Air Filter

If

AIR FILTER

or

AIR PURIFIER

is installed in the indoor unit,

the system will perform a static pressure check of the system every

24 hours at 1:00 p.m. to monitor filter accumulation (TrueSense

t

Dirty Filter Detection) or whenever power is applied to the system
or the system is transitioned from Off to Cool or Heat modes. The

blower will run at a medium airflow for one minute.
This system operates by setting a base line static pressure based on

the highest airflow the system could run (this could be heat or cool
airflow). The measurement is taken at a low airflow and then

calculated up to the highest airflow the system could see.

Frozen Coil Detection

During cooling operation, the User Interface will monitor the static
pressure of the system. If the static pressure is increasing

dramatically, the User Interface will turn off cooling for up to one
hour, record fault in the “Last 10 Events” screen, and run the fan at

a reduced airflow. The User Interface will continue to monitor the

static pressure. If it is reduced before one hour has elapsed, it will
resume cooling operation. After one hour, cooling will be resumed.

Dehumidify Operation

Once a target cooling humidity setpoint is selected in the Advanced
Setup COOLING HUMIDITY screen, two other setup options

affect Dehumidify operation: COOLING AIRFLOW and

DEHUMIDIFY.
COOLING AIRFLOW: Setting this to

COMFORT

or

QUIET

will enable the system to use low airflow to help dehumidify the
space. If duct sweating becomes an issue, setting DEHUM

AIRFLOW to

HIGH

may resolve the problem.

DEHUMIDIFY: Located in the Cooling Humidity screen of the
Advanced Setup, this option has 2 settings:

ON

and

OFF

.

If DEHUMIDIFY is set to

ON

(factory default), then the cooling

unit will be allowed to overcool the space up to 3

_

F (2

_

C) if the

humidity level is above the cooling humidity target setpoint.
The amount of over--cooling allowed varies with the

dehumidification demand, the cooling demand, and the actual

space temperature. More over--cooling is allowed with greater
dehumidification demand.
When the space temperature is at or above 75

_

F (24

_

C) and the

dehumidify demand is high, over--cooling up to 3

_

F (2

_

C)

is

allowed. As the space temperature approaches 70

_

F (21

_

C), less

over--cooling is allowed. At 70

_

F (21

_

C) space temperature, no

more over--cooling is allowed no matter how great the dehumidify

demand. This is done to protect the equipment.
If DEHUMIDIFY is set to

OFF

and Cooling Airflow is set to

COMFORT

, normal dehumidification mode is enabled. For

normal dehumidification, no over--cooling is allowed when the
cooling humidity is above the target setpoint, but airflow will be

reduced during a normal cooling mode to reduce humidity. The
airflow depends on the amount of dehumidify demand. If Cooling

Airflow is set to

EFFICIENCY

or

MAXIMUM

, only

Dehumidify (over--cooling to dehumidify) will be performed.

Hybrid Heat Setup / Operation

Furnace Lockout

(

in HYBRID HEAT SETUP menu) is the

outside temperature above which the furnace will not run except

for defrost (otherwise known as the aux heat lockout).

Heat Pump Lockout

— (in HYBRID HEAT SETUP) is the

outside temperature below which the heat pump will not run

(otherwise known as the balance point).
These values can be set identical to each other. If they are not

identical, the system will stage up and down normally from heat
pump to furnace when the outside temperature is between these

settings. The User Interface will not allow the heat pump lockout

setting to be above the furnace lockout setting.
The factory default settings for both of these is NONE (no

lockouts). Even though a heat pump lockout temperature may be
set, the system will still use the furnace in defrost operation, and

may stage back down to heat pump when defrost is completed after

a 2 minute delay.

Hybrid Heat Defrost

— (in HYBRID HEAT SETUP) When the

outdoor unit needs a defrost cycle, the furnace will run during
defrost regardless of lockout temperature, unless told not to in the

Hybrid Heat Setup screen. After defrost, the system may stage

down to heat pump after a 2 minute delay.
If the room temperature falls below 40

_

F (4

_

C) and a furnace

lockout is in enabled, the furnace lockout will be overridden to
bring on the furnace.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: