5 - PRO-DIALOG PLUS CONTROL OPERATION

5.1 - Start/stop control

The table below summarises the unit control type and stop 
or go status with regard to the following parameters.
• 

Operating type: this is selected using the start/stop 
button on the front of the user interface.

 

LOFF: local off, L-C: local on, L-SC: local schedule, 
REM: remote, CCN: network, MAST: Master

• 

Remote start/stop contacts: these contacts are used 
when the unit is in remote operating type (Remote). 
See sections 3.6.2 and 3.6.3.

• 

CHIL_S_S: this network command relates to the unit 
start/stop when the unit is in network mode (CCN).

• 

Command set to Stop: the unit is halted. 

• 

Command set to Start: the unit runs in accordance 
with schedule 1.

• 

Start/Stop schedule: occupied or unoccupied status of 
the unit as determined by the unit start/stop program 
(Schedule 1).

• 

Master control type. This parameter is used when the 
unit is the master unit in a two chiller lead/lag arrange-
ment. The master control type determines whether the 
unit is to be controlled locally, remotely or through 
CCN (this parameter is a Service configuration).

• 

CCN emergency shutdown: if this CCN command is 
activated, it shuts the unit down whatever the active 
operating type.

• 

General alarm: the unit is totally stopped due to failure.

ACTIVE OPERATING TYPE

STATUS OF PARAMETERS

CONTROL 

TYPE

UNIT 

MODE

LOFF L-C

L-SC

REM

CCN

MAST CHIL_S_S Remote start/

stop contact

Master 

control type

Start-Stop 

time schedule

CCN emergency 

shutdown

General 

alarm

-

-

-

-

-

-

-

-

-

-

Active

-

-

Off

-

-

-

-

-

-

-

-

-

-

-

oui

-

Off

-

-

-

-

Active

-

Off

-

-

-

-

-

CCN

Off

-

-

-

-

Active

-

-

-

-

Unoccupied

-

-

CCN

Off

-

-

-

-

-

Active Off

-

CCN

-

-

-

CCN

Off

-

-

-

-

-

Active -

-

CCN

Unoccupied

-

-

CCN

Off

-

-

-

-

Active

-

On

-

-

Occupied

Disabled

No

CCN

On

-

-

-

-

-

Active On

-

CCN

Occupied

Disabled

No

CCN

On

Active -

-

-

-

-

-

-

-

-

-

-

Local

Off

-

-

Active

-

-

-

-

-

-

Unoccupied

-

-

Local

Off

-

-

-

-

-

Active -

-

Local

Unoccupied

-

-

Local

Off

-

Active -

-

-

-

-

-

-

-

Disabled

No

Local

On

-

-

Active

-

-

-

-

-

-

Occupied

Disabled

No

Local

On

-

-

-

-

-

Active -

-

Local

Occupied

Disabled

No

Local

On

-

-

-

Active -

-

-

Open

-

-

-

-

Remote

Off

-

-

-

Active -

-

-

-

-

Unoccupied

-

-

Remote

Off

-

-

-

-

-

Active -

Open

Remote

-

-

-

Remote

Off

-

-

-

-

-

Active -

-

Remote

Unoccupied

-

-

Remote

Off

-

-

-

Active -

-

-

Closed

-

Occupied

Disabled

No

Remote

On

-

-

-

-

-

Active -

Closed

Remote

Occupied

Disabled

No

Remote

On

5.2 - Heat exchanger water pump control

Master/slave control is not active, or it is active and unit is 
the master unit:
In the On, Stopping or Delay modes and if the unit is 
stopped the pump is started up and continues to operate 
for 20 seconds after the compressor has stopped. It is 
stopped if the boiler is active, but could be started up due 
to the capacity limitation function.

Master/slave function is active and unit is the slave unit:
The pump is started up, when the unit is started up and if 
the demand limit is above 1%. Otherwise the pump will be 
stopped 30 seconds after the last compressor has stopped, 
except if the configuration parameter "lag_pump" has been 
configured to turn the pump even if it has been set to stop. 
In this case the pump will run continuously.

A periodical quick pump start-up has been configured:
The water pump is started up each day at 14.00 hours for 
two seconds. 

5.3 - Control interlock contact

This contact checks the status of a loop (water flow switch 
and customer safety loop, see chapter 3.6). It prevents the 
unit from starting if it is open when the delay at start-up 
has expired. This open contact leads to an alarm shut-
down, if the unit is running. 

5.4 - Heat exchanger frost protection

The heater for the heat exchanger and the water pump 
(for units with a pump) can be energised to protect the heat 
exchanger, if it may be damaged by frost, when the unit is 
shut down for a long time at low outdoor temperature.

NOTE: Heat exchanger heater control parameters can be 
modified, using the Service configuration.

5.5 - Control point

The control point represents the water temperature that 
the unit must produce. The heat exchanger entering water 
temperature is controlled by default, but the heat exchanger 
leaving water temperature can also be controlled (requires 
a Service configuration modification).

Control point = active se reset

Summary of Contents for 61AF

Page 1: ...61AF Pro Dialog Control Operating instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP PRO DIALOG...

Page 2: ...2 Default screen characteristics 6 4 3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode...

Page 3: ...is an electronic control system to regulate units of the following types 61AF These units have only one refrigerant circuit The Pro Dialog control regulates compressor start up to control the water l...

Page 4: ...y communication via the CCN bus 3 4 The sensors Pressure sensors Two types of electronic sensors are used low pressure suction pressure and pump entering pressure optional high pressure discharge pres...

Page 5: ...X J12 Series RJ 45 series connection Pin 1 signal Pin 2 ground Pin 3 signal J2A J2B J3 J4 J12 J3 J11 J10 J9B J9A J5 J6 J7A J7B J8 J1 J2 J6 J5 J4 J9 J8 J7 3 6 2 Volt free on off contact If the unit wor...

Page 6: ...entry screen 0_ Password value 0 basic access Description The password is entered digit by digit The cursor is shown at the current digit that flashes The arrow keys modify the digit value The digit m...

Page 7: ...for the first selected character Modify value Description of the screen hsp 2 45 C Current value 46 C New value before validation Heating Setpoint 2 Item description The value is validated with the En...

Page 8: ...emperatures Pressures Setpoint Inputs Outputs Unit status Operating time Language selection Alarm menu Configuration menu Disconnection Reset of the alarms Current alarms Alarm history Time schedule H...

Page 9: ...N mode and this override value will have priority over the other limit values external or limit control 8 Control point This point can be forced in CCN mode and this override value will have priority...

Page 10: ...sor A2 st_cp_a2 nnnnn Number of start ups compressor A2 hr_fana1l nnnnn hours Number of low speed operating hours fan A1 hr_fana1h nnnnn hours Number of high speed operating hours fan A1 hr_fana2l nnn...

Page 11: ...off time schedule OCC1P02S Unit setpoint selection time schedule 4 9 15 HOLIDAY menu NAME DESCRIPTION HOLDY_01 Holiday period 1 HOLDY_02 Holiday period 2 HOLDY_03 Holiday period 3 HOLDY_04 Holiday pe...

Page 12: ...start up of the first electric heater stage ehs_defr Yes No No Quick electric heat stages for defrost 4 9 20 RESETCFG menu NAME FORMAT DEFAULT UNIT DESCRIPTION oathr_non 10 to 51 7 10 C Outside tempe...

Page 13: ...ive on the same day the occupied mode takes priority over the unoccupied period Each of the eight periods can be displayed and changed with the aid of a sub sub menu The following table shows how to a...

Page 14: ...Wednesday Thursday Friday Saturday Sunday Holiday OCCTOD6 0 00 24 00 00 00 Occupied from UNOCTOD6 0 00 24 00 00 00 Occupied until DOW7 0 1 0 Period 7 days of the week MTWTFSSH Monday Tuesday Wednesda...

Page 15: ...Off Active Unoccupied Remote Off Active Open Remote Remote Off Active Remote Unoccupied Remote Off Active Closed Occupied Disabled No Remote On Active Closed Remote Occupied Disabled No Remote On 5 2...

Page 16: ...ion of compressor starts which makes leaving water temperature control less precise In addition the high pressure low pressure or defrost unloading functions can also affect the temperature control ac...

Page 17: ...CCN bus All parameters required for the master slave function must be configured through the Service configura tion menu Master slave operation requires the connection of a tempe rature probe at the c...

Page 18: ...ctions The local interface and its various menus give access to all unit operating conditions If an operating fault is detected an alarm is activated and an alarm code is stored in the Alarms menu sub...

Page 19: ...01 Water heat exchanger frost protection Automatic if the same alarm has not tripped during the last 24 hours otherwise manual Water flow rate too low or defective thermistor Unit is shut down 19 P 05...

Page 20: ...arm No Alarm code Alarm description Reset type Probable cause Action taken by the control Process faults continued 37 FC nn Illegal factory configuration number Manual The unit size has been configure...