Order No. 16112-76, 01.2013. Supersedes order No.: 16112-76, 10.2010.
Manufactured by: Carrier SCS, Montluel, France.
Manufacturer reserves the right to change any product specification without notice.
Printed in the European Union.
6.4 - Alarm codes (continued)
Alarm No. Alarm
code
Alarm description
Reset type
Probable cause
Action taken by the control
Process faults (continued)
37
FC-nn
Illegal factory configuration
number
Manual
The unit size has been configured
with the wrong value
Unit is shut down
38
Sr-nn
Maintenance alert
Manual
Maintenance has been carried out
on one of the critical components
None
39
P-28
Customer safety lock
Automatic
The customer safety input has
been activated
Unit is shut down