APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — OUTPUTS
ITEM
EXPANSION
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
CIR.A
OUTPUTS CIRCUIT A
CP.A1
Compressor A1 Relay
OFF/ON
CIRCA_D
CP_A1
8
CP.A2
Compressor A2 Relay
OFF/ON
CIRCA_D
CP_A2
8
CP.A3
Compressor A3 Relay
OFF/ON
CIRCA_D
CP_A3
8
CP.A4
Compressor A4 Relay
OFF/ON
CIRCA_D
CP_A4
8
HGB.A
Hot Gas Bypass Circ A
OFF/ON
CIRCA_D
HGBP_A
6
HT.A1
Comp A1 Heater Relay
OFF/ON
CIRCA_D
cp_a1_ht
8
HT.A2
Comp A2 Heater Relay
OFF/ON
CIRCA_D
cp_a2_ht
8
HT.A3
Comp A3 Heater Relay
OFF/ON
CIRCA_D
cp_a3_ht
8
HT.A4
Comp A4 Heater Relay
OFF/ON
CIRCA_D
cp_a4_ht
8
FAN.A
Circuit A Fan Stages
X
0-6
CIRCA_D
FAN_ST_A
SPD.A
Circ A Varifan Position
XXX (%)
0-100
CIRCA_AN
hd_pos_a
11
EXV.A
Circuit A EXV % Open
XXX (%)
0-100
CIRCA_AN
EXV_A
8
FRP.A
Refrigerant Pump Out A
OFF/ON
Not supported.
CIRCA_D
FR_PMP_A
FRVA
Free Cooling Valve A
OPEN/CLSE
Not supported.
CIRCA_D
FR_VLV_A
HR1.A
Air Cond Enter Valve A
OPEN/CLSE
RECLAIM
hr_ca_a
16
HR2.A
Air Cond Leaving Valv A
OPEN/CLSE
RECLAIM
hr_la_a
16
HR3.A
Water Cond Enter Valv A
OPEN/CLSE
RECLAIM
hr_en_a
16
HR4.A
Water Cond Leav Valve A
OPEN/CLSE
RECLAIM
hr_lw_a
16
RV.A
4 Way Valve Circuit A
OPEN/CLSE
Not supported.
CIRCA_D
RV_A
CIR.B
OUTPUTS CIRCUIT B
CP.B1
Compressor B1 Relay
OFF/ON
CIRCB_D
CP_B1
8
CP.B2
Compressor B2 Relay
OFF/ON
CIRCB_D
CP_B2
8
CP.B3
Compressor B3 Relay
OFF/ON
CIRCB_D
CP_B3
8
CP.B4
Compressor B4 Relay
OFF/ON
CIRCB_D
CP_B4
8
HGB.B
Hot Gas Bypass Circ B
OFF/ON
CIRCB_D
HGBP_B
6
HT.B1
Comp B1 Heater Relay
OFF/ON
CIRCB_D
CP_HT_B1
8
HT.B2
Comp B2 Heater Relay
OFF/ON
CIRCB_D
CP_HT_B2
8
HT.B3
Comp B3 Heater Relay
OFF/ON
CIRCB_D
CP_HT_B3
8
HT.B4
Comp B4 Heater Relay
OFF/ON
CIRCB_D
CP_HT_B4
8
FAN.B
Circuit B Fan Stages
X
0-6
CIRCB_D
FAN_ST_B
SPD.B
Circ B Varifan Position
XXX (%)
0-100
CIRCB_AN
hd_pos_b
11,12
EXV.B
Circuit B EXV % Open
XXX (%)
0-100
CIRCB_AN
EXV_B
8
FRP.B
Refrigerant Pump Out B
OFF/ON
Not supported.
CIRCB_D
FR_PMP_B
FRVB
Free Cooling Valve B
OPEN/CLSE
Not supported.
CIRCA_D
FR_VLV_B
HR1.B
Air Cond Enter Valve B
OPEN/CLSE
RECLAIM
hr_ca_b
16
HR2.B
Air Cond Leaving Valv B
OPEN/CLSE
RECLAIM
hr_la_b
16
HR3.B
Water Cond Enter Valv B
OPEN/CLSE
RECLAIM
hr_en_b
16
HR4.B
Water Cond Leav Valve B
OPEN/CLSE
RECLAIM
hr_lw_b
16
RV.B
4 Way Valve Circuit B
OPEN/CLSE
Not supported.
CIRCB_D
RV_B
CIR.C
OUTPUTS CIRCUIT C
CP.C1
Compressor C1 Relay
OFF/ON
CIRCC_D
CP_C1
8
CP.C2
Compressor C2 Relay
OFF/ON
CIRCC_D
CP_C2
8
CP.C3
Compressor C3 Relay
OFF/ON
CIRCC_D
CP_C3
8
CP.C4
Compressor C4 Relay
OFF/ON
CIRCC_D
CP_C4
8
HGB.C
Hot Gas Bypass Circ C
OFF/ON
CIRCC_D
HGBP_C
14
HT.C1
Comp C1 Heater Relay
OFF/ON
CIRCC_D
cp_c1_ht
8
HT.C2
Comp C2 Heater Relay
OFF/ON
CIRCC_D
cp_c2_ht
8
HT.C3
Comp C3 Heater Relay
OFF/ON
CIRCC_D
cp_c3_ht
8
HT.C4
Comp C4 Heater Relay
OFF/ON
CIRCC_D
cp_c4_ht
8
FAN.C
Circuit C Fan Stages
X
0-6
CIRCC_D
FAN_ST_C
SPD.C
Circ C Varifan Position
XXX (%)
0-100
CIRCC_AN
hd_pos_c
14
EXV.C
Circuit C EXV % Open
XXX (%)
0-100
CIRCC_AN
EXV_C
10
FRP.C
Refrigerant Pump Out C
OFF/ON
Not supported.
CIRCC_D
FR_PMP_ C
FRVC
Free Cooling Valve C
OPEN/CLSE
Not supported.
CIRCC_D
FR_VLV_C
GEN.O
GENERAL OUTPUTS
PMP.1
Water Exchanger Pump 1
OFF/ON
STATEGEN
CPUMP_1
6
PMP.2
Water Exchanger Pump 2
OFF/ON
STATEGEN
CPUMP_2
6
CND.P
Reclaim Condenser Pump
OFF/ON
STATEGEN
COND_PUMP
16
CO.HT
Cooler Heater Output
OFF/ON
STATEGEN
COOLHEAT
6
CN.HT
Condenser Heater Output
OFF/ON
RECLAIM
cond_htr
16
REDY
Chiller Ready Status
OFF/ON
forcible
RECLAIM
READY
6
RUN
Chiller Running Status
OFF/ON
forcible
STATEGEN
RUNNING
15
SHUT
Customer Shutdown Stat
OFF/ON
forcible
STATEGEN
SHUTDOWN
15
CATO
Chiller Capacity 0-10 v
XX.X
forcible
STATEGEN
CAPT_010
15
ALRM
Alarm Relay
OFF/ON
STATEGEN
ALARM
6
ALRT
Alert Relay
OFF/ON
STATEGEN
ALERT
6
BOIL
Boiler Command
OFF/ON
Not supported.
STATEGEN
BOILER
C.ALM
Critical Alarm Relay
OFF/ON
forcible
STATEGEN
critical_qck
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...