background image

7

Equipment Summary

The “EQUIPMENT SUMMARY” screen will appear after
Accessories have been selected. This screen will give a summary of

all equipment automatically found or manually selected. If a wrong

selection was made, press left--side button (BACK selection) to go
back to that particular screen and make changes. When everything

is OK, press right--side button again to continue. (See Fig. 20.)
The “SETUP COMPLETE! SAVE ALL SELECTIONS?” screen

will appear after Equipment Summary. To Save All Selections
press (YES) right--side button. Pressing the left--side button (NO

selection) will return to the Equipment Summary screen where

changes can be performed to any of the equipment selection
screens. After selecting YES, the initial power up sequence of the

new Infinity Control is complete.

EQUIPMENT SUMMARY

FURNACE

58MVB0100-12

AC

24ANA136A003

FILTER

EAC

HUMIDIFIER

YES

UV LIGHTS

YES

   NO                           YES

SETUP

COMPLETE!

SAVE

ALL SELECTIONS/

   NO                           YES

A07247

Fig. 20 -- Equipment Summary

Static Pressure Check

STATIC

PRESSURE

CHECK

PLEASE WAIT

EXTERNAL STATIC

PRESSURE

MEASURED:

0.72 INCHES

AT 1200 CFM

CONTINUE >

A05000

Fig. 21 -- Static Pressure Check

This screen will appear after Setup is exited. The system will

perform a static pressure check. This process will take about 1 1/2
minutes to complete. When completed, a screen will appear

displaying the static pressure (in inches) across the equipment at
the expected highest delivered airflow. If the blower RPM is

greater than 1200, then a warning will appear, but equipment
operation and the TrueSense

t

dirty filter detection operation will

not be affected.

NOTE

: The static pressure check occurs only at initial installation,

or when INSTALL is run in the INSTALL/SERVICE menu.

QUICK START

For first time installers, Quick Start will allow a quick start up of

the Infinity System before learning all the details of system
operation. However, for the best possible comfort and operation

refer to the Infinity Control Owner’s Manual.

Set Day, Time & Desired Humidity

1. Open the door of the Infinity Control and press the

BASIC

button.

2. Adjust the highlighted

HOUR

setting using the

LEFT

Up/

Down button.

3. Press

SCROLL

button (down) to highlight

MINUTE

.

4. Adjust the

MINUTE

setting using the

LEFT

Up/Down

button.

5. Press

SCROLL

button (down) to highlight

DAY

.

6. Adjust the current

DAY

setting using the

LEFT

Up/Down

button.

7. Press

SCROLL

button (down) to highlight

HUMIDITY

.

8. Press the red

HEAT

button to select heating humidity.

9. Adjust desired heating humidity level using either (+/--) but-

ton.

10. Press the blue

COOL

button to select cooling humidity.

11. Adjust the desired cooling humidity level using ei-

ther(+/--)button.

12. To exit press

BASIC

button or close door.

13. If changes are made, you will be asked to “

SAVE

CHANGES? YES/NO

.”

Override Heating Schedule

1. Press the red

HEAT

button. Heating mode is confirmed

when the red LED next to the red

HEAT

button is lit.

2. Use the

RIGHT

Up/Down button to select your desired

heating temperature.

3. The default time for temporarily overriding the temperature

schedule is 2:00 HRS as indicated by the text on the lower
left.

NOTE

: Override time will not appear if programming has been

turned off.

4. You can change the temporary override time in 15--minute

increments by pressing the

LEFT

Up/Down button until

the desired override time is selected, or press the

HOLD

button anytime to override the schedule indefinitely.

Quick Program Schedule For All Days

This section will give you a quick program schedule for

ALL

DAYS

of the week. For more information on how to create

customized schedules for every day, the entire week, or weekend,
refer to the Owner’s Manual.

1. Open the door of the control.
2. Press the

SCHEDULE

button, which allows you to create

one schedule for the entire home.

3. Press either the

LEFT

or

RIGHT

side button repeatedly (if

necessary) until

“ALLDAYS”

is displayed. The

WAKE

time period will be highlighted.

4. Using the

LEFT

Up/Down button, set the start time for this

time period.

5. Press the red

HEAT

button. Heating temperature will begin

flashing.

6. Set the heating temperature using the

RIGHT

Up/Down

button.

7. Press the blue

COOL

button. Cooling temperature will be-

gin flashing.

8. Set the cooling temperature using the

RIGHT

Up/Down

button.

9. Set the remaining periods by using the

SCROLL

button to

select “

DAY

”, “

EVENING

”, and “

SLEEP

”.

10. Exit the scheduling mode by either closing the door or

pressing the

SCHEDULE

button.

11. If changes are made, you will be asked to “

SAVE

CHANGES YES/NO.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: