background image

2

INSTALLATION, START--UP OVERVIEW

This instruction covers installation of the Infinity Control

only

.

Physical installation instructions for the indoor and outdoor

equipment, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the

Infinity System are covered only in this installation instruction. It is

the guide to connecting

the system components and

commissioning the system once all physical components are

installed. Special screen prompts and start--up capabilities are
provided in the Infinity System to simplify and automate the initial

commissioning of the system.

S

Install Infinity Control according to this instruction.

S

Install indoor unit, outdoor unit, and accessories according to
their instructions.

S

Wire complete system according to this instruction.

S

Setup, commission, and operate system according to this
instruction to assure a smooth and trouble free start--up.

INSTALLATION

Check Equipment and Job Site

Inspect equipment. File claim with shipping company prior to

installation if shipment is damaged or incomplete.

Infinity Control Location and Wiring

Considerations

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect power before routing control wiring.

!

WARNING

All wiring must comply with national, local, and state codes.

Infinity Control Location

The Infinity Control User Interface is the command center for the

Infinity System. It should be located where it is easily accessible
and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines

should be followed:
The Infinity Control and Room Sensors should be mounted:

S

Approximately 5--ft (1.5 m) from the floor.

S

Close to or in a frequently used room, preferably on an inside
partitioning wall.

S

On a section of wall without pipes or ductwork.

The Infinity Control and Room Sensors should

NOT

be mounted:

S

Close to a window, on an outside wall, or next to a door leading
to the outside.

S

Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature--radiating objects which could cause a false
reading.

S

Close to or in direct airflow from supply registers.

S

In areas with poor air circulation, such as behind a door or in an
alcove.

Remote Room Sensor Option

A Remote Room Sensor can be used with the Infinity Control to

take the place of the User Interface internal temperature sensor.
This allows the Infinity Control to be mounted in areas with less

than optimal airflow (such as near an exterior door, window or in a

closet). The remote sensor can be wired to the terminal block
connectors labeled S1 and S2 at the User Interface backplate, or the

ZS1 and ZS1C connection at the Damper Control Module. In
either case, the Infinity Control will automatically detect the

Remote Room Sensor and ignore its internal temperature sensor.
Typically, one remote sensor is used but, multiple sensors may be

used and averaged in some applications. Averaging requires a
special series--parallel wiring method with a specific number of

sensors. See Fig. 2. It is also important to note the humidity sensor

cannot be remotely located, so do not locate the Infinity Control in
an area where humidity sensing may not be accurate.

Sensor 1

Sensor 2

Sensor 3

Sensor 4

S1

S2

A07116

Fig. 2 -- Remote Room Sensor -- Parallel Wiring

Wiring Considerations

Ordinary thermostat wire is recommended. Use 22 AWG or larger
for normal wiring applications. Continuous wire lengths over 100

ft. should use 20 AWG or larger.

NOTE

: ABCD bus wiring only requires a four--wire connection;

however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
installation.
Each communicating device in the Infinity System has a four--pin
connector labeled ABCD. It is recommended that the following

color code be used when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each

ABCD connector in the system MUST be wired consistently.

Shielded Wire

If the thermostat wiring will be located near or in parallel with high

voltage wiring, cable TV or Ethernet wiring, then shielded

thermostat wire can be used to reduce or eliminate potential
interference. The shield wire should be connected to the C

terminal, or ground, at the indoor unit. The shield wire should
NOT be connected to any terminal at the user interface. Connecting

the shield to ground at both ends can cause current loops in the

shield, reducing shield effectiveness.

Mounting Infinity Control

First become familiar with all plastic assembly pieces shown in

Figures 3 through 10. The User Interface will snap together with
the backplate.
A backplate is supplied (see Fig. 4 and 5). Attach backplate using

only a small hole in the wall allowing a four wire connection to
pass through. Mount the assembly to the backplate.

NOTE

:

Once Infinity Control is secured to wall with the

backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing.

Decorative Backplate

Sold separately, a thin decorative backplate (see Fig. 6 and 9) is

available to hide any marks/screw holes left from the previous
thermostat. This decorative backplate (or beauty ring) is used by

snapping it onto the back of the mounting plate before securing the
plate to the wall.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: