APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — SERVICE TEST
*Place the Enable/Off/Remote Contact switch to the Off position prior to configuring
T.REQ
to ON. Configure the desired item to ON, then
place the Enable/Off/Remote Contact switch to the Enable position.
†Place the Enable/Off/Remote Contact switch to the Off position prior to configuring
Q.REQ
to ON. The switch should be in the Off position
to perform Quick Test.
ITEM
EXPANSION
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
TEST
COMPRESSORS
N/A
T.REQ
Manual Sequence
OFF/ON*
forcible
N/A
service_test
51,74
CP.A1
Compressor A1 Output
OFF/ON
forcible
N/A
comp_serv_a_1
51
CP.A2
Compressor A2 Output
OFF/ON
forcible
N/A
comp_serv_a_2
51
CP.A3
Compressor A3 Output
OFF/ON
forcible
N/A
comp_serv_a_3
51
CP.A4
Compressor A4 Output
OFF/ON
forcible
N/A
comp_serv_a_4
51
HGB.A
Hot Gas Bypass A Output
OFF/ON
forcible
N/A
hgbp_serv_a
CP.B1
Compressor B1 Output
OFF/ON
forcible
N/A
comp_serv_b_1
51
CP.B2
Compressor B2 Output
OFF/ON
forcible
N/A
comp_serv_b_2
51
CP.B3
Compressor B3 Output
OFF/ON
forcible
N/A
comp_serv_b_3
51
CP.B4
Compressor B4 Output
OFF/ON
forcible
N/A
comp_serv_b_4
51
HGB.B
Hot Gas Bypass B Output
OFF/ON
forcible
N/A
hgbp_serv_b
CP.C1
Compressor C1 Output
OFF/ON
forcible
N/A
comp_serv_c_1
51
CP.C2
Compressor C2 Output
OFF/ON
forcible
N/A
comp_serv_c_2
51
CP.C3
Compressor C3 Output
OFF/ON
forcible
N/A
comp_serv_c_3
51
CP.C4
Compressor C4 Output
OFF/ON
forcible
N/A
comp_serv_c_4
51
HGB.C
Hot Gas Bypass C Output
OFF/ON
forcible
N/A
hgbp_serv_c
QUIC
QUICK TEST MODE
N/A
51
Q.REQ
Quick Test Mode
OFF/ON†
forcible
N/A
test_request
75
EXV.A
Circuit A EXV % Open
XXX (%)
0-100
forcible
N/A
exv_qck_a
50,51
EXV.B
Circuit B EXV % Open
XXX (%)
0-100
forcible
N/A
exv_qck_b
50,51
EXV.C
Circuit C EXV % Open
XXX (%)
0-100
forcible
N/A
exv_qck_c
50,51
FAN.A
Circuit A Fan Stages
X
0-6
forcible
N/A
fan_qck_a
FAN.B
Circuit B Fan Stages
X
0-6
forcible
N/A
fan_qck_b
FAN.C
Circuit C Fan Stages
X
0-6
forcible
N/A
fan_qck_c
SPD.A
Circ A Varifan position
XXX (%)
0-100
forcible
N/A
hd_qck_a
SPD.B
Circ B Varifan position
XXX (%)
0-100
forcible
N/A
hd_qck_b
SPD.C
Circ C Varifan position
XXX (%)
0-100
forcible
N/A
hd_qck_c
FRV.A
Free Cooling Valve A
OPEN/CLSE
Not supported.
forcible
N/A
fr_qck_1a
FRP.A
Refrigerant Pump Out A
OFF/ON
Not supported.
forcible
N/A
fr_qck_2a
FRV.B
Free Cooling Valve B
OPEN/CLSE
Not supported.
forcible
N/A
fr_qck_1b
FRP.B
Refrigerant Pump Out B
OFF/ON
Not supported.
forcible
N/A
fr_qck_2b
FRV.C
Free Cooling Valve C
OPEN/CLSE
Not supported.
forcible
N/A
fr_qck_1c
FRP.C
Refrigerant Pump Out C
OFF/ON
Not supported.
forcible
N/A
fr_qck_2c
RV.A
4 Way Valve Circuit A
OPEN/CLSE
Not supported.
forcible
N/A
rv_qck_a
RV.B
4 Way Valve Circuit B
OPEN/CLSE
Not supported.
forcible
N/A
rv_qck_b
BOIL
Boiler Command
OFF/ON
Not supported.
forcible
N/A
boiler_qck
HR1.A
Air Cond Enter Valve A
OPEN/CLSE
forcible
N/A
hr_ea_qck_a
HR2.A
Air Cond Leaving Valv A
OPEN/CLSE
forcible
N/A
hr_la_qck_a
HR3.A
Water Cond Enter Valv A
OPEN/CLSE
forcible
N/A
hr_ew_qck_a
HR4.A
Water Cond Leav Valve A
OPEN/CLSE
forcible
N/A
hr_lw_qck_a
HR1.B
Air Cond Enter Valve B
OPEN/CLSE
forcible
N/A
hr_ea_qck_b
HR2.B
Air Cond Leaving Valv B
OPEN/CLSE
forcible
N/A
hr_la_qck_b
HR3.B
Water Cond Enter Valv B
OPEN/CLSE
forcible
N/A
hr_ew_qck_b
HR4.B
Water Cond Leav Valve B
OPEN/CLSE
forcible
N/A
hr_lw_qck_b
PMP.1
Water Exchanger Pump 1
OFF/ON
forcible
N/A
cpump_qck1
PMP.2
Water Exchanger Pump 2
OFF/ON
forcible
N/A
cpump_qck2
CND.P
Reclaim Condenser Pump
OFF/ON
forcible
N/A
cond_pump_qck
CL.HT
Cooler Heater Output
OFF/ON
forcible
N/A
coo_heat_qck
CP.HT
Condenser Heater Output
OFF/ON
forcible
N/A
cond_htr_qck
CH.A1
Compressor A1 Heater
OFF/ON
forcible
N/A
cp_ht_qck_a1
CH.A2
Compressor A2 Heater
OFF/ON
forcible
N/A
cp_ht_qck_a2
CH.A3
Compressor A3 Heater
OFF/ON
forcible
N/A
cp_ht_qck_a3
CH.A4
Compressor A4 Heater
OFF/ON
forcible
N/A
cp_ht_qck_a4
CH.B1
Compressor B1 Heater
OFF/ON
forcible
N/A
cp_ht_qck_b1
CH.B2
Compressor B2 Heater
OFF/ON
forcible
N/A
cp_ht_qck_b2
CH.B3
Compressor B3 Heater
OFF/ON
forcible
N/A
cp_ht_qck_b3
CH.B4
Compressor B4 Heater
OFF/ON
forcible
N/A
cp_ht_qck_b4
CH.C1
Compressor C1 Heater
OFF/ON
forcible
N/A
cp_ht_qck_c1
CH.C2
Compressor C2 Heater
OFF/ON
forcible
N/A
cp_ht_qck_c2
CH.C3
Compressor C3 Heater
OFF/ON
forcible
N/A
cp_ht_qck_c3
CH.C4
Compressor C4 Heater
OFF/ON
forcible
N/A
cp_ht_qck_c4
HGB.A
Hot Gas Bypass A Output
N/A
HGB.B
Hot Gas Bypass B Output
N/A
HGB.C
Hot Gas Bypass C Output
N/A
Q.RDY
Chiller Ready Status
OFF/ON
forcible
N/A
ready_qck
Q.RUN
Chiller Running Status
OFF/ON
EMM
forcible
N/A
running_qck
SHUT
Customer Shutdown Stat
OFF/ON
EMM
forcible
N/A
shutdown_qck
CATO
Chiller Capacity 0-10v
XX.X (vdc)
forcible
N/A
CAPT_010_qcK
ALRM
Alarm Relay
OFF/ON
forcible
N/A
alarm_qck
ALRT
Alert Relay
OFF/ON
forcible
N/A
alert_qck
C.ALM
Critical Alarm Relay
OFF/ON
Not supported.
forcible
N/A
critical_qck
Summary of Contents for AQUASNAP 30RBA315
Page 77: ...77 Fig 37 Control Schematic 30RB060 080 a30 4619...
Page 78: ...78 Fig 38 Control Schematic 30RB090 150 a30 4620...
Page 79: ...79 Fig 39 Control Schematic 30RB160 190 a30 4622...
Page 80: ...80 Fig 40 Control Schematic 30RB210 300 a30 4622...
Page 81: ...81 Fig 41 Heat Reclaim Control Schematic a30 4622...