Setpoint Menu – SETPOINT
No. Point name
Status
Default
Unit
Displayed text*
Description
1
csp1
-28.9 to 20.0
12.0
°C
Cooling Setpoint 1
Cooling setpoint 1 (used during occupied periods)
2
csp2
-28.9 to 20.0
12.0
°C
Cooling Setpoint 2
Cooling setpoint 2 (used during unoccupied periods)
3
ice_sp
-28.9 to 20.0
12.0
°C
Cooling Ice Setpoint
Cooling ice setpoint
4
hsp1
20.0 to 65.0
50.0
°C
Heating Setpoint 1
Heating setpoint 1 (used during occupied periods)
5
hsp2
20.0 to 65.0
50.0
°C
Heating Setpoint 2
Heating setpoint 2 (used during unoccupied periods)
6
hsp3
20.0 to 65.0
50.0
°C
Heating Setpoint 3
Used as Domestic Hot Water Setpoint when Heating
Device Control is selected (optional)
7
ramp_sp
0.1 to 1.1
0.6
^C
Ramp Loading Setpoint Ramp loading setpoint (rate at which the water
temperature may change within one minute)
8
lim_sp1
0 to 100
100
%
Switch Limit Setpoint 1 Demand limit setpoint 1
9
lim_sp2
0 to 100
100
%
Switch Limit Setpoint 2 Demand limit setpoint 2
10
lim_sp3
0 to 100
100
%
Switch Limit Setpoint 3 Demand limit setpoint 3
11
cond_sp
30.0 to 58.0
40.0
°C
Condensing Setpoint
Condensing setpoint (see also section 8.12.3)
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
No. Point name
Status
Unit
Displayed text*
Description
1
ONOFF_SW
open / close
-
On/Off - Remote Switch
Remote on/off switch
2
HC_SW
open / close
-
Remote heat/Cool Switch
Remote heating/cooling selection switch
3
on_ctrl
off / cool / heat
-
Current Control
Current control: Off, Cool, Heat
4
SETP_SW1
open / close
-
Remote Setpoint Switch1
Remote Setpoint Switch 1
5
SETP_SW2
open / close
-
Remote Setpoint Switch2
Remote Setpoint Switch 2
6
LIM_SW1
open / close
-
Limit Switch 1 Status
Demand limit switch 1
7
LIM_SW2
open / close
-
Limit Switch 2 Status
Not applicable (please ignore this parameter)
8
FLOW_SW
open / close
-
Exchanger Flow Switch
Flow switch status
9
DIFF_FLW
open / close
-
Diff Exchanger Flow Sw
Condenser Flow switch status (currently not available)
10
LOCK_SW
open / close
-
Lock Input
Customer interlock status
11
DSHTR_SW
open / close
-
Desuper heater demand
Desuperheater demand (currently not available)
12
HP_SW_A
open / close
-
High Pressure Switch A
High pressure switch A
13
HP_SW_B
open / close
-
High Pressure Switch B
High pressure switch B
14
SP_RESET
0 to 20
mA
Setpoint Reset Signal
Setpoint reset signal
*Depends on the selected language (English by default).
Outputs Menu – OUTPUTS
No. Point name
Status
Unit
Displayed text*
Description
1
CP_A1
off / on
-
Compressor A1 Output
Compressor A1 command
2
CP_A2
off / on
-
Compressor A2 Output
Compressor A2 command
3
CP_A3
off / on
-
Compressor A3 Output
Compressor A3 command
4
FAN_A
-
Condenser Fan Stages A
Condenser fan stages, circuit A
5
EXVPosA
%
EXV Position Circuit A
EXV position, circuit A
6
HD_POS_A
%
Head Pressure position A
Head pressure, circuit A
7
RV_A
off / on
-
Reverse Valve cir A
Not applicable (please ignore this parameter)
8
LLS_A
off / on
-
Liquid Line Solenoid A
Liquid line solenoid valve status, circuit A
9
CP_B1
off / on
-
Compressor B1 Output
Compressor B1 command
10
CP_B2
off / on
-
Compressor B2 Output
Compressor B2 command
11
FAN_B
-
Condenser Fan Stages B
Condenser fan stages, circuit B
12
EXVPosB
%
EXV Position Circuit B
EXV position, circuit B
13
HD_POS_B
%
Head Pressure position B
Head pressure, circuit B
14
RV_B
off / on
-
Reverse Valve cir B
Not applicable (please ignore this parameter)