background image

13

 

SYSTEM  MAINTENANCE

< BACK

REMIND OWNER OF
MAINTENANCE EVERY:

12  MONTHS

% USED:

50%

RESET >

A07033

Fig. 30 -- System Maintenance

Pressing the right side button will reset the timer. Pop--up

confirmation will be shown.

Setup -- Utility Saver

Cooling/Heat Pump Heating: (Hybrid Heat & Hydronic Heat
Only)

S

Turn off, Low Stage

Utility Saver is used to force the equipment to a lower stage (low

or off) when activated by the utility company, typically during

peak load times.
This setup is available only if the equipment has a utility saver

input (refer to outdoor equipment Installation Instructions). This
setup controls the response of the equipment when the utility saver

input is active.
The choices include:

S

Turn Off , (equipment turns off)

S

Low Stage (available if the AC/heat pump is a 2--stage model,
runs low speed only)

CHECKOUT MENUS

The Checkout menu will show the equipment installed in the

system. A sample checkout menu is shown in Fig. 31.

CHECKOUT

FURNACE

HEAT PUMP HEATING

HEAT PUMP COOLING

HUMIDIFIER

VENTILATOR

   BACK               SELECT

A03204

Fig. 31 -- Checkout Menu

Checkout -- Furnace or Gas PAC

Make sure the furnace is properly installed before continuing.

S

LOW HEAT RUNTIME: 5 min.

S

HIGH HEAT RUNTIME: 5 min.

This menu item allows the furnace to be exercised. First, a low heat

runtime and high heat runtime are selected. Range = 5 -- 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start--up sequence. This

sequence will be displayed on the Infinity Control screen. After the
gas valve and blower motor turn on, the screen will automatically

change to “

FURNACE CHECK

” and show the current operating

status of the furnace.

Checkout -- Electric Heat

S

ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min.,
Range = 0 -- 120 min.

If you have a fan coil with electric heaters, this menu item will

allow the heaters to be exercised.

With self--identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non--identifying

heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised

then press START (right--side button). The display will change to

show the fan coil’s operating status.

Checkout -- Heat Pump Heating

S

HIGH HEAT RUNTIME: 5 min.

S

LOW HEAT RUNTIME: 5 min.

S

DEFROST: NO

The heat pump heating mode can be exercised with this menu

option. With a 2--stage heat pump, a low heat runtime and a high

heat runtime are independently selectable to exercise. A defrost
cycle is also selectable. Default time = Fixed 5 min. minimum,

range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.

Checkout -- Heat Pump Cooling or AC Cooling

S

HIGH COOL RUNTIME: 5 min.

S

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2--stage heat pump or AC

unit, a low cool runtime and a high cool runtime are independently

selectable to exercise. The display will change to show the heat
pump or AC operating status.
Default time = Fixed 5 min. minimum, range = 5 -- 120 min.

NOTE

:

Airflows during Checkout modes are fixed to the

Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump (or AC) cooling mode, exit the
Checkout screen and apply a cooling demand to the system.

Checkout -- Humidifier

S

OFF

S

ON

The humidifier can be exercised On and Off with this menu option.

Charging (Appears with Variable Capacity Heat

Pump)

S

Enables charging mode of the variable capacity heat pump.

Evacuation (Appears with Variable Capacity Heat

Pump)

S

Allows the heat pump to be evacuated of refrigerant.

EXV Position (Appears with Variable Capacity

Heat Pump)

S

Positions the Electronic Expansion Valve (open or closed)

Charge Calculation (Appears with Variable

Capacity Heat Pump)

S

Calculates the amount of charge needed in the system. Takes into
account lineset length, liquid line diameter, and indoor coil
model.

Checkout -- Ventilator

Speed:

S

OFF

S

LOW

S

HIGH

The ventilator can be exercised through all of its operating speeds

with this menu option.

UID

01

--

V

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...

Reviews: