100
APPENDIX B — CCN TABLES (cont)
CONFIGURATION DISPLAY TABLES (cont)
* Enter unit size. This item allows the controls to determine capacity
of each compressor and the total number of fans on each circuit
based on a compressor arrangement array (can be viewed in table
FACTORY2). It is not necessary to enter compressor capacity and
number of fans on each circuit. See the Unit Compressor Configu-
ration table below as a reference.
† Number of fans controlled directly by a variable speed fan actua-
tor using 0 to 10 vdc signal. This will enable the controls to
determine the remaining discrete fan staging outputs from the
total fans on each circuit. Configure to 1 for low ambient head
pressure control.
UNIT COMPRESSOR CAPACITY (%) CONFIGURATION
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
!CtrlD /
PD5_RBRQ:
Device Name
8 chars
Description
24 chars
PRO-DIALOG 5
30RB&30RQ
Location
24 chars
Software Part Number
16 chars
CSA-SR-20C460301
Model Number
20 chars
Serial Number
12 chars
Reference Number
24 chars
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
DISPCONF
Metric Display on STDU
Yes/No
No
DISPUNIT
Language Selection
0=English
1=Espanol
2=Francais
3=Portugues
4=English2
0=English
1=Espanol
2=Francais
3=Portugues
4=English2
0
LANGUAGE
FACTORY
Unit Type
1 (Cooling Only),
2 (not supported)
1
unit_typ
Unit Capacity*
56 to 500
Unit Dependent
tons
unitsize
NB Fans on Varifan Cir A†
0 to 6
0
varfan_a
NB Fans on Varifan Cir B†
0 to 6
0
varfan_b
NB Fans on Varifan Cir C†
0 to 6
0
varfan_c
Air Cooled Reclaim Sel
Yes/No
No
recl_opt
Free Cooling Select
Yes/No
No
free_opt
Electrical Heat Stages
0 to 4
0
ehs_sel
Boiler Command Select
Yes/No
No
boil_sel
Power Frequence 60HZ Sel
Yes/No
Yes
freq_60H
Energy Management Module
Yes/No
No
emm_nrcp
Hot Gas Bypass Select
0-Hot gas bypass valve (not
used)
1=Used for Startup only
2=Close Control
3=High Ambient (if High
pressure mode is active,
close control shall be active)
0
hgbp_sel
Pro_dialog Display Selec
No=Use
Comfort
Link™
display as user interface
(factory installed)
Yes=Use Pro_dialog
synopsis as user interface
(not supported)
No
pd4_disp
Factory Password
0 to 150
111
fac_pass
High Static Fan Control
Yes/No
No
hsta_fan
MCHX Exchanger Select
Yes/No
Unit Dependent
mchx_sel
VLT Fan Drive Select
Not Supported
0
vlt_sel
VLT Fan Drive RPM
Not Supported
0
vlt_rpm
Desuperheater Select
Not Supported
No
desuper
Dual Speed Fan Select
Not Supported
No
dual_fan
30RB UNIT
SIZE
POINT NAME (FACTORY2 TABLE)
cap_a1
cap_a2
cap_a3
cap_a4
cap_b1
cap_b2
cap_b3
cap_b4
cap_c1
cap_c2
cap_c3
cap_c4
060
20
20
0
0
20
0
0
0
0
0
0
0
070
25
25
0
0
20
0
0
0
0
0
0
0
080
20
20
0
0
20
20
0
0
0
0
0
0
090
25
25
0
0
20
20
0
0
0
0
0
0
100
25
25
0
0
25
25
0
0
0
0
0
0
110
25
25
0
0
20
20
20
0
0
0
0
0
120
25
25
0
0
25
25
25
0
0
0
0
0
130
25
25
25
0
20
20
20
0
0
0
0
0
150
25
25
25
0
25
25
25
0
0
0
0
0
160
25
25
25
25
20
20
20
0
0
0
0
0
170
25
25
25
25
25
25
25
0
0
0
0
0
190
25
25
25
25
25
25
25
25
0
0
0
0
210
25
25
25
0
20
20
20
0
25
25
25
0
225
25
25
25
0
25
25
25
0
25
25
25
0
250
25
25
25
0
25
25
25
0
25
25
25
25
275
25
25
25
25
25
25
25
25
25
25
25
0
300
25
25
25
25
25
25
25
25
25
25
25
25
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...