background image

11

Heater Size:

S

(choices dependent upon fan coil model)

This will show the heater size entered during the start--up process.

This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self--identifying, this

value is not shown.

Elect Heat Lockout

S

NONE (default)

S

+5 to 55

_

F (--15 to 13

_

C)

Outside temperature above which the electric heat will not operate
except for defrost.

G Terminal

This setup option selects desired operation when the R--G circuit

changes state on the fan coil control board depending on setup.

S

DISABLED (Default)

S

FAN -- turns on fan to selected fan speed when G terminal is
energized. See Fig. 26. This setting is used in conjunction with
fresh air supply products (e.g. fresh air make--up air dampers).

S

FAN SPEED -- select Low, Med, High for all zones when G
terminal is energized

S

SHUTDOWN -- shuts off fan and equipment when initiated.
This function is not intended for emergency fire shutdown. It
may be activated by a dry contact from an external device such
as a float switch or a relay. User selects whether the contact is
NC -- normally closed (default) or NO -- normally open. User
Interface displays SYSTEM MALFUNCTION on screen and
registers G terminal shutdown event in Last 10 System Events.
See Fig. 27.

Dehum Drain

Turns off the continuous fan at the end of cooling for five minutes

in order to drain the indoor coil of water. The fan will only be

turned off if a dehumidify demand existed at the start of or during
the cooling cycle. Default is enabled.

Reheat Dehum

Enables electric heat to be used while Cool to Dehumidify is

running. This will allow the Cool to Dehumidify function to run
much longer, greatly improving humidity control in cooling mode.

Accumulated electrical energy used while reheating (in
kilowatt--hours) is shown on the Fan Coil Run Hours screen and

can be reset there. This is only available with fan coil systems.

Setup -- Heat Pump / AC

Cooling Lockout:

S

NONE (default)

S

45

_

F (7

_

C)

S

50

_

F (10

_

C)

S

55

_

F (13

_

C)

Outside temperature below which cooling will not be provided.

Low Ambient Cooling:

S

NO (default)

S

YES

Selecting

YES

will enable the low ambient cooling operation in

the outdoor unit. This setting is only available with communicating
outdoor units and with Cooling Lockout set to

NONE

. Low

ambient kits are not needed with communicating outdoor units.
For detailed sequence of operation, see outdoor unit installation

instructions.

Entered Size:

S

(dependent on indoor unit model)

Size of the outdoor unit entered during the start--up process. If the

outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the

indoor unit can handle.

Defrost Interval:

S

30 minutes

S

60 minutes

S

90 minutes

S

120 minutes (default)

S

Auto--Defrost interval optimized by outdoor control (default for
communicating HP)

Time interval at which defrost cycles can occur on a heat pump.

Lockout Temp:

S

Off (default)

S

+5 to 55

_

F (--15 to 18

_

C)

Locks out the heat pump from operating below the selected outside

temperature. Appears with a fan coil only. Must be below any
electric lockout temperature in Fan Coil Setup.

Quiet Shift

S

Off (default)

Turns on Quiet Shift function in 1--stage or 2--stage

communicating heat pumps.

High Cool Latch:

S

NONE (default)

S

On

S

80 to 110

_

F (27 to 43

_

C)

S

DISABLE (disable use of high cool stage)

Outside temperature above which only the high stage (of a 2--stage
outdoor unit) will run when cooling.

High Heat Latch

S

OFF (default)

S

On

S

20 to 50

_

F (--7 to 10

_

C) 2 --stage heat pump runs only high

stage heating below a selectable outdoor temperature. Selections
from 20 to 50

_

F (--7 to 10

_

C) are available in 5

_

F (3

_

C)

increments.

S

DISABLE (disable use of high heat stage)

Max Heat RPM (Appears with variable capacity heat pump)

Clamps the operating speed of the heat pump to this maximum.
Used to reduce operating noise while in high heating capacity.

Reducing this value will reduce the heating capacity of the heat

pump.

Heat Pump Airflow (Capacity) Limiting

The following settings allow the installer to restrict the heat pump
within certain minimum and maximum airflows. These airflows are

converted to capacities. The Min and Max limits are determined by
the equipment size.
Min CFM (only appears with variable capacity heat pump)
Minimum CFM to run a variable capacity heat pump. This will
increase the minimum operating capacity of the heat pump. Default

value is the heat pump air flow for the lowest heat capacity.
Maximum CFM (only appears with variable capacity heat pump)
Maximum CFM to run a variable capacity heat pump This will
reduce the operating capacity of the heat pump. Default value is the

heat pump air flow for the highest heat capacity.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: