7 - TOUCH PILOT JUNIOR INTERFACE - DETAILED MENU STRUCTURE
7.1 - Main menu
Icon
Displayed text*
Description
Associated table
General Parameters
General Parameters
GENUNIT
Temperature
Temperature
TEMP
Pressure
Pressure
PRESSURE
Setpoint
Setpoint
SETPOINT
Inputs
Inputs status
INPUTS
Outputs
Outputs status
OUTPUTS
Pump Status
Pump Status
PUMPSTAT
Heating Device
Heating Device
HDC_STAT
Runtime
Runtime
RUNTIME
Free Cooling Status
Free Cooling Status
FCOOL_ST
Modes
Modes
MODES
Configuration
Configuration menu
CONFIG
* Depends on the selected language (English by default).
CAUTION:
Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
General Parameters Menu – GENUNIT
No. Point name
Status
Unit
Displayed text*
Description
1
CTRL_TYP
0 to 2
-
Local=0 Net.=1 Remote=2
Operating mode:
0 = Local
1 = Network
2 = Remote
2
STATUS
-
-
Running Status
Off, Running, Stopping, Delay, Trip out, Ready,
Override, etc.
3
ALM
-
-
Alarm State
Alarm state: Normal, Partial, Shutdown
4
min_left
-
min
Minutes Left for Start
Minutes before the unit start-up
5
HEATCOOL
-
-
Heat/Cool Status
Heating/cooling status: Heat/Cool
6
HC_SEL
0 to 1
-
Heat/Cool Select
Heating/cooling selection:
0 = Cooling
1 = Heating
7
SP_SEL
0 to 3
-
Setpoint Select
Setpoint selection
8
0=Auto 1=Spt1 2=Spt2
3=Spt3
0 = Auto (schedule control)
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
9
SP_OCC
no / yes
-
Setpoint Occupied?
Setpoint occupancy status