background image

17

5.9 - Additional electric heater stage control

As an option, the heat pump units can control up to four 
additional electric heating stages.

The electric heating stages are activated to complement the 
heating capacity when the following conditions are satisfied:
• 

The unit uses 100% of the available heating capacity, 
or the unit is limited in its operation by a protection 
mode (low suction temperature, hot gas or defrost 
sequence in progress protection), and in all cases cannot 
satisfy the heating load.

• 

The outdoor temperature is below a configured 
threshold (see HCCONFIG configuration).

• 

Unit capacity limitation is not active.

The user may configure the last available electric heating 
stages as a safety stage. In this case, the safety stage is only 
activated in addition to the other stages if there is a 
machine fault, preventing the use of the heating capacity. 
The other electric heating stages will continue to operate 
as described above.

5.10 - Control of a boiler

The unit can control the start-up of a boiler. When the boiler 
is operating, the unit water pump is stopped. A heat pump 
unit and a boiler cannot operate together.

In this case the boiler output is activated in the following 
conditions:
• 

A fault prevents the use of the heat pump capacity.

• 

The unit works at a very low outside temperature, 
making the heat pump capacity insufficient. The outside 
air temperature threshold for use of the boiler is fixed at 
-10°C, but this value can be adjusted in the HCCONFIG 
menu.

NOTE: The control of the electric heating stages or of a 
boiler is not authorised for slave units.

5.11 - Eco function

The 61AF units include an Eco function. This function is 
based on the circulating refrigerant flow and allows 
maintaining the superheat setpoint. The function is not 
available during defrost and during the first minute of 
operation.

The objective of this function is to obtain higher performan-
ces and improved efficiency.

5.12 - Master/slave assembly

Two Pro- units can be linked to produce a master/
slave assembly. The two machines are interconnected over 
the CCN bus. All parameters required for the master/slave 
function must be configured through the Service configura-
tion menu.

Master/slave operation requires the connection of a tempe-
rature probe at the common manifold on each machine, if 
the heat exchanger leaving water temperature is controlled. 
It is not required, if the entering water temperature is 
controlled.

The master/slave assembly can operate with constant or 
variable flow. In the case of variable flow each machine 
must control its own water pump and automatically shut 
down the pump, if the cooling capacity is zero.

For constant flow operation the pumps for each unit are 
continuously operating, if the system is operating. The 
master unit can control a common pump that will be 
activated, when the system is started. In this case the slave 
unit pump is not used.

All control commands to the master/slave assembly (start/
stop, setpoint, heating mode operation, load shedding, etc.) 
are handled by the unit which is configured as the master, 
and must therefore only be applied to the master unit. They 
will be transmitted automatically to the slave unit.

The master unit can be controlled locally, remotely or by 
CCN commands. Therefore to start up the assembly, simply 
validate the Master operating type (Master) on the master 
unit. If the Master has been configured for remote control 
then use the remote volt-free contacts for unit start/stop. 

The slave unit must stay in CCN operating type continuously. 
To stop the master/slave assembly, select Local Off on the 
master unit or use the remote volt-free contacts if the unit 
has been configured for remote control.

One of the functions of the master unit (depending on its 
configuration) may be the designation, whether the master 
or slave is to be the lead machine or the follower. The roles 
of lead machine and follower will be reversed when the 
difference in running hours between the two units exceeds 
a configurable value, ensuring that the running times of the 
two units are automatically equalised.

The changeover between lead machine and follower may 
take place when the assembly is started up, or even whilst 
running. The running time balancing function is not active 
if it has not been configured: in this case the lead machine 
is always the master unit.

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...

Reviews: