5

NRCP2-BASE control board

Optional PD-AUX board

NRCP2-BASE board connections 

Connector/channel

Type

Terminal

Description

CH 08/J4

DI

32-33

Remote on/off switch

CH 09/J4

DI

Customer safety loop input (0 = fault, 1 = OK)

CH 10/J4

DI

73-74

Capacity limitation selection

CH 12/J5

DI

Setpoint selection

CH 13/J5

DI

Power detection input (micro-cut protection)

CH 20/J2B

DO

Reversible four-way valves

CH 21/J2B

DO

Water heater command

XXXX/J12

Series

RJ-45 series connection

- Pin 1: 

- Pin 2: ground

- Pin 3: signal -

J2A

J2B

J3

J4

J12

J3

J11

J10

J9B
J9A

J5

J6

J7A J7B J8

J1

J2

J6

J5

J4

J9

J8 J7

3.6.2 - Volt-free on/off contact
If the unit works in the remote operating mode (Remote) 
the operation of the on/off contact is as follows:

Without multiplexing

Off

On heating

On/off contact 

Open

Closed

With multiplexing

Off

On heating

On auto

On/off contact 

Open

Closed

Open

3.6.3 - Volt-free setpoint selection contact

Heating

hsp 1

hsp 2 

Set point selection contact

Open

Closed

3.6.4 - Volt-free capacity limitation selection contact

100%

Limit

Capacity limitation

Open

Closed

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Reviews: