoor

equipment, Damper Control Module, and accessories are provided

with each unit.
Setup, commissioning, operation, and troubleshooting of the

Infinity Zone System are covered in this installation instruction. It
is the guide to connecting the system components and

commissioning the system once all physical components are

installed. Special screen prompts and start--up capabilities are
provided in the Infinity System to simplify and automate the initial

commissioning of the system.

S

Install Infinity Zone Control according to this instruction.

S

Install indoor unit, outdoor unit, and accessories according to
their instructions.

S

Wire complete system according to this instruction.

S

Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start--up.

INSTALLATION

Check Equipment and Job Site

Inspect equipment. File claim with shipping company prior to

installation if shipment is damaged or incomplete.

Infinity Zone Control Location and Wiring

Considerations

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect power before routing control wiring.

!

WARNING

All wiring must comply with national, local, and state codes.

Infinity Zone Control Location

The Infinity Zone Control User Interface is the command center for

the Infinity Zone System and is typically located in Zone 1 to sense

and control temperature in this zone. It should be located where it
is easily accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines
should be followed:
The Infinity Zone Control and Room Sensors should be mounted:

S

Approximately 5--ft (1.5 meters) from the floor.

S

Close to or in a frequently used room, preferably on an inside
partitioning wall.

S

On a section of wall without pipes or ductwork.

The Infinity Zone Control and Room Sensors should

NOT

be

mounted:

S

Close to a window, on an outside wall, or next to a door leading
to the outside.

S

Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature--radiating objects which could cause a false
reading.

S

Close to or in direct airflow from supply registers.

S

In areas with poor air circulation, such as behind a door or in an
alcove.

Remote Room Sensor Option

A Remote Room Sensor can be used with the Infinity Zone
Control to take the place of the User Interface internal temperature

sensor. This allows the Infinity Zone Control to be mounted in

areas with less than optimal airflow (such as near an exterior door,
window or in a closet). The remote sensor can be wired to the

terminal block connectors labeled S1 and S2 at the User Interface
backplate, or the ZS1 and ZS1C connection at the Damper Control

Module. In either case, the Infinity Zone Control will automatically

detect the Remote Room Sensor and ignore its internal temperature
sensor. It is also important to note the humidity sensor cannot be

remotely located, so do not locate the Infinity Zone Control in an
area where humidity sensing may not be accurate.
In addition, the Remote Room Sensor is a temperature sensor only,
having no additional user inputs. This sensor is typically connected

to the Damper Control Module and used to sense and control

temperature in each zone.

Remote Sensor Averaging

Typically, one Remote Room Sensor is used per zone, but multiple
sensors may be used and averaged in some applications. Averaging

requires a special series--parallel wiring method with a specific
number of sensors. See Fig. 2 in this manual for wiring diagram.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

Damper Control

Module

ZS_

Damper Control

Module

ZS_C

A03233

Fig. 2 -- Remote Room Sensor -- Parallel Wiring

Smart Sensor

Any zone may use a Smart Sensor. It provides a temperature

display and buttons to adjust the desired temperature in that zone
only. It also displays outdoor temperature and indoor humidity

sensed at the User Interface. Only one Smart Sensor may be used
per zone. They cannot be averaged like Remote Room Sensors. If a

Smart Sensor is used in a zone, a Remote Room Sensor may also

be used in the same zone. The Remote Room Sensor has priority
over the Smart Sensor. The Smart Sensor will display the Remote

Room Sensor temperature.

NOTE

: Smart Sensors must be addressed to identify which zone it

will control. See Smart Sensor Installation Instructions for details.

Wiring Considerations

Ordinary thermostat wire is recommended. Use 22 AWG or larger

for normal wiring applications. Continuous wire lengths over

100--ft. (3 m) should use 20 AWG or larger.

NOTE

: ABCD bus wiring only requires a four--wire connection;

however, it is good practice to run thermostat cable having more

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: