background image

15

Run Times:

S

Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.

S

Kilowatt hours used of electric reheat for dehumidification.

Service -- Today’s Date

This menu item allows the installer to enter the current date. It is

used for time/date stamping of system faults. This should be
verified every time prior to viewing “LAST 10 SYSTEM

EVENTS” section.

Service -- Model / Serial Numbers

This menu item allows the installer to view the model number and
serial number (if available) of all communicating pieces of

equipment in the system. This is only available in original factory
supplied circuit board. If a circuit board is replaced, the model and

serial number information is no longer available.

Service -- Service Phone Number

This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the

system. This name and phone number will appear to the
homeowner whenever a service reminder pop--up message is

displayed (i.e. Change Filter, etc.).
To edit:

S

Use Right Up/Down button to move cursor left and right.

S

Use Left Up/Down button to select numbers and letters.

S

Use Scroll button to move up and down between NAME and
NUMBER.

OPERATIONAL INFORMATION

Continuous Fan Operation

Pressing FAN button will scroll through the following:

S

AUTO = No fan operation except during equipment operation.

S

LOW = Approximately 50% of High Speed operation.

S

MED = Half way between High and Low speed operation.

S

HIGH = Highest of either High Heating or High Cooling CFM.

Continuous fan operation is programmable. The programming
option must be enabled in the Thermostat Setup. See the

Homeowner’s Manual for detailed instructions on programming

the fan.

Five--Minute Compressor Timeguard

This timer prevents compressor from starting unless it has been off

for at least 5 minutes. It can be defeated by simultaneously pressing
the Fan and Right Up buttons.

Emergency Heat (for heat pump applications)

To activate Emergency Heat, you must press and hold the HEAT

button for 3 seconds to activate. Repeat to deactivate.

Heat Source Selection (Hybrid or Hydronic Heat)

If user wishes to override normal operation in Hybrid Heat or

Hydronic Heat applications, press and hold the heat button for 3
seconds to select desired heat source.

Keypad Lockout

Keypad can be locked by pressing “Fan” and “Humidity/Oat”

buttons at the same time for 3 seconds. When keys are locked, a
lock symbol will appear in the upper left corner of screen. Follow

same procedure to unlock keypad.

Heat and Cool LED

The Heat and Cool LEDs will pulsate during actual equipment

operation. This can be defeated in the Advanced Setup Screens.

Equipment Cycle Timer (adjustable 4--6 cycles per

hour)

This timer prevents the start of a heating or cooling cycle until 15
(or 10) minutes after the last start of the same cycle. Its function is

to assure that the equipment is not cycled more than the selected

times per hour. This timer is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature is

manually changed. It can also be defeated for one cycle by
simultaneously pressing the Fan and Right Up buttons.

Staging Timer

In multistage heating or cooling, this timer prevents any higher

stage from turning on until the preceding stage has been on for 10
minutes.
For furnace heating, the high stage timer is adjustable to force
longer minimum low stage run time. See Furnace Setup for details.

A demand of 5

_

or more will override the staging timer and allow

higher stages to energize.
In Hybrid Heat, the staging timer is 15 minutes between heat pump

and gas furnace operation. This timer is adjustable in the Hybrid
Heat Setup menu to force longer minimum heat pump run time and

longer low stage furnace run time. A demand of 5

_

F or more will

override the staging timer and allow higher stages to energize.

Three--Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a

minimum of three minutes. If the setpoint is changed, this timer is
automatically cancelled, allowing the equipment to turn off

immediately when the demand is removed.

Heat/Cool setpoints (Desired Temperatures)

A minimum difference of 2

_

(default) is enforced between heating

and cooling desired temperatures. This is done by allowing one

setting to “push” the other to maintain this difference. This
difference is adjustable via the Install/Service menu under

Thermostat Setup.

Temperature Display

The actual temperature displayed is always rounded toward the

setpoint. This is because the system is operating and measuring the

temperature in sixteenths of a degree, but displaying in whole
numbers. The system may be turned off and on within .5

_

of

setpoint, but the display may not change. This is by design and
does not indicate a problem with the control.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat

to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the setpoint is changed, the

30--minute requirement is defeated. This Auto Changeover time is
adjustable via the Install/Service menu under Thermostat Setup.

Range = 5 -- 120 min.

Smart Recovery

With Smart Recovery selected (factory default), transition out of
setback begins 1.5 hours before selected recovery time and

gradually adjusts room temperature so desired temperature will be
achieved at selected recovery time. It operates in both heating and

cooling. This only applies to programmable operation.
For example: Set back temperature in heating is 64

_

F. Smart

Recovery setpoint is 70

_

F at 7:00 a.m. At 5:30 a.m., the control

calculates the required temperature recovery rate (recovery temp --
set back temp or current temp if greater) / 90 minutes. If the current

temp at 5:30 = 66

_

F, the recovery rate = (70 -- 66)

_

F/90 minutes =

0.04

_

per minute. In order to achieve setpoint, the control ramps up

the setpoint 0.04

_

F / minute from 5:30 a.m. until 7:00 a.m. This

changing setpoint is displayed while it is occurring.

NOTE

: Temperatures should not be set back so far that the

equipment cannot recover in 90 minutes.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: