101
APPENDIX B — CCN TABLES (cont)
CONFIGURATION DISPLAY TABLES (cont)
NOTES:
1. Compressor capacity will be automatically be determined if unit
size entered in FACTORY1 table matches the values in the unit
compressor configuration table.
2. Total number of fans includes fans controlled by a variable speed
fan. This value will be automatically populated if unit size entered
in FACTORY1 table matches the values in the unit compressor
configuration table.
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
FACTORY2
Compressor A1 Capacity
0 to 99
0
cap_a1
Compressor A2 Capacity
0 to 99
0
cap_a2
Compressor A3 Capacity
0 to 99
0
cap_a3
Compressor A4 Capacity
0 to 99
0
cap_a4
Compressor B1 Capacity
0 to 99
0
cap_b1
Compressor B2 Capacity
0 to 99
0
cap_b2
Compressor B3 Capacity
0 to 99
0
cap_b3
Compressor B4 Capacity
0 to 99
0
cap_b4
Compressor C1 Capacity
0 to 99
0
cap_c1
Compressor C2 Capacity
0 to 99
0
cap_c2
Compressor C3 Capacity
0 to 99
0
cap_c3
Compressor C4 Capacity
0 to 99
0
cap_c4
Circuit A Total Fans NB
0 to 6
0
nb_fan_a
Circuit B Total Fans NB
0 to 6
0
nb_fan_b
Circuit C Total Fans NB
0 to 6
0
nb_fan_c
EXV A Maximum Steps Numb
0/15000
0=EXV not used
exva_max
EXV B Maximum Steps Numb
0/15000
0
exvb_max
EXV C Maximum Steps Numb
0/15000
0
exvc_max
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
HOLIDAY/
HOLDY01S to
HOLDY16S
Holiday Start Month
0-12
0
HOL_MON
Start Day
0-31
0
HOL_DAY
Duration (days)
0-99
0
HOL_LEN
MST_SLV
MASTER SLAVE CONTROL
Master/Slave Select
0=Disable
1=Master
2=Slave
0=Disable
1=Master
2=Slave
0
ms_sel
Master Control Type
1=Local Control
2=Remote Control
3=CCN Control
1=Local Control
2=Remote Control
3=CCN Control
1
ms_ctrl
Slave Address
1 to 236
2
slv_addr
Lag Start Timer
2 to 30
10
min
lstr_tim
Lead/Lag Balance
Yes/No
No
ll_bal
Lead/Lag Balance Delta
40 to 400
168
hours
ll_bal_d
Lag Unit Pump Control
0=Stop if Unit Stops
1=Run if Unit Stops
0=Stop if Unit Stops
1=Run if Unit Stops
0
lag_pump
Lead Pulldown Time
0 to 60
0
min
lead_pul
OCCDEFCS/
OCCPC01S and
OCCPC02S
Timed Override Hours
0-4
0
OVR_EXT
Period 1 DOW (MTWTFSSH)
0/1
11111111
DOW1
Occupied From
00:00-24:00
00:00
OCCTOD1
Occupied To
00:00-24:00
24:00
UNOCTOD1
Period 2 DOW (MTWTFSSH)
0/1
11111111
DOW2
Occupied From
00:00-24:00
00:00
OCCTOD2
Occupied To
00:00-24:00
00:00
UNOCTOD2
Period 3 DOW (MTWTFSSH)
0/1
00000000
DOW3
Occupied From
00:00-24:00
00:00
OCCTOD3
Occupied To
00:00-24:00
00:00
UNOCTOD3
Period 4 DOW (MTWTFSSH)
0/1
00000000
DOW4
Occupied From
00:00-24:00
00:00
OCCTOD4
Occupied To
00:00-24:00
00:00
UNOCTOD4
Period 5 DOW (MTWTFSSH)
0/1
00000000
DOW5
Occupied From
00:00-24:00
00:00
OCCTOD5
Occupied To
00:00-24:00
00:00
UNOCTOD5
Period 6 DOW (MTWTFSSH)
0/1
00000000
DOW6
Occupied From
00:00-24:00
00:00
OCCTOD6
Occupied To
00:00-24:00
00:00
UNOCTOD6
Period 7 DOW (MTWTFSSH)
0/1
00000000
DOW7
Occupied From
00:00-24:00
00:00
OCCTOD7
Occupied To
00:00-24:00
00:00
UNOCTOD7
Period 8 DOW (MTWTFSSH)
0/1
00000000
DOW8
Occupied From
00:00-24:00
00:00
OCCTOD8
Occupied To
00:00-24:00
00:00
UNOCTOD8
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...