background image

9

Reset Factory Defaults:
Program Schedule:

S

Yes/No to reset back to Energy Star default Time and Temp
schedules.

User Settings:

S

Yes/No to reset the user settings in the Advanced Setup to
factory default settings.

Install Settings:

S

Yes/No to reset install settings in Install/Service menus to factory
default settings.

Last 10 System Events:

S

Yes/No to reset last 10 events under Service Info menu.

Setup -- Furnace

Upon a first time start--up of the Infinity Control, the furnace DIP
switch settings will be copied to the furnace setup menu. Any

changes can then be made from the Infinity Control.

Furnace Airflow:

S

COMFORT (default)

S

EFFICIENCY

Selects the airflow of the furnace when heating.

EFFICIENCY

is

the airflow used to meet specified ratings,

COMFORT

is a

decreased airflow used to increase the output air temperature and

provide increased comfort.

Cooling Airflow:

S

COMFORT (default) -- cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.

S

QUIET-- minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.

Heat Pump Heating:

S

COMFORT (default) Heat Pump airflow is varied depending on
outdoor temperature to maximize comfort.

S

EFF 325 -- Fixed airflow used to achieve specified ratings . This
is nominally 325 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

EFF 350 -- Fixed airflow used to achieve specified ratings . This
is nominally 350 CFM/ton, but will vary if a 2--stage outdoor
unit is used.

S

MAXIMUM -- 400 CFM/ton.

Heat Pump Cooling:

S

COMFORT (default) -- cooling airflow is varied depending on
humidity and temperature demands settings. This selection
enables the full dehumidify and comfort capabilities of the
system. When COMFORT is not selected, the unit will not run
reduced airflows for dehumidification.

S

EFF 325 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 325
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

EFF 350 -- fixed airflow used to achieve specified ratings -- no
dehumidification airflow reduction. This is nominally 350
CFM/ton, but will vary if a 2--stage outdoor unit is used.

S

MAXIMUM -- 400 CFM/ton. No dehumidification airflow
reduction.

S

QUIET-- minimum cooling airflow that the system can safely
run (typically 300 CFM/ton). Use this setting if duct noise is a
severe problem. Note that duct sweating in high humidity
environments could be an issue.

Dehum Airflow:

S

NORMAL (factory default) -- When equipment is running to
dehumidify, the airflow is allowed to adjust to a minimum to
satisfy the dehumidification call.

S

HIGH -- Minimum airflow during the dehumidify mode is
increased to reduce duct and register sweating.

Low Heat Rise

S

ON

S

OFF (default)

Set to

ON

if the system contains a bypass humidifier. The

ON

setting will increase the furnace low heat airflow.

Staging

S

SYSTEM (default)

S

LOW

S

LOW--MED

S

LOW--HIGH

S

MEDIUM

S

MED--HIGH

S

HIGH

S

FURNACE

NOTE

: Controls the staging of the furnace. More staging options

will be available if furnace is capable of more stages.

SYSTEM

setting will allow the Infinity Control to determine furnace staging.

LOW

will only run the low stage of furnace heat.

LOW--MED

will run the low and medium stages (2 stages of heat).

MED

will

only run the medium stage of heat.

MED--HIGH

will run the

medium and high stages (2 stages of heat).

HIGH

will only run the

high stage of furnace heat.

G Terminal

This setup option selects desired operation when the R--G circuit

changes state on the furnace control board depending on setup.

S

DISABLED (Default)

S

FAN -- turns on fan to selected fan speed when G terminal is
energized. See Fig. 26. This setting is used in conjunction with
fresh air supply products (e.g. fresh air/make--up air dampers).

S

FAN SPEED -- select Low, Med, High for all zones when G
terminal is energized

S

SHUTDOWN -- shuts off fan and equipment when initiated.
This function is not intended for emergency fire shutdown. It
may be activated by a dry contact from an external device such
as a float switch or a relay. User Interface displays SYSTEM
MALFUNCTION on screen and registers G terminal shutdown
event in Last 10 System Events. See Fig. 27.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: