8.11 -  Built-in DHW and space heating control (HDC)

30WG/61WG units with Heating Device Control are specially 
designed to optimise the operation of heating installations 
that require hot-water production for traditional heating and 
domestic hot water (DHW) requirements. In this case an 
AUX board is included in the unit control box.

The Touch Pilot J. control of the 30WG/61WG includes 
algorithms that permit constant and automatic optimisation:

•  Control of a three-way directional on/off valve based 

on the heating or domestic hot water requirements 
(3-way valve used to switch between Space Heating 
and Domestic Hot Water).

•  Control of the electric heater stages can complement the 

heating loop (booster heater), 1 to 4 electric heating stages.

•  Hot water setpoint reset (heating units) based on the 

outside air temperature (weather compensation function).

•  Priority control between heating and domestic hot 

water applications.

8.11.1 -  Sensor

Outside air temperature sensor can be used to reset the 
setpoint or determine the summer/winter mode. 

The control point is reset with a value calculated according 
to the outdoor air temperature reading.

8.11.2 -  User connection terminals

Three volt-free contacts are available at a user connection 
terminal board.

•  A contact for DHW demand from the tank.
•  A volt-free contact for DHW priority.
•  A volt-free contact for the summer mode.

8.11.3 -  Control of electric heater stages

The unit can control up to four electric heater stages as 
supplementary heating.

Electric heater stages are activated to supplement the heating 
capacity under the following conditions:

•  The unit uses 100% of its available heating capacity or 

the unit is limited in its operation by a protection mode 
(e.g. low suction temperature protection) and in all 
cases cannot satisfy the heating demand.

• 

The.outside.temperature.is.below.a.configurable.
threshold.defined.in.the.Heat/Cool.Configuration.menu.

(HCCONFIG).

•  Unit demand limitation is not active.

To set Electric heating stage OAT threshold

1..Navigate.to.the.Configuration.menu.

2. Select 

Heat/Cool Config 

(HCCONFIG).

3. Set 

Elec Stage OAT Threshold

 [ehs_th].

Elec Stage OAT Threshold [ehs_th]

-5 to 21°C

5°C

If. required,. the. user. can. configure. the. last. electric. heater.

stage available as a safety stage. That safety stage is only 
activated in addition to the other stages if there is a unit fault 
that prevents the use of the heating capacity. The other electric 
heater stages continue to operate as described earlier. 

The electric heater stages operate only in the heating mode, 
but not during domestic hot water production.

8.11.4 -  Heating or domestic hot water mode

A three-way valve permits switching the heating capacity to 
a domestic hot water tank.

The unit requests changeover to the domestic hot water mode 
if all of the following conditions have been met:

•  The volt-free tank request contact is closed.
•  Time schedule 3 is occupied (DHW mode requested) OR 

the volt-free priority contact (DHW priority) is closed.

Based on the operating mode the water setpoint is adjusted:

•  In heating mode, setpoints hsp1 and hsp2 are used. 

They.can.be.modified.by.user.reset.or.based.on.OAT.

•  In domestic hot water production mode setpoint hsp3 

is used. No setpoint reset is used.

The unit requests changeover to the heating mode if at least 
one of the following conditions applies:

•  The volt-free tank request contact is open.
• 

The.max..duration.in.the.DHW.mode.has.finished.

•  Time schedule 3 is in an unoccupied period  

(DHW mode not requested).

If a mode change is requested while a compressor is operating, 
it is stopped before the three-way valve changes to the new 
mode, and then the unit is re-started.

If the unit is in domestic hot water production mode, a “DHW” 
message (“DHW running”) is displayed on the user interface 
next to the current operating mode.

8.11.5 -  Summer mode

The Summer mode is used to control DHW mode. When the 
Summer mode is active (space heating is not required) the unit 
can start the water tank to provide hot domestic water.

The Summer mode is activated when

 

the Summer switch is 

closed.OR.outdoor.air.temperature.exceeds.the.predefined.
Summer.OAT.threshold.for.a.specific.time.period.(start.delay)..

The Summer mode is deactivated when the Summer switch is 
open OR outdoor air temperature is below the Summer OAT 

threshold.for.a.specific.time.period.(stop.delay).

To verify Summer switch status

1. Navigate to the Main menu.
2. Select 

Heating Device

 (HDC_STAT).

3. Verify 

Summer Switch

 [SUMM_SW].

Summer Switch [SUMM_SW]

open/closed

open = mode inactive; closed = mode active

To set Summer OAT threshold and start/stop delay

1..Navigate.to.the.Configuration.menu.

2. Select 

HDC Configuration

 (HDC_CONF).

3. Set 

Summer OAT Threshold 

[summ_oat].

Summer OAT Threshold [summ_oat]

15 to 30°C

20°C

4. Set 

Summer OAT start/stop delay

 [summ_on / summ_off].

Summer OAT start delay  [summ_on] / ...stop delay  [summ_off]

0-12 h

5 h

8.11.6 -  Additional water pump

An additional water pump, installed in the heating water 
circuit starts if the summer mode is deactivated. 

If.the.anti-stick.function.is.configured,.the.additional.water.

pump starts periodically.

Summary of Contents for AquaSnap 30WG Series

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Junior Control 30WG 30WGA 61WG...

Page 2: ...ns 10 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 11 5 1 Reading the Welcome screen 11 5 2 Exploring the Synoptic screen 11 5 3 Starting Stopping the unit 11 5 4 Setting the schedule 12 5 5 Display settin...

Page 3: ...t any time without notice 8 10 Additional space heating control 28 8 11 Built in DHW and space heating control HDC 29 8 12 Condensing pressure control optional 30 8 13 Master Slave control 30 9 DIAGNO...

Page 4: ...instructions prior to proceeding with any work Pay attention to all safety warnings The information provided herein is solely for the purpose of allowing customers to operate and service the equipment...

Page 5: ...trical cables and conduits terminal box covers and motor frames with great care 2 CONTROLLER OVERVIEW 2 1 Control system 30WG 30WGA 61WGunitscomewiththeTouchPilotJunior control that serves as a user i...

Page 6: ...f the green LED is not flashing this indicates a LEN bus wiring problem 3 4 Pressure transducers The control implements three types of pressure transducers where two pressure transducers high pressure...

Page 7: ...ustomer safety loops Condenser 3 way valve SIOB cir A 80 80 Used to control the water flow on the condenser side Boiler SIOB cir A 69 70 Used to command a boiler Running SIOB cir A 37 38 Used to signa...

Page 8: ...me screen will be displayed 4 2 Connections Connections are located on the bottom side of the controller The controller comes with two RS485 ports where the first port is used to connect to CCN Carrie...

Page 9: ...er password User password required Legend Genunit Config Schedule HDC Configuration Date Time Pump Configuration Holiday Reset Config Control Identification Heat Cool Config Broadcast User Configurati...

Page 10: ...rt no action taken on the unit Steady icon Alarm s active on the unit see section 9 5 OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the u...

Page 11: ...d 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 5 1 Reading the Welcome screen The Welcome screen is the first screen shown after starting the user interface It displays the application name as well as the...

Page 12: ...is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel button to exit the screen without making modificat...

Page 13: ...r level security ensures that only authorised users are allowed to modify critical unit parameters Only logged in users are allowed to access the Configuration menu It is strongly recommended to chang...

Page 14: ...ion is from a PC using a web browser with Java IMPORTANT UsefirewallsandVPNforsecureconnection 6 2 Opening the web interface To access theTouch Pilot Junior control enter the IP address of the unit in...

Page 15: ...ditional features some tables may contain parameters that cannot be configured for a given unit General Parameters Menu GENUNIT No Point name Status Unit Displayed text Description 1 CTRL_TYP 0 to 2 L...

Page 16: ...emperature circuit A 4 SST_B C Saturated Suction Tp B Saturated suction temperature circuit B 5 SUCT_A C Gas Suction Temp A Compressor suction temperature circuit A 6 SUCT_B C Gas Suction Temp B Compr...

Page 17: ...pen close Remote Setpoint Switch2 Remote Setpoint Switch 2 6 LIM_SW1 open close Limit Switch 1 Status Demand limit switch 1 7 LIM_SW2 open close Limit Switch 2 Status Not applicable please ignore this...

Page 18: ...oint Evaporator water delta temp setpoint 12 CL_WdpSp kPa Cool Water DP Setpoint Evaporator water delta pressure setpoint 13 CL_DvPos 0 to 100 Cool Pump drive position Evaporator pump drive position 1...

Page 19: ...ber of starts compressor A1 7 hr_cp_a2 hour Compressor A2 Hours Operating hours compressor A2 8 st_cp_a2 Compressor A2 Starts Number of starts compressor A2 9 hr_cp_a3 hour Compressor A3 Hours Operati...

Page 20: ...Displayed text Description 1 m_delay no yes Delay Active Start up delay in effect 2 m_2ndspt no yes Second Setpoint Active Second setpoint in use The setpoint used during unoccupied periods 3 m_reset...

Page 21: ...a given unit Genunit Config Menu GENCONF No Point name Status Default Unit Displayed text Description 1 lead_cir 0 to 2 0 Cir Priority Sequence Circuit priority 2 0 Auto 1 A Lead 2 B Lead 0 Automatic...

Page 22: ...the selected language English by default Heat Cool Config Menu HCCONFIG No Point name Status Default Unit Displayed text Description 1 cr_sel 0 to 3 0 Cooling Reset Select Cooling reset selection 2 hr...

Page 23: ...fu 30 1 to 52 2 40 5 C OAT Full Reset Value OAT max reset value 12 dt_hr_no 0 to 14 1 0 C Delta T No Reset Value Delta T no reset value 13 dt_hr_fu 0 to 14 1 0 C Delta T Full Reset Value Delta T max r...

Page 24: ...onth Day of the month 2 month 1 to 12 Month of year Month 3 year 20nn Year Year 4 dow Monday Sunday Day of Week Day of the week Time HH MM 5 hour 0 to 24 hour Hour Hour 6 minute 0 to 59 min Minute Min...

Page 25: ...operate in Cooling mode only The unit operation is based on the following parameters Unit On Off status This parameter indicates whether the unit is shut down not authorised to start or in operation...

Page 26: ...mpdel for cooler OR 4 Set PumpAuto Rotation Delay cdpmpdel for condenser Pump Auto Rotation Delay clpmpdel cdpmpdel 24 to 3000 h 48 h 8 4 3 Pump speed control If the pump with variable flow option has...

Page 27: ...g setpoint reset which can be applied if the condensing setpoint control depends on outdoor air temperature reading reset source OAT Cooling mode 30WG 30WGA 61WG Cooling control point reset is used to...

Page 28: ...et boiler manual command 1 Navigate to the Configuration menu 2 Select Heat Cool Config HCCONFIG 3 Set Boiler Manual Command boil_on Boiler Manual Command boil_on No OAT sensor logic is applied Yes Bo...

Page 29: ...ntinue to operate as described earlier The electric heater stages operate only in the heating mode but not during domestic hot water production 8 11 4 Heating or domestic hot water mode A three way va...

Page 30: ...ch Pilot Junior continuously optimises system operation to obtain the best system efficiency by controlling the number of fans required for any thermal load and outside temperature conditions 8 12 3 C...

Page 31: ...2 Select Current Alarms 3 The list of active alarms will be displayed 9 3 Resetting alarms The alarm can be reset either automatically by the control or manually through the touch panel display or th...

Page 32: ...12002 Circuit B Discharge Pressure Transducer Failure As above Circuit B shuts down As above 12004 Circuit A Suction Pressure Transducer Failure As above Circuit A shuts down Automatic up to 3 alarms...

Page 33: ...stand alone mode Automatic if communication is restored 10031 Unit is in CCN emergency stop Network emergency stop command Unit shuts down Automatic if emergency stop is deactivated 10032 Cooler pump...

Page 34: ...enser water loop failure pump overload Water loop pressure drop too low Unit shuts down Automatic 11107 Condenser water loop failure switch fail Switch fault Unit shuts down Automatic 6 times within 2...

Page 35: ...nd no serious damage can occur to your equipment The Manufacturer provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to he...

Page 36: ...rder No 10161 09 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: