8.3 -  Control interlock contact

This contact checks the status of a loop (customer safety loop, 
see section 8.3). It prevents the unit from starting if it is open 
when the delay at start-up has expired. 

This open contact leads to an alarm shut-down, if the unit is 
running (alarm 10028).

8.4 -  Heat exchanger water pump control

The unit can control one or two water pump(s) per heat 

exchanger..The.pump.is.turned.on.when.the.option.is.configured.
in.the.Pump.Config.menu.(PUMPCONF).and.the.unit.is.in.

heating/cooling mode (depending on the unit) or in delay mode. 

Since the minimum value for delay at start-up is 1 minute 

(configurable.between.1.and.15.minutes),.the.pump.will.run.
for.at.least.one.minute.before.the.first.compressor.starts.

Please note that in case of units with two pumps on one heat 
exchanger, only one pump can be running at a time.

To set pump(s) and its sequence

1..Navigate.to.the.Configuration.menu.

2. Select 

Pump Configuration 

(PUMPCONF).

3. Set 

Cooler Pumps Sequence

 [clpumpseq] OR

4. Set

 Condenser Pumps Sequence 

[cdpmpseq].

Cooler Pumps Sequence [clpumpseq] *

Condenser Pumps Sequence [cdpmpseq] *

   0 = No Pump          

   1 = One Pump Only  

   2 = Two Pumps Auto   

   3 = Pump#1 Manual    

   4 = Pump#2 Manual 
*Values between 2 and 4 can be selected only in case of dual pumps control.

8.4.1 -  Pump operation

The pump keeps running for 2 minutes after the unit goes to 
the stopping mode. 

The pump is turned off if the unit is shut down due to an 
alarm unless the fault is a freeze protection error. The pump 
can be started in particular operating conditions when freeze 
protection of the heat exchanger is active. 

If the pump has failed and another pump is available, the 
unit is stopped and started again with the second pump.
If there is no pump available, the unit shuts down.

8.4.2 -  Automatic pump selection

If two pumps are controlled and the reversing function has 
been selected (PUMPCONF), the control balances the pump 

run.time.to.match.the.configured.pump.changeover.delay.

If this delay has elapsed, the pump reversing function is 
activated during the next time when there is no compressor 
running in the system.

To set pump automatic rotation delay

1..Navigate.to.the.Configuration.menu.

2. Select 

Pump Configuration 

(PUMPCONF).

3. Set 

Pump Auto Rotation Delay

 [clpmpdel] for cooler OR

4. Set 

Pump Auto Rotation Delay 

[cdpmpdel] for condenser.

Pump Auto Rotation Delay [clpmpdel / cdpmpdel]

24 to 3000 h    

48 h

8.4.3 -  Pump speed control

If. the. pump. with. variable. flow. option. has. been. selected.

(factory-installed option), it is possible to control the water 

flow.in.three.ways:

• 

Adjusted fixed flow rate:

 The control ensures a constant 

pump speed based on compressor capacity.

• 

Constant temperature difference:

.Water.flow.control.

based on constant delta T on the water exchanger.

• 

Constant pressure difference:

.Water.flow.control.based.on.

constant water delta pressure (the control continuously 
acts on the pump speed).

Choosing the best possible method of water loop control 
allows for optimising the water delivery in the water loop. 
Pump speed control may also be optimised by the installer 
at service-access level.

8.4.4 -  Pump protection (pump anti-stick function)

The control provides a means to automatically start the pump 
each day at 14:00 for 2 seconds when the unit is off (pump 
anti-sticking).

If.the.unit.is.fitted.with.two.pumps,.the.first.pump.is.started.

on even days and the second pump is started on odd days.

Starting the pump periodically for a few seconds extends 
the lifetime of the pump bearings and the tightness of the 
pump seal. 

To set periodical pump quick start

1..Navigate.to.the.Configuration.menu.

2. Select 

Pump Configuration 

(PUMPCONF).

3. Set 

Cool Pump Anti-Sticking

 [clpmpper] OR 

4. Set Cond Pump Anti-Sticking [cdpmpper].

Cool Pump Anti-Sticking [clpmpper]

Cond Pump Anti-Sticking [cdpmpper]

no/yes

yes

8.5 -  Control point

The control point represents the water temperature that the 
unit must produce. The heat exchanger entering water 
temperature is controlled by default, but the heat exchanger 
leaving water temperature can also be controlled (service 

configuration.is.required).

Control point = Active se Reset

8.5.1 -  Active setpoint

Three setpoints can be selected as active in Cooling mode 
and in Heating mode. 

The 

first  cooling/heating  setpoint

 is normally used during 

occupied periods and the 

second cooling/heating setpoint 

is 

used during unoccupied periods. The 

third cooling setpoint

 

is used for ice storage and the 

third heating setpoint 

is used 

for domestic hot water control.

Setpoint 1

Setpoint 2

Setpoint 3

Cooling  

30WG/30WGA/61WG

Occupied 

period

Unoccupied 

period

Ice storage 

cooling setpoint

Heating  

30WG/61WG

Occupied 

period

Unoccupied 

period

DHW setpoint

Summary of Contents for AquaSnap 30WG Series

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Junior Control 30WG 30WGA 61WG...

Page 2: ...ns 10 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 11 5 1 Reading the Welcome screen 11 5 2 Exploring the Synoptic screen 11 5 3 Starting Stopping the unit 11 5 4 Setting the schedule 12 5 5 Display settin...

Page 3: ...t any time without notice 8 10 Additional space heating control 28 8 11 Built in DHW and space heating control HDC 29 8 12 Condensing pressure control optional 30 8 13 Master Slave control 30 9 DIAGNO...

Page 4: ...instructions prior to proceeding with any work Pay attention to all safety warnings The information provided herein is solely for the purpose of allowing customers to operate and service the equipment...

Page 5: ...trical cables and conduits terminal box covers and motor frames with great care 2 CONTROLLER OVERVIEW 2 1 Control system 30WG 30WGA 61WGunitscomewiththeTouchPilotJunior control that serves as a user i...

Page 6: ...f the green LED is not flashing this indicates a LEN bus wiring problem 3 4 Pressure transducers The control implements three types of pressure transducers where two pressure transducers high pressure...

Page 7: ...ustomer safety loops Condenser 3 way valve SIOB cir A 80 80 Used to control the water flow on the condenser side Boiler SIOB cir A 69 70 Used to command a boiler Running SIOB cir A 37 38 Used to signa...

Page 8: ...me screen will be displayed 4 2 Connections Connections are located on the bottom side of the controller The controller comes with two RS485 ports where the first port is used to connect to CCN Carrie...

Page 9: ...er password User password required Legend Genunit Config Schedule HDC Configuration Date Time Pump Configuration Holiday Reset Config Control Identification Heat Cool Config Broadcast User Configurati...

Page 10: ...rt no action taken on the unit Steady icon Alarm s active on the unit see section 9 5 OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the u...

Page 11: ...d 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 5 1 Reading the Welcome screen The Welcome screen is the first screen shown after starting the user interface It displays the application name as well as the...

Page 12: ...is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel button to exit the screen without making modificat...

Page 13: ...r level security ensures that only authorised users are allowed to modify critical unit parameters Only logged in users are allowed to access the Configuration menu It is strongly recommended to chang...

Page 14: ...ion is from a PC using a web browser with Java IMPORTANT UsefirewallsandVPNforsecureconnection 6 2 Opening the web interface To access theTouch Pilot Junior control enter the IP address of the unit in...

Page 15: ...ditional features some tables may contain parameters that cannot be configured for a given unit General Parameters Menu GENUNIT No Point name Status Unit Displayed text Description 1 CTRL_TYP 0 to 2 L...

Page 16: ...emperature circuit A 4 SST_B C Saturated Suction Tp B Saturated suction temperature circuit B 5 SUCT_A C Gas Suction Temp A Compressor suction temperature circuit A 6 SUCT_B C Gas Suction Temp B Compr...

Page 17: ...pen close Remote Setpoint Switch2 Remote Setpoint Switch 2 6 LIM_SW1 open close Limit Switch 1 Status Demand limit switch 1 7 LIM_SW2 open close Limit Switch 2 Status Not applicable please ignore this...

Page 18: ...oint Evaporator water delta temp setpoint 12 CL_WdpSp kPa Cool Water DP Setpoint Evaporator water delta pressure setpoint 13 CL_DvPos 0 to 100 Cool Pump drive position Evaporator pump drive position 1...

Page 19: ...ber of starts compressor A1 7 hr_cp_a2 hour Compressor A2 Hours Operating hours compressor A2 8 st_cp_a2 Compressor A2 Starts Number of starts compressor A2 9 hr_cp_a3 hour Compressor A3 Hours Operati...

Page 20: ...Displayed text Description 1 m_delay no yes Delay Active Start up delay in effect 2 m_2ndspt no yes Second Setpoint Active Second setpoint in use The setpoint used during unoccupied periods 3 m_reset...

Page 21: ...a given unit Genunit Config Menu GENCONF No Point name Status Default Unit Displayed text Description 1 lead_cir 0 to 2 0 Cir Priority Sequence Circuit priority 2 0 Auto 1 A Lead 2 B Lead 0 Automatic...

Page 22: ...the selected language English by default Heat Cool Config Menu HCCONFIG No Point name Status Default Unit Displayed text Description 1 cr_sel 0 to 3 0 Cooling Reset Select Cooling reset selection 2 hr...

Page 23: ...fu 30 1 to 52 2 40 5 C OAT Full Reset Value OAT max reset value 12 dt_hr_no 0 to 14 1 0 C Delta T No Reset Value Delta T no reset value 13 dt_hr_fu 0 to 14 1 0 C Delta T Full Reset Value Delta T max r...

Page 24: ...onth Day of the month 2 month 1 to 12 Month of year Month 3 year 20nn Year Year 4 dow Monday Sunday Day of Week Day of the week Time HH MM 5 hour 0 to 24 hour Hour Hour 6 minute 0 to 59 min Minute Min...

Page 25: ...operate in Cooling mode only The unit operation is based on the following parameters Unit On Off status This parameter indicates whether the unit is shut down not authorised to start or in operation...

Page 26: ...mpdel for cooler OR 4 Set PumpAuto Rotation Delay cdpmpdel for condenser Pump Auto Rotation Delay clpmpdel cdpmpdel 24 to 3000 h 48 h 8 4 3 Pump speed control If the pump with variable flow option has...

Page 27: ...g setpoint reset which can be applied if the condensing setpoint control depends on outdoor air temperature reading reset source OAT Cooling mode 30WG 30WGA 61WG Cooling control point reset is used to...

Page 28: ...et boiler manual command 1 Navigate to the Configuration menu 2 Select Heat Cool Config HCCONFIG 3 Set Boiler Manual Command boil_on Boiler Manual Command boil_on No OAT sensor logic is applied Yes Bo...

Page 29: ...ntinue to operate as described earlier The electric heater stages operate only in the heating mode but not during domestic hot water production 8 11 4 Heating or domestic hot water mode A three way va...

Page 30: ...ch Pilot Junior continuously optimises system operation to obtain the best system efficiency by controlling the number of fans required for any thermal load and outside temperature conditions 8 12 3 C...

Page 31: ...2 Select Current Alarms 3 The list of active alarms will be displayed 9 3 Resetting alarms The alarm can be reset either automatically by the control or manually through the touch panel display or th...

Page 32: ...12002 Circuit B Discharge Pressure Transducer Failure As above Circuit B shuts down As above 12004 Circuit A Suction Pressure Transducer Failure As above Circuit A shuts down Automatic up to 3 alarms...

Page 33: ...stand alone mode Automatic if communication is restored 10031 Unit is in CCN emergency stop Network emergency stop command Unit shuts down Automatic if emergency stop is deactivated 10032 Cooler pump...

Page 34: ...enser water loop failure pump overload Water loop pressure drop too low Unit shuts down Automatic 11107 Condenser water loop failure switch fail Switch fault Unit shuts down Automatic 6 times within 2...

Page 35: ...nd no serious damage can occur to your equipment The Manufacturer provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to he...

Page 36: ...rder No 10161 09 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: