background image

15

Charge Calculation (Appears with Variable

Capacity Heat Pump)

S

Calculates the amount of charge needed in the system. Takes
into account lineset length, liquid line diameter, and indoor coil
model.

Checkout -- Ventilator

Speed:

S

OFF

S

LOW

S

HIGH

The ventilator can be exercised through all of its operating speeds

with this menu option.

Checkout -- Zoning

Duct Assessment

This is the same Duct Assessment that runs on first start--up.

Measures duct capacity for each zone. The Duct Assessment will
perform an airflow measurement on each zone and determine the

relative size of each zone along with damper leakage. This
assessment will require approximately 1 minute for each zone in

the system.

NOTE

: A Duct Assessment will automatically occur every 24

hours at selected time to check system static and calibrate dampers.

Sensor / Damper Check:

The Sensor/Damper Check allows the installer to check each zone

damper for operation, as well as insure the zone sensor corresponds

to that particular zone.
When first initiated, the Zone 1 damper will fully open, and all

other zones will close. Using the scroll button, the installer can
select each zone and verify the damper is fully open while all other

dampers remain closed.
After proper damper operation has been verified, the installer can
now check and verify that each Remote Room Sensor corresponds

to the proper zone damper in the same zone. Start from the top and
highlight zone 1 to open damper. Temporarily disconnect any other

zone Remote Room Sensor (at sensor location). That zone damper

will now open, while the Zone 1 damper will close.
EXAMPLE: If the Zone 2 Remote Room Sensor is disconnected,

the Zone 2 damper will now open as indicated on the User
Interface display. The word

“FAIL”

will also be displayed instead

of the actual temperature for Zone 2. Reconnect Zone 2 sensor and
try all remaining sensors one at a time in the system. Smart Sensors

may also be checked, see Smart Sensor Installation Instructions for

procedure.

Airflow Limits:

S

LOW

S

MED LOW

S

MED

S

MED HIGH

S

HIGH (default)

S

NO LIMIT

Because there is no bypass damper, the Zone Airflow Limit check
will allow the installer to assess the airflow noise generated by the

system providing the maximum amount of airflow to each zone.

Select ZONE, then select AIRFLOW LIMIT: When Start is
pressed (right side button), the selected zone’s damper will fully

open, all others will close, and the indoor unit will provide the
maximum airflow for that zone (as selected in SETUP —

ZONING, Airflow Limits). If the airflow noise is objectionable, the
installer can select a lower airflow noise limit. If the noise is not

objectionable, the installer should leave HIGH selected, or even

NO LIMIT.

NOTE

: Selecting a lower airflow noise limit may decrease the

homeowner’s comfort in that zone.

Sensor Types:

Shows list of all zones with corresponding sensor types.
UI = User Interface
SS = Smart Sensor
RS = Remote Sensor

Checkout -- System Access Module (SAM)

See System Access Module Installation Instructions for full details.

SERVICE MENUS

The Service Info menu will only show the equipment installed in

the system. Below is a sample using a furnace and a heat pump
(Hybrid Heat). A sample service menu is shown in Fig. 34.

SERVICE INFO

FURNACE STATUS

HEAT PUMP STATUS

LAST 10 SYSTEM FAULTS

RUN/FAULT HISTORY

TODAY’S DATE

MODEL/SERIAL NUMBER

SERVICE PHONE NUMBER

   BACK               SELECT

A03205

Fig. 34 -- Service Menu

Service -- Furnace Status or Gas PAC Status

The Status screens will show all of the current operating parameters
of each installed piece of equipment.

NOTE

: To view a less detailed Equipment Status screen, press the

right side button. This will display equipment stage, fan status,
actual and target humidify settings.

Heat Stage:

S

OFF, LOW, HIGH

Displays stage of heat that the furnace is currently delivering.

Airflow CFM:

S

(furnace model dependent)

Cubic Feet per Minute of air the User Interface is currently

requesting.

Inducer RPM (90% furnaces only):

S

Actual inducer motor RPM value.

Blower RPM:

S

Actual blower motor RPM value.

Static Press:

S

Inches of water. Displays calculated static pressure that the
furnace is currently experiencing.

S

If static pressure cannot be accurately calculated, the display will
read UNKNOWN. When this is seen, the system is adjusting to
high static pressure by cutting back blower RPM.

Lockout Timer:

S

Seconds

If a lockout timer is active, this will show the current time value.

See furnace manual for details on lockout timers.

Service -- Fan Coil Status

Electric Heat:

S

OFF, LOW, MED, HIGH

Displays stages of electric heat that the fan coil is currently
delivering.

Airflow CFM:

S

(fan coil model number dependent)

UIZ0

1

--

V

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: