12

Lo Air Multiplier

Adjusts the low airflow speed on non--communicating two--stage

units. Choose 0.65 for units with a Bristol compressor, choose 0.80
(default) for units with a Copeland scroll compressor.

Setup -- Hybrid Heat

 

HYBRID HEAT SETUP

FURNACE
LOCKOUT:

> 30 F

HEAT PUMP
LOCKOUT:

< 15 F

DEFROST W/FURNACE:

YES

< BACK

HP TO FURNACE
STAGE TIME:

15 MIN

OUTSIDE LOCKOUT TEMPS

A07030

Fig. 28 -- Hybrid Heat Setup

FURNACE LOCKOUT -- Temperature above which only the heat

pump will operate, except for defrost.

S

Default = NONE

S

Available settings = NONE thru >55

_

F (13

_

C)

HEAT PUMP LOCKOUT -- Temperature below which only the

furnace will operate.

S

Default = NONE

S

Available settings = NONE thru <55

_

F (13

_

C)

DEFROST W/FURNACE -- Choose whether furnace operates
during defrost cycle.

S

Default = YES

S

Available settings = YES / NO

HP TO FURNACE STAGING TIME -- Adjust the minimum
amount of time the heat pump will run before furnace will be

allowed to run.

S

Default = 15 MIN

S

Available settings = 15--60 minutes. If a demand of 5

_

F (3

_

C) or

greater exists, the timer will be overridden.

Setup -- Hydronic Heat

 

HYDRONIC HEAT SETUP

AIRFLOW:

800 CFM

BLOWER ON DELAY:

30 SEC

HOT WATER
LOCKOUT:

> 30 F

HEAT PUMP
LOCKOUT:

< 45 F

DEFROST W/WATER:

YES

BLOWER OFF DELAY: 30 SEC

< BACK

A07031

Fig. 29 -- Hydronic Heat Setup

HOT WATER LOCKOUT -- Outside temperature above which the

hot water will not operate except for defrost (if needed).

S

Available settings -- NO, 5 to 55

_

F (--15 to 13

_

C) in 1

_

increments

HEAT PUMP LOCKOUT -- Outside temperature below which
only the hot water will run, 1

_

F (.6

_

C) resolution.

S

Appears only with a heat pump outdoor unit.

S

Available settings -- NO, 5 to 55

_

F (--15 to 13

_

C) in 1

_

increments

DEFROST W/WATER:

S

Available settings: YES / NO (Default =YES)

S

Appears only if heat pump is available If no, hot water will not
run during a defrost.

AIRFLOW -- Selects desired airflow during Hydronic Heating

S

Available range from OFF, 500 CFM(minimum) to 400

CFM/ton cooling maximum in 50 CFM increments.

S

Default is the cooling airflow. (350 CFM/ton)

S

OFF selection does not turn off airflow if heat pump is
defrosting.

BLOWER ON DELAY -- Time after hot water is requested that the

blower will turn on.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 30

BLOWER OFF DELAY-- Time after hot water request terminates
before the blower will turn off.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 0.

Setup -- Accessories

Filter Type:

S

AIR FILTER (i.e. TrueSense

t

)

S

ELEC. AIR CLEANER

S

AIR PURIFIER (i.e. TrueSense

t

)

CLEAN INTERVAL: Never, 1 to 18 months. (Default = 90)
Enables a timer for the filter notification.
Interval at which the Clean Filter notification will turn on.
PRESSURE MONITOR: ENABLE/DISABLE -- enables the static

pressure calculation for media--type filters.

Humidifier Installed:

S

NO

S

YES

If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default = 12
months)
Interval at which the Change Humidify Pad notification will be

displayed.
HUMIDIFY WITH FAN: (Heating Mode Only)

S

NO (default)

S

YES

If YES, the humidifier will turn on if there is a humidify demand
present. The fan will turn on to Low speed if the fan setting is

Auto.

Ventilator:
NOTE

: Only appears if ventilator is installed.

CLEAN INTERVAL:

S

60 to 180 days of actual operation (default = 90)

Interval at which the Clean Ventilator Pre--filter notification will

turn on.

UV Lights Installed

S

NO

S

YES

If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:

S

6 to 48 months operation time (default = 12 months)

Interval at which the Change UV Lights notification will be
displayed.

Setup -- System Maintenance

Remind Owner of Routine Maintenance Every:

This setup is used to adjust the timer interval in which the normal

System Maintenance notification is turned on for the homeowner.
(See Fig. 30.)
Range =

S

OFF

S

6 to 24 months, (default = 12 months)

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: