20
Free Cooling Status Menu – FCOOL_ST (continued)
No. Point name
Status
Unit
Displayed text*
Description
6
fc_fanst
0 to 10
-
FC Fan Stage
Free Cooling / Dry Cooler fan stage
7
fc_fansp
0 to 100
%
FC Varifan Speed
Free Cooling / Dry Cooler: Fan speed
8
FC_HOUR
0 to 999999
hour
FC Operating Hours
Free Cooling / Dry cooler: Operating hours
9
FC_FAN1S
0 to 999999
-
FC Fan Stage 1 Start
FC / Fan stage 1: Number of starts
10
FC_FAN1H
0 to 999999
hour
FC Fan Stage 1 Hours
FC / Fan stage 1: Operating hours
11
FC_FAN2S
0 to 999999
-
FC Fan Stage 2 Start
FC / Fan stage 2: Number of starts
12
FC_FAN2H
0 to 999999
hour
FC Fan Stage 2 Hours
FC / Fan stage 2: Operating hours
13
FC_FAN3S
0 to 999999
-
FC Fan Stage 3 Start
FC / Fan stage 3: Number of starts
14
FC_FAN3H
0 to 999999
hour
FC Fan Stage 3 Hours
FC / Fan stage 3: Operating hours
15
FC_FAN4S
0 to 999999
-
FC Fan Stage 4 Start
FC / Fan stage 4: Number of starts
16
FC_FAN4H
0 to 999999
hour
FC Fan Stage 4 Hours
FC / Fan stage 4: Operating hours
17
FC_FAN5S
0 to 999999
-
FC Fan Stage 5 Start
FC / Fan stage 5: Number of starts
18
FC_FAN5H
0 to 999999
hour
FC Fan Stage 5 Hours
FC / Fan stage 5: Operating hours
19
FC_FAN6S
0 to 999999
-
FC Fan Stage 6 Start
FC / Fan stage 6: Number of starts
20
FC_FAN6H
0 to 999999
hour
FC Fan Stage 6 Hours
FC / Fan stage 6: Operating hours
21
FC_FAN7S
0 to 999999
-
FC Fan Stage 7 Start
FC / Fan stage 7: Number of starts
22
FC_FAN7H
0 to 999999
hour
FC Fan Stage 7 Hours
FC / Fan stage 7: Operating hours
*Depends on the selected language (English by default).
Modes Menu – MODES
No. Point name
Status
Unit
Displayed text*
Description
1
m_delay
no / yes
-
Delay Active
Start-up delay in effect
2
m_2ndspt
no / yes
-
Second Setpoint Active
Second setpoint in use: The setpoint used during
unoccupied periods
3
m_reset
no / yes
-
Reset Active
Setpoint reset active
4
m_limit
no / yes
-
Demand Limit Active
Demand limit active
5
m_ramp
no / yes
-
Ramp Loading Active
Ramp loading active
6
m_cooler
no / yes
-
Cooler Heater Active
Pump enabled for freeze protection
7
m_clpmpp
no / yes
-
Cooler Pump Per. Active
Evaporator pump active periodically
8
m_cdpmpp
no / yes
-
Cond. Pump Per. Active
Condenser pump active periodically
9
m_night
no / yes
-
Night Low Noise Active
Night low noise active
10
m_SM
no / yes
-
System Manager Active
System Manager active
11
m_leadla
no / yes
-
Master Slave Active
Master/slave mode active
12
m_heater
no / yes
-
Electric Heat Active
Electric heating active
13
m_lo_ewt
no / yes
-
Heating Low EWT lockout
Heating low EWT lockout
14
m_boiler
no / yes
-
Boiler Active
Boiler active status
15
m_ice
no / yes
-
Ice Mode Active
Ice mode active (cooling setpoint 3 is used)
16
m_sst_a
no / yes
-
Low Suction Circuit A
Low suction, circuit A
17
m_sst_b
no / yes
-
Low Suction Circuit B
Low suction, circuit B
18
m_dgt_a
no / yes
-
High DGT Circuit A
High DGT, circuit A
19
m_dgt_b
no / yes
-
High DGT Circuit B
High DGT, circuit B
20
m_hp_a
no / yes
-
High Pres Override cir A
High pressure override, circuit A
21
m_hp_b
no / yes
-
High Pres Override cir B
High pressure override, circuit B
22
m_sh_a
no / yes
-
Low SuperHeat circuit A
Low superheat, circuit A
23
m_sh_b
no / yes
-
Low SuperHeat circuit B
Low superheat, circuit B
24
m_dhw
no / yes
-
Domestic Hot Water Mode
Domestic hot water mode status
25
m_summer
no / yes
-
Summer Mode Active
Summer mode status
*Depends on the selected language (English by default).