19

6.4 - Alarm codes

Alarm 

No.

Alarm 

code

Alarm description

Reset type

Probable cause

Action taken by the control

Thermistor faults

1

th-01 Sensor fault, fluid entering water heat 

exchanger

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

2

th-02  Sensor fault, fluid leaving water heat 

exchanger

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

3

th-03 Defrost sensor fault, circuit A

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

4

th-04 Defrost sensor fault, second coil

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

5

th-10 Outside temperature sensor fault

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

6

th-11 CHWS fluid sensor fault (master/slave) Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

The master/slave mode is 

stopped

7

th-12 Suction sensor fault

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

8

th-24 Economiser sensor fault

Automatic when the temperature 

measured by the sensor returns to normal

Defective thermistor

Unit is shut down

Pressure transducer faults

9

Pr-01  Discharge pressure transducer fault

Automatic when the voltage transmitted 

by the sensor returns to normal

Defective transducer or connection 

fault

Unit is shut down

10

Pr-04    Suction pressure transducer fault

Automatic when the voltage transmitted 

by the sensor returns to normal

Defective transducer or connection 

fault

Unit is shut down

11

Pr-13  Economiser pressure transducer fault Automatic when the voltage transmitted 

by the sensor returns to normal

Defective transducer or connection 

fault

Unit is shut down

12

Pr-24 Water pump pressure transducer fault Automatic when the voltage transmitted 

by the sensor returns to normal

Defective transducer or connection 

fault

Unit is shut down

Communication fault

13

Co-E1 Communication loss with  the EXV 

board

Automatic when communication is 

re-established

Installation bus fault or defective 

slave board

Unit is shut down

14

Co-O1 Communication loss with PD-AUX 

board No.1

Automatic when communication is 

re-established

Installation bus fault or defective 

slave board

Unit with optional water pressure 

sensors, unit is shut down.

15

Co-O2 Communication loss with PD-AUX 

board No. 2

Automatic when communication is 

re-established

Installation bus fault or defective 

slave board

None

16

A1-01 CP A1 fault: Kriwan electrical 

protection open

Manual

Compressor overheating

Compressor is shut down

17

A2-01 CP A2 fault: Kriwan electrical 

protection open

Manual

Compressor overheating

Compressor is shut down

Process faults

18

P-01  Water heat exchanger frost protection. Automatic if the same alarm has not tripped 

during the last 24 hours, otherwise manual.

Water flow rate too low or defective 

thermistor

Unit is shut down

19

P-05  Low suction temperature.

Automatic when the temperature returns to 

normal, and if this alarm has not appeared 

during the last 24 hours, otherwise manual.

Pressure sensor defective, EXV 

blocked or low refrigerant charge

Unit is shut down

20

P-08

High superheat

Automatic when the temperature returns to 

normal, and if this alarm has not appeared 

during the last 24 hours, otherwise manual.

Pressure sensor defective, EXV 

blocked or low refrigerant charge

Unit is shut down

21

P-11  Low superheat

Automatic when the temperature returns to 

normal, and if this alarm has not appeared 

during the last 24 hours, otherwise manual.

Pressure sensor defective, EXV 

blocked or low refrigerant charge

Unit is shut down

22

P-14  Water flow control and customer 

interlock fault

Automatic if the unit is in manual 

shut-down status, otherwise manual.

Heat exchanger pump defect or 

water flow switch fault

Unit is shut down, if the alarm 

occurs in defrost mode, if not 

the unit remains on.

23

P-16

Compressor A1 not started or no 

pressure increase registered

Manual

Connection problem

Compressor is shut down

24

P-17

Compressor A2 not started or no 

pressure increase registered

Manual

Connection problem

Compressor is shut down

25

P-29

Communication loss with the System 

Manager

Automatic when communication is 

re-established

CCN installation bus defective

Unit goes into autonomous 

mode

26

P-30

Communicaiton loss between master 

and slave

Automatic when communication is 

re-established

CCN installation bus defective

Unit goes into autonomous 

mode

27

P-31

CCN emergency stop

Manual

Network command

Unit is shut down

28

P-32  Fault water pump 1

Manual

Pump overheating or poor pump 

connection

Unit is completely stopped if 

there is no emergency pump

29

P-37

Repeated high pressure unloading

Automatic

Transducer defective or fan circuit fault None

30

P-40

Repeated low suction temperature 

unloading

Manual

Pressure sensor defective or 

refrigerant charge too low

Unit is shut down

31

P-43

Heat exchanger temperature too low, 

less than 8°C, prevents unit start-up

Automatic when the temperature detected 

returns to normal

Operating compressor protection 

out of range or pressure sensor fault

The unit cannot start

32

P-50

Refrigerant leak

Automatic when the concentration returns 

to a lower value than the normal threshold

Refrigerant leak or volatile 

components present in the machine 

atmosphere

None

33

P-63

High pressure fault

Manual

Fan fault

Unit is shut down

34

P-97

Reversed entering/leaving water sensors Manual

Sensor defective, sensors reversed Unit is shut down

35

MC-nn Master chiller configuration error 

Automatic when the master configuration 

returns to normal or when the unit is no 

longer in master/slave mode

Master/slave configuration error

Master/slave mode is stopped

36

FC-nO No factory configuration

Automatic if the configuration is entered

Unit size has not been configured

Unit is shut down

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Reviews: