background image

16

5.5.1 - Active setpoint
Two setpoints can be selected for the heating mode. Usually, 
the second setpoint is used for unoccupied periods. 

Depending on the current operating type, the active setpoint 
can be selected:
• 

by choosing the item in the GENUNIT menu,

• 

via the user’s volt-free contacts,

• 

via network commands

• 

via the setpoint timer program (schedule 2).

The following tables summarise the possible selections 
depending on the control types (local, remote or network) 
and the following parameters:
• 

Setpoint select in local control: item LSP_SEL in the 
GENUNIT menu permits selection of the active set-
point, if the unit is in local operating type.

• 

Operating mode.

• 

Setpoint selection contacts: setpoint selection contact 
status.

• 

Schedule 2 status: schedule for setpoint selection.

5.6 - Capacity limitation

Capacity limitation is used to restrict the unit power 
consumption. The Pro-Dialog control system allows 
limitation of the unit capacity, using user-controlled volt-
free contacts. 

Capacity limitation can result in a demand limit, a capacity 
loss or a limit demand in the night mode.

The unit capacity can never exceed the limitation setpoint 
activated by these contacts. The limitation setpoints can be 
modified in the SETPOINT menu.

5.7 - Capacity control

This function adjusts the number of active compressors to 
keep the heat exchanger water temperature at its setpoint. 
The precision with which this is achieved depends on the 
capacity of the water loop, the flow rate, the load, and the 
number of stages available on the unit. The control system 
continuously takes account of the temperature error with 
respect to the setpoint, as well as the rate of change in this 
error and the difference between entering and leaving 
water temperatures, in order to determine the optimum 
moment at which to add or withdraw a capacity stage.

If the same compressor undergoes too many starts (per 
hour) or runs below one minute each time it is started this 
automatically brings about reduction of compressor starts, 
which makes leaving water temperature control less precise.

In addition, the high pressure, low pressure or defrost 
unloading functions can also affect the temperature control 
accuracy. Compressors are started and stopped in a sequence 
designed to equalise the number of start-ups (value weighted 
by their operating time).

5.8 - Defrost function

Defrost is activated to reduce frost build-up on the air heat 
exchanger. During the defrost cycle the fans of that circuit 
are stopped, and the four-way refrigerant valve is reversed, 
forcing the circuit to cooling mode. The fan can temporarily 
be restarted during the defrost cycle. The defrost cycle is 
fully automatic and does not require any setting.

LOCAL OPERATING MODE
PARAMETER STATUS

Operating mode

Local setpoint 

selection

Time schedule 2 

status

Active setpoint

Heating

sp1

-

Heating setpoint 1

Heating

sp 2 

-

Heating setpoint 2

Heating

auto

occupied

Heating setpoint 1

Heating

auto

unoccupied

Heating setpoint 2

REMOTE OPERATING MODE
PARAMETER STATUS

Operating mode

Setpoint selection 

contact

Active setpoint

Heating

sp 1 (open)

Heating setpoint 1

Heating

sp 2 (closed)

Heating setpoint 2

5.5.2 - Reset
Reset means that the active setpoint is modified so that less 
machine capacity is required. The setpoint is decreased. 

This modification is in general a reaction to a drop in the 
load. For the Pro-Dialog control system, the source of the 
reset can be configured in the HCCONFIG table.

This reset can be based on:
• 

either the outside temperature:

 

this gives a measure of the load trends for the 
building

 

if the outside temperature decreases, the setpoint 
will again increase.

• 

or the return water temperature: 

 

this is the heat exchanger delta T and gives an 
average building load

 

if the temperature difference is reduced, the 
setpoint will decrease.

In both cases the reset parameters, i.e. slope, source and 
maximum value, are configurable in the RESETCFG menu.

Reset is a linear function based on three parameters.
• 

A reference at which reset is zero (outdoor temperature 
or delta T - no reset value).

• 

A reference at which reset is maximum (outdoor 
temperature or delta T - full reset value).

• 

The maximum reset value.

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Reviews: