4.9.17 - GENCONF menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

ramp_sel

Yes/No

No

-

Ramp loading sequence

off_on_d

1 to 15

1

min

Start-up delay 

nh_start

00:00 to 24:00

00:00

-

Night mode start hour

nh_end

00:00 to 24:00

00:00

-

Night mode stop hour

bas_menu

0 to 3

0

-

Basic menu configuration

0 = total access

1 = access to the alarm menu by password

2 = access to the setpoint menu by password 

3 = combination of 1 and 2

synoptic

Yes/No

No

-

Synoptic diagram display

4.9.18 - PUMPCONF menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

pump_seq

Yes/No

No

-

Heat exchanger pump availability

pump_per

Yes/No

No

-

Pump seizure protection

pump_sby

Yes/No

No

-

Pump shutdown when the unit is in standby

pump_loc

Yes/No

Yes

-

Flow rate verification when the pump has shut down

4.9.19 - HCCONFIG menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

hr_sel

0 to 3

0

-

Heating reset selection

1 = outside temp., 0 = none, 2 = delta T

heat_th

-20 to 0

-15

°C

Outside temperature threshold heating mode

boil_th

-30 to 15

-25

°C

Outside temperature threshold for the boiler

ehs_th

-5 to 21

5

°C

Outside temperature threshold for electric heater stages

ehs_back

Yes/No

No

-

One backup electric heater stage

ehs_pull

0 to 60

0

minutes

Delay before start-up of the first electric heater stage

ehs_defr

Yes/No

No

-

Quick electric heat stages for defrost

4.9.20 - RESETCFG menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

oathr_non

-10 to 51.7

-10

°C

Outside temperature for no reset

oathr_fu

-10 to 51.7

-10

°C

Outside temperature for maximum reset

dt_hr_non

-17.8 to -3.9

-17.8

^C

Delta T for no reset

dt_hr_fu

-17.8 to -3.9

-17.8

^C

Delta T for maximum reset

v_hr_non

-17.8 to -6.7

-17.8

^C

Current value for no reset

v_hr_fu

-17.8 to -6.7

-17.8

^C

Current value for maximum reset

hr_deg

-34.4 to 1.1

-17.8

^C

Heating mode reset value

4.9.21 - USERCONF menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

language

 0 to 5

0

-

Language selection  

English = 0, Spanish = 1, French =  2, German = 3, Italian = 4, 

Translation = 5

use_pass

1 to 9999

11

-

User password

4.9.22 - DATETIME menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

hour

0 to 24

hours

Hour

minutes

0 to 59

minutes

Minutes

dow

1 to 7

-

Day of the week

tom_hol

No/Yes

No

Holiday tomorrow?

tod_hol

No/Yes

No

-

Holiday today?

dlig_off

No/Yes

-

Winter time change-over active?

dlig_on

No/Yes

-

Summer time change-over active?

d_of_m

1 to 31

-

Day of the month

month

1 to 12

-

Month

year

0 to 99

-

Year

4.9.23 - CTRL_ID menu

NAME

FORMAT

DEFAULT

UNIT    

DESCRIPTION

elemt_nb

1 to 239

1

-

Element number

bus_nb

0 to 239

0

-

Bus number

baudrate

9600 to 38400

9600

-

Communication speed

61 AF Pro- 

Description

CSA-SR-20H430NN 

-

Software version

Serial number

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Reviews: