background image

4

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury,

death or equipment damage.
Before installing, modifying, or servicing system, the main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

!

WARNING

1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced:

a. Remove existing control from wall.

b. Disconnect wires from existing control.

c. Discard or recycle old control.

NOTE

: Mercury is a hazardous waste, if existing control contains

any mercury, it MUST be disposed of properly. The User Interface
does not contain mercury.

3. Select Infinity Control mounting plastic (recess mount or

surface mount and decorative backplate if desired).

4. Route wires through large hole in mounting plastic. Level

rear plastic against wall (for aesthetic value only -- Infinity

Control need not be level to operate properly) and mark
wall through two mounting holes.

5. Drill two 3/16--in (4.8 mm) mounting holes in wall where

marked.

6. Secure mounting plastic to wall using two screws and an-

chors provided.

7. Adjust length and routing of each wire to reach each wire

entry on the connector backplate. Strip 1/4--in (6.4 mm) of
insulation from each wire.

8. Match and connect thermostat wires to proper terminals on

User Interface backplate. See wiring diagram Fig. 11, 12,
and 13.

A

B

C

D

A

B

C

D

User Interface

Green

Yellow

White

Red

OAT

Optional Remote

Room Sensor

HUM

COM
24V

Humidifier

Connection

S2

S1

A

B

C

D

ABCD

Connections

Communicating

 AC or HP

Green

Yellow

White

Red

OAT

Sensor

(Optional)

Variable-Speed

Furnace/ Fan Coil

A03146

Fig. 11 -- Universal Four--Wire Connection Diagram

A

B

C

D

A

B

C

D

C

Y

ABCD

Connection

User Interface

           1-Spd. 
Non-Communicating
              AC

 

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

COM

24V

Humidifier

Connection

   Y/Y2

S2

S1

OAT

OAT

Sensor

Variable-Speed

Furnace/Fan Coil

A07022

Fig. 12 -- Connection Diagram for Furnace or FE Fan Coil

w/1--Stage AC

A

B

C

D

A

B

C

D

ABCD

Connection

User Interface

            1-Spd. 
Non-communicating
               HP

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

C

Humidifier

Connection

   Y

S2

S1

W2

 Y

O

C

R

O

R

W

OAT

OAT

Sensor

Variable-Speed

Fan Coil

G

A07023

Fig. 13 -- Connection Diagram for FE Fan Coil with

Non-- Communicating 1--stage HP

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)

NOTE

: It is not mandatory that the above color code be used, but

each ABCD connection in the system MUST be wired consistently.
A separate ABCD Connector comes inside packaging and should
be used when connecting to furnace (or fan coil). Ensure connector
is inserted properly into circuit board. (See Fig. 14.)

A B C D

A03193

Fig. 14 -- Wire ABCD Connector

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: