3.6 -  Actuators

Electronic Expansion Valve

The electronic expansion valve (EXV) is used to adjust the 

refrigerant.flow.to.changes.in.the.operating.conditions.of.the.

machine. The high degree of accuracy with which the piston 

is.positioned.provides.precise.control.of.the.refrigerant.flow.

and suction superheat.

Flow switch

For.units.without.internal.pumps,.a.flow.switch.is.mounted.
to.ensure.that.the.minimum.flow.rate.required.for.the.correct.

operation and protection of the system is maintained. If the 

flow.switch.fails,.the.alarm.condition.shuts.off.the.unit.

Water pumps (optional)

The controller can independently regulate each water heat 

exchanger.pump..Touch.Pilot.Junior.enables.constant.flow.

control based on the minimum pump speed setpoint.

Water.flow.control.can.also.be.based.on.the.heat.exchanger.

temperature difference or the water pressure difference.

Boiler

If there is a unit fault in the heating mode this output authorises 
start-up and shutdown of a boiler. 30WG/30WGA units can 

be.fitted.with.a.boiler.which.is.energised.only.when.requested.

by the controller in case of heating demand

For 61WG units, 

the boiler is activated when the operating conditions are not 
suitable for thermodynamic heating or the unit is down due 
to a detected failure. See also section 8.10.1.

Electric heaters

Electric heaters are used as a supplementary heating source 
in the heating mode. See also section 8.10.2

.

3.7 -  Available connections

Connections available at the user terminal block may vary 
depending on the selected options. The following table 
summarizes connections at the user terminal block.

IMPORTANT:

 Some contacts can be accessed only when 

the unit operates in Remote mode.

3.7.1 -  Terminal block connections

Description

Board

Connector Remarks

Remote On/Off 

contact

SIOB, 

cir A

+:32/ -:33

Used for the unit on/off 

control (Remote mode)

Remote Heat/

Cool contact

SIOB, 

cir A

+:63/ -:64

Used to set cooling and 

heating when the unit is in 

Remote mode 

Switch-

controlled 

demand limit

SIOB, 

cir A

+:73/ -:74

Used to control demand 

limit

Switch dual 

setpoint

SIOB, 

cir A

+:65/ -:66

Used to select the second 

cooling setpoint

Lock switch

SIOB, 

cir A

+:34/ -:35

Used for the customer 

safety loops

Condenser 

3-way valve

SIOB, 

cir A

+:80+/-:80- Used to control the water 

flow on the condenser side

Boiler

SIOB, 

cir A

+:69/ -:70

Used to command a boiler

Running

SIOB, 

cir A

+:37/-: 38

Used to signal a running 

status (at least one 

compressor start)

Description 

(cont.)

Board 

(cont.)

Connector 

(cont.)

Remarks  

(continued)

Alarm

SIOB, 

cir A

+: 30/-: 31 Used to signal an alarm

Domestic hot 

water (DHW)

AUX1

-:310 / 

CH12: 311

Used to control domestic 

hot water production

Domestic hot 

water (DHW) 

priority switch 

AUX1

-:312 / 

+:313

Used to control domestic 

hot water priority

Summer 

switch

AUX1

-:323 / 

+:322

Used to stop the Space 

Heating loop additional 

pump during summer time

Electrical 

Heater Stage 1 

AUX1

341 / 12

Used to control the 

electrical heater stage 1 

Electrical 

Heater Stage 2 

AUX1

342 / 12

Used to control the 

electrical heater stage 2

Electrical 

Heater Stage 3 

AUX1

343 / 12

Used to control the 

electrical heater stage 3

Electrical 

Heater Stage 4 

AUX1

344 / 12

Used to control the 

electrical heater stage 4

Additional 

pump 

command

AUX1

365 / 12

Used to command the 

additional pump in case of 

DHW option

DHW  

diverting valve

AUX1

340 / 12

Used to command the DHW 

loop in case of DHW option

3.7.2 -  Volt-free contact (on/off and cooling/heating)

For units with a boiler, on/off contacts and cooling/heating 
contacts are as follows:

Off

Cooling

Heating

On/Off contact

open

closed

closed

Cooling/Heating contact

open

open

closed

Off: 

Unit is stopped

Cooling:  Unit is allowed to start in Cooling

Heating:  Unit is allowed to start in Heating 

3.7.3 -  Volt-free setpoint selection contact

When the unit is under remote control, the volt-free contact 
is used to determine the active setpoint. This dry contact is 
used to switch between setpoints. It is active only when the 
control is in Remote mode. See also section 8.5.1.

