Table 27 — Water Temperature Difference Reset Configuration
NOTE:
Bold
values indicate sub-mode level.
MODE
KEYPAD ENTRY
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
DISP
UNIT
SERV
OPTN
RSET
Reset Cool and Heat Tmp
CRST
Cooling Reset Type
0
No Reset
0
No Reset
Flashing to indicate Edit mode. May require Password
/
2
Delta T Temp
Use up or down arrows to change value to 2.
2
Accepts the change.
CRST
At mode level
SETPOINTS
/
Change to Setpoints Mode
COOL
Cooling Setpoints
CSP.1
Cooling Setpoint 1
x 4
CRV.2
CRT1
Delta T No Reset Temp
Cooler Temperature difference where no temperature
reset is required.
0
Value of CRT1
0
Flashing to indicate Edit mode
10.0
Value of No Temperature Reset, 10 from the example.
10.0
Accepts the change.
CRT1
CRT2
Delta T Full Reset Temp
Cooler Temperature difference where full temperature
reset, DGRC is required.
0
Value of CRT2.
0
Flashing to indicate Edit mode
2.0
Value of full Temperature Reset, 2 from the example.
2.0
Accepts the change.
CRT2
x 4
CRS2
DGRC
Degrees Cool Reset
Amount of temperature reset required.
0
Value of DGRC
0
Flashing to indicate Edit mode
5.0
Amount of Temperature Reset required, 5 from the example.
5.0
Accepts the change.
DGRC
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...