The lead machine will always be started first. When the 
lead machine is at its full available capacity, start-up delay 
(configurable) is initialised on the follower. When this delay 
has expired, and if the error on the control point is greater 
than 1.7°C, the follower unit is authorised to start and the 
pump is activated. The follower will automatically use the 
master unit active setpoint. The lead machine will be held at 
its full available capacity for as long as the active capacity 
on the follower is not zero. When the follower unit receives 
a command to stop, its evaporator water pump is turned 
off with 20 seconds delay.

In the event of a communication fault between the two 
units, each shall return to an autonomous operating mode 
until the fault is cleared.  If the master unit is halted due to 
an alarm, the slave unit is authorised to start without prior 
conditions.

ATTENTION: For heat pumps operating in master/slave 
mode and using an NRCP2 board or equipped with electric 
heater stages control must be on the entering water 
temperature.

6 - DIAGNOSTICS - TROUBLESHOOTING

6.1 - General

The Pro- control system has many fault tracing aid 
functions. The local interface and its various menus give 
access to all unit operating conditions. If an operating fault 
is detected, an alarm is activated and an alarm code is 
stored in the Alarms menu, sub-menus CUR_ALRM and 
ALARMRST.

6.2 - Displaying alarms

The alarm LED on the interface (see chapter 4.1) allows 
the quick display of the unit status.
• 

A flashing LED shows that the circuit is operating but 
there is an alert.

• 

A steady LED shows that the circuit has been shut 
down due to a fault.

The ALARMRST menu on the main interface displays up 
to five fault codes that are active on the unit.

6.3 - Resetting alarms

When the cause of the alarm has been corrected the alarm 
can be reset, depending on the type, either automatically 
on return to normal, or manually when action has been 
taken on the unit. Alarms can be reset even if the unit is 
running.

This means that an alarm can be reset without stopping the 
machine. In the event of a power supply interrupt, the unit 
restarts automatically without the need for an external 
command. However, any faults active when the supply is 
interrupted are saved and may in certain cases prevent a 
circuit or a unit from restarting.

A manual reset must be run from the main interface via 
the ALARMRST menu, item RST_ALM. Depending on 
the configuration in the GENCONF menu, access to the 
item may be protected by a password.

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...