CL-7
MODE — SERVICE TEST (cont)
*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring
T.REQ
to ON. Configure the desired item to ON, then
place the Enable/Off/Remote Contact switch to the Enable position.
†Place the Enable/Off/Remote Contact switch to the Off position prior to configuring
Q.REQ
to ON. The switch should be in the Off position
to perform Quick Test.
SUB-MODE
ITEM
DISPLAY
ITEM EXPANSION
ENTRY
QUIC†(cont)
CH.A1
OFF/ON
Compressor A1 Heater
CH.A2
OFF/ON
Compressor A2 Heater
CH.A3
OFF/ON
Compressor A3 Heater
CH.A4
OFF/ON
Compressor A4 Heater
CH.B1
OFF/ON
Compressor B1 Heater
CH.B2
OFF/ON
Compressor B2 Heater
CH.B3
OFF/ON
Compressor B3 Heater
CH.B4
OFF/ON
Compressor B4 Heater
CH.C1
OFF/ON
Compressor C1 Heater
CH.C2
OFF/ON
Compressor C2 Heater
CH.C3
OFF/ON
Compressor C3 Heater
CH.C4
OFF/ON
Compressor C4 Heater
HGB.A
OFF/ON
Hot Gas Bypass A Output
HGB.B
OFF/ON
Hot Gas Bypass B Output
HGB.C
OFF/ON
Hot Gas Bypass C Output
Q.RDY
OFF/ON
Chiller Ready Status
Q.RUN
OFF/ON
Chiller Running Status
SHUT
OFF/ON
Customer Shut Down Stat
CATO
xx.x
Chiller Capacity 0-10v
ALRM
OFF/ON
Alarm Relay
ALRT
OFF/ON
Alert Relay
C.ALM
OFF/ON
Critical Alarm Relay
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...