75
T.REQ
value to
ON
and press
. Manual Control
mode is now active. Press the arrow keys to move to the appro-
priate item. To activate an item locate the item, press
and the display will show
OFF
. Press
and
OFF
will
flash. Use either arrow key to change the value to
ON
and
press
. The item should be active. To turn the item
off, locate the item, press
and the display will show
ON
. The chiller must be enabled by turning the Enable/Off/
Remote Contact switch to Enable. Press
and
ON
will
flash. Use either arrow key to change the value to
OFF
and
press
. The item should be inactive.
To enter the Quick Test mode, the Enable/Off/Remote
Contact switch must be in the OFF position. Move the LED to
the Service Test mode. Press
to access
TEST
.
Use
the
key until the display reads
QUIC
. Press
to
access
Q.REQ
. Press
and the display will show
OFF
.
Press
and
OFF
will flash. Enter the password if
required. Use either arrow key to change the
QUIC
value to
ON
and press
. Quick Test mode is now active. Fol-
low the same instructions for the Manual Control mode to acti-
vate a component.
Example — Test the chilled water pump (see Table 47).
Power must be applied to the unit. Enable/Off/Remote
Contact switch must be in the OFF position.
Table 47 — Testing the Chilled Water Pump
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MODE
(Red LED)
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
EXPANSION
VALUE
DESCRIPTION
(Units)
COMMENT
SERVICE TEST
Service Test Mode
TEST
Manual Sequence
QUIC
Q.REQ
PASS WORD
Password may be required
0111
Each
will lock in the next
digit. If 0111 is not the password,
use the arrow keys to change the
password digit and press
when correct.
Q.REQ
Returns to the original field
OFF
OFF
OFF will flash
ON
The Enable/Off/Remote Contact
switch must be in the OFF
position.
Q.REQ
EXV.A
EXV.B
PMP.1
Water Exchanger
Pump 1
OFF
OFF
OFF will flash
ON
ON
Pump 1 will turn on.
ON
ON will flash
OFF
OFF
Pump 1 will turn off.
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...