Contact

Active setpoint

SP1

SP2

SP3

Auto

SETP_SW1

open

close

open

close

SETP_SW2

open

open

close

close

3.7.4 -  Volt-free demand limit selection contact

One dry contact can be used to limit unit capacity. The limit 

threshold.can.be.defined.via.the.user.interface.in.the.Setpoint.

menu (see section 5.6).

100%

Limit 1

Limit 2

Limit 3

Demand limit 1 contact

open

closed

open

closed

3.7.5 -  Summer switch (HDC option)

For units with HDC option, the summer switch can be used 
to control with the volt-free contact.

Summer switch

Summer mode

open

not active

closed

active

Summary of Contents for AquaSnap 30WG Series

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Junior Control 30WG 30WGA 61WG...

Page 2: ...ns 10 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 11 5 1 Reading the Welcome screen 11 5 2 Exploring the Synoptic screen 11 5 3 Starting Stopping the unit 11 5 4 Setting the schedule 12 5 5 Display settin...

Page 3: ...t any time without notice 8 10 Additional space heating control 28 8 11 Built in DHW and space heating control HDC 29 8 12 Condensing pressure control optional 30 8 13 Master Slave control 30 9 DIAGNO...

Page 4: ...instructions prior to proceeding with any work Pay attention to all safety warnings The information provided herein is solely for the purpose of allowing customers to operate and service the equipment...

Page 5: ...trical cables and conduits terminal box covers and motor frames with great care 2 CONTROLLER OVERVIEW 2 1 Control system 30WG 30WGA 61WGunitscomewiththeTouchPilotJunior control that serves as a user i...

Page 6: ...f the green LED is not flashing this indicates a LEN bus wiring problem 3 4 Pressure transducers The control implements three types of pressure transducers where two pressure transducers high pressure...

Page 7: ...ustomer safety loops Condenser 3 way valve SIOB cir A 80 80 Used to control the water flow on the condenser side Boiler SIOB cir A 69 70 Used to command a boiler Running SIOB cir A 37 38 Used to signa...

Page 8: ...me screen will be displayed 4 2 Connections Connections are located on the bottom side of the controller The controller comes with two RS485 ports where the first port is used to connect to CCN Carrie...

Page 9: ...er password User password required Legend Genunit Config Schedule HDC Configuration Date Time Pump Configuration Holiday Reset Config Control Identification Heat Cool Config Broadcast User Configurati...

Page 10: ...rt no action taken on the unit Steady icon Alarm s active on the unit see section 9 5 OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the u...

Page 11: ...d 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 5 1 Reading the Welcome screen The Welcome screen is the first screen shown after starting the user interface It displays the application name as well as the...

Page 12: ...is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel button to exit the screen without making modificat...

Page 13: ...r level security ensures that only authorised users are allowed to modify critical unit parameters Only logged in users are allowed to access the Configuration menu It is strongly recommended to chang...

Page 14: ...ion is from a PC using a web browser with Java IMPORTANT UsefirewallsandVPNforsecureconnection 6 2 Opening the web interface To access theTouch Pilot Junior control enter the IP address of the unit in...

Page 15: ...ditional features some tables may contain parameters that cannot be configured for a given unit General Parameters Menu GENUNIT No Point name Status Unit Displayed text Description 1 CTRL_TYP 0 to 2 L...

Page 16: ...emperature circuit A 4 SST_B C Saturated Suction Tp B Saturated suction temperature circuit B 5 SUCT_A C Gas Suction Temp A Compressor suction temperature circuit A 6 SUCT_B C Gas Suction Temp B Compr...

Page 17: ...pen close Remote Setpoint Switch2 Remote Setpoint Switch 2 6 LIM_SW1 open close Limit Switch 1 Status Demand limit switch 1 7 LIM_SW2 open close Limit Switch 2 Status Not applicable please ignore this...

Page 18: ...oint Evaporator water delta temp setpoint 12 CL_WdpSp kPa Cool Water DP Setpoint Evaporator water delta pressure setpoint 13 CL_DvPos 0 to 100 Cool Pump drive position Evaporator pump drive position 1...

Page 19: ...ber of starts compressor A1 7 hr_cp_a2 hour Compressor A2 Hours Operating hours compressor A2 8 st_cp_a2 Compressor A2 Starts Number of starts compressor A2 9 hr_cp_a3 hour Compressor A3 Hours Operati...

Page 20: ...Displayed text Description 1 m_delay no yes Delay Active Start up delay in effect 2 m_2ndspt no yes Second Setpoint Active Second setpoint in use The setpoint used during unoccupied periods 3 m_reset...

Page 21: ...a given unit Genunit Config Menu GENCONF No Point name Status Default Unit Displayed text Description 1 lead_cir 0 to 2 0 Cir Priority Sequence Circuit priority 2 0 Auto 1 A Lead 2 B Lead 0 Automatic...

Page 22: ...the selected language English by default Heat Cool Config Menu HCCONFIG No Point name Status Default Unit Displayed text Description 1 cr_sel 0 to 3 0 Cooling Reset Select Cooling reset selection 2 hr...

Page 23: ...fu 30 1 to 52 2 40 5 C OAT Full Reset Value OAT max reset value 12 dt_hr_no 0 to 14 1 0 C Delta T No Reset Value Delta T no reset value 13 dt_hr_fu 0 to 14 1 0 C Delta T Full Reset Value Delta T max r...

Page 24: ...onth Day of the month 2 month 1 to 12 Month of year Month 3 year 20nn Year Year 4 dow Monday Sunday Day of Week Day of the week Time HH MM 5 hour 0 to 24 hour Hour Hour 6 minute 0 to 59 min Minute Min...

Page 25: ...operate in Cooling mode only The unit operation is based on the following parameters Unit On Off status This parameter indicates whether the unit is shut down not authorised to start or in operation...

Page 26: ...mpdel for cooler OR 4 Set PumpAuto Rotation Delay cdpmpdel for condenser Pump Auto Rotation Delay clpmpdel cdpmpdel 24 to 3000 h 48 h 8 4 3 Pump speed control If the pump with variable flow option has...

Page 27: ...g setpoint reset which can be applied if the condensing setpoint control depends on outdoor air temperature reading reset source OAT Cooling mode 30WG 30WGA 61WG Cooling control point reset is used to...

Page 28: ...et boiler manual command 1 Navigate to the Configuration menu 2 Select Heat Cool Config HCCONFIG 3 Set Boiler Manual Command boil_on Boiler Manual Command boil_on No OAT sensor logic is applied Yes Bo...

Page 29: ...ntinue to operate as described earlier The electric heater stages operate only in the heating mode but not during domestic hot water production 8 11 4 Heating or domestic hot water mode A three way va...

Page 30: ...ch Pilot Junior continuously optimises system operation to obtain the best system efficiency by controlling the number of fans required for any thermal load and outside temperature conditions 8 12 3 C...

Page 31: ...2 Select Current Alarms 3 The list of active alarms will be displayed 9 3 Resetting alarms The alarm can be reset either automatically by the control or manually through the touch panel display or th...

Page 32: ...12002 Circuit B Discharge Pressure Transducer Failure As above Circuit B shuts down As above 12004 Circuit A Suction Pressure Transducer Failure As above Circuit A shuts down Automatic up to 3 alarms...

Page 33: ...stand alone mode Automatic if communication is restored 10031 Unit is in CCN emergency stop Network emergency stop command Unit shuts down Automatic if emergency stop is deactivated 10032 Cooler pump...

Page 34: ...enser water loop failure pump overload Water loop pressure drop too low Unit shuts down Automatic 11107 Condenser water loop failure switch fail Switch fault Unit shuts down Automatic 6 times within 2...

Page 35: ...nd no serious damage can occur to your equipment The Manufacturer provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to he...

Page 36: ...rder No 10161 09 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